| 2015-03-30 16:04:12 | BUILDING PLAN REVIEW |
| | PERMIT: 14120580 |
| | ADD: 901 45TH ST./ QUANTUM HOUSE |
| | CONT: HEDRICK BROTHERS |
| | TEL: ( 561)589-8880 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. MARCH 30/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST, PLEASE SEE SURVEY NOTE # 5 THIS SURVEY |
| | WAS PREPARED FOR DELINEATING THE EXISTING IMPROVEMENTS |
| | IN THE VICINITY OF THE QUANTUM HOUSE, NOT FOR THE |
| | DELINEATING THE AH FLOOD ZONE FROM THE B FLOOD ZONE. |
| | PLEASE PROVIDE A SURVEY FOR THIS LOCATION. THE EXISTING |
| | STRUCTURE MAY OR MAY NOT BE LOCATED IN A AH FLOOD ZONE |
| | LOOKING BETWEEN THE FIMA FLOOD MAPS AND THE COUNTY GIS, |
| | THERE IS SOME DISCREPANCY BETWEEN THE FEMA FLOOD MAP |
| | PANEL 120192- 0015-B DATED 3/01/79 IS THE CURRENT MAP. |
| | THE BASE FLOOD ELEVATION SHOWN ON THIS MAP IS 17'-0" |
| | NGVD. |
| | IF THE EXISTING BUILDING IS LOCATED IN THE AH FLOOD |
| | ZONE, THEN SUBSTANTIAL IMPROVEMENT ON THE EXISTING |
| | BUILDING THAT WILL BE ANOTHER FACTOR, SEE W.P.B. |
| | MUNI-CODE 94-611 DEFINITION FOR SUBSTANTIAL |
| | IMPROVEMENT. |
| | |
| | 2) COMPLIED. |
| | 3) PAGE 002 SHEET LIFE SAFETY 1: |
| | 3A) COMPLIED. |
| | |
| | 3B) COMPLIED. OCCUPANT LOADS ROUNDED UP |
| | 3C) 2ND REQUEST NO PLANS SUBMITTED. CONSTRUCTION TYPE |
| | INDICATES: III-B SPRINKLERED, PLEASE SPECIFY COMPLIANCE |
| | WITH FBC-B 903.3.1.1 NFPA 13 OR 903.3.1.2 NFPA 13R. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION,107.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: 5. FIRE SUPPRESSION |
| | SYSTEMS SHALL INCLUDE: EARLY WARNING SMOKE EVACUATION |
| | SYSTEMS, SCHEMATIC FIRE SPRINKLERS. |
| | |
| | 4)2ND REQUEST. THIS BUILDING QUALIFIES FOR THE RESIDENT |
| | INSPECTOR PROGRAM WITH AN AREA OF 20,000 SQ. FT. 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| | INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| | OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| | BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| | QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| | FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| | BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| | AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| | THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| | AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: (5.) |
| | FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| | FOOT. RESIDENT INSPECTOR FORMS WILL BE E-MAILED OUT TO |
| | THE CONTRACTOR CONTACT. |
| | |
| | 4A)FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 4B) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| | [email protected] |
| | |
| | 4C) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE |
| | PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND |
| | BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO |
| | SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR |
| | THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP |
| | INSPECTORS. |
| | |
| | 4D) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 5) THE PERMIT APPLICATION INDICATES A TOTAL OF |
| | 2,800,000.00 FOR THE TOTAL PROJECT PLEASE BREAK OUT THE |
| | VARIOUS PERMIT VALUES FOR ; |
| | SIGNAGE, LANDSCAPING, SITE WORK, PAVING, IRRIGATION, |
