Plan Review Details - Permit 14120587
Plan Review Stops For Permit 14120587
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-31 Cont ID  
Sent By sciard Date 2014-12-31 Time 13:41 Rev Time 0.00
Received By sciard Date 2014-12-31 Time 13:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-12-18 Cont ID  
Sent By pleduc Date 2014-12-18 Time   Rev Time 0.00
Received By pleduc Date 2014-12-18 Time 15:40 Sent To E
Notes
2014-12-18 16:03:29THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PER SECTION 7.2.1.6.2, ACCESS-CONTROLLED EGRESS DOORS
 ARE PERMITTED PROVIDED THAT ALL SEVEN OF THE FOLLOWING
 CRITERIA ARE MET:
  
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION
 OF AN APPROACHING OCCUPANT OR LOSS OF POWER TO THE
 SENSOR.
  
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
  
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES
 HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
  
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS
 SHALL REMAIN UNLOCKED FOR NOT LESS THAN 30 SECONDS.
  
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM
 HAS BEEN MANUALLY RESET.
  
 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL
 REMAIN UNLOCKED UNTIL THE FIRE ALARM SYSTEM HAS BEEN
 MANUALLY RESET.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-31 Cont ID  
Sent By sciard Date 2014-12-31 Time 13:41 Rev Time 0.00
Received By sciard Date 2014-12-18 Time 14:13 Sent To  
Notes
2014-12-18 14:14:00ROUTED TO FIRE