| | FIRE SPRINKLER, FIRE ALARM LOW VOLTAGE, ALL PERMITS |
| | THAT WILL NOT BE INCLUDED UNDER THE PRIME PERMIT. |
| | THE MEP & ROOFING ARE A NO FEE SUB-PERMIT. THIS WAY WE |
| | CAN FIGURE THE ACTUAL PERMIT FEES FOR THE BUILDING |
| | PERMIT. W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF |
| | PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | 108.3* BUILDING PERMIT VALUATION. |
| | RESPONSE: NOTED FOR FUTURE REFERENCE: |
| | |
| | |
| | 6) SEMI-COMPLIED. PLEASE PROVIDE WHAT THE MEAN ROOF |
| | HEIGHT IS FOR THIS PROJECT, NEITHER THE A3.00 SERIES |
| | NOR SHEET S-5 PROVIDE WHAT THE MEAN ROOF HEIGHT. SHEET |
| | S-5 THE ROOF PRESSURES ARE LOW FOR A 4:12 PITCH ROOF IN |
| | A C EXPOSURE. WILL THE ROOF PRESSURES FOR OVER THE |
| | CLEAR STORY BE ON A SEPARATE PRESSURE CHART? AGAIN |
| | PROVIDE THE MEAN ROOF HEIGHT FOR THE CLEARSTORY. FBC-B |
| | 1609.6.4.4.1/ TABLE 1609.6.2(2) |
| | |
| | 6A)SEMI COMPLIED. THE DESIGNER OF RECORD HAS PROVIDED |
| | TO CHARTS ONE FOR THE MAIN BUILDING MEAN ROOF HEIGHT, |
| | THE SECOND FOR THE CLEARSTORY. THE CHARTS FOR THE ROOF |
| | SHOW A 10 SQ. FT. AREA FOR FASTENING, THIS IS CORRECT, |
| | BUT NEITHER CHART SHOWS OPENINGS GREATER THAN 10 SQ FT |
| | FOR WINDOWS AND DOORS. CHARTS SHOULD SHOW PRESSURES, |
| | POSITIVE & NEGATIVE FOR 10, 20, 50, & 100 SQ. FT. VASD. |
| | FBC-B 1609.6.4.4.1/ TABLE 1609.6.2(2) |
| | |
| | 6B)2ND REQUEST, THE ROOF ZONES 2 & 3 BOTH INDICATE THE |
| | SAME PRESSURES AS IF THERE WAS A 3 FOOT PARAPET AROUND |
| | THE PERIMETER ELIMINATING ROOF ZONE # 3 THE ROOF |
| | SCHEMATIC SHOWS A ROOF ZONE 3 AND A CORNER DISTANCE OF |
| | 6 FT. FBC-B 1609.6.4.4.1/ TABLE 1609.6.2(2). UPDATE |
| | CHARTS. |
| | |
| | 6C) COMPLIED |
| | |
| | 7) 2ND REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | PRODUCT APPROVALS HAVE NOT IDENTIFIED OPENING SIZES, |
| | TYPE OF GLAZING, MULLIONS, PRESSURES, FASTENERS, NOR |
| | PRESSURES, CIRCLE TO IDENTIFY FOR REVIEW. |
| | NOTE: IF EITHER THE DESIGNER OF RECORD OR THE |
| | CONTRACTOR WOULD PREFER TO SUBMIT THE PRODUCT APPROVALS |
| | AFTER THE PERMIT ISSUANCE AS A DEFERRED SUBMITTAL |
| | PLEASE IN YOUR RESPONSE LETTER NOTE AS SUCH. 107.3.4.2 |
| | DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, |
| | DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF |
| | THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED |
| | SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL |
| | REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL |
| | WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 8)2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 9) COMPLIED. CHANGED LOCATION OF THE RATED WALLS AND |
| | DOORS LEADING TO THE RESIDENTIAL CORRIDOR. |
| | 10) 2ND REQUEST. PAGE 08 SHEET A1.0, PAGE 10/A1.2 AND |
| | PAGE 12/ A1.4. IN SPEAKING WITH THE DESIGNER OF RECORD, |
| | THE 2ND MEANS OF EGRESS FROM THE R1 OCCUPANCIES WAS |
| | GOING TO BE THROUGH THE DINING ROOM 157. THERE WAS TO |
| | BE NO KITCHEN IN THIS AREA AND THE EXIT DOOR WAS TO BE |
| | THE DOOR FROM THE DINING ROOM THAT LEADS TO THE |
| | EXTERIOR. THE DESIGNER OF RECORD WAS CONSIDERING THIS |
| | AREA TO BE CONSIDERED A HORIZONTAL EXIT (FBC-B 1025.2) |
| | WITH A 2 HOUR FIRE BARRIER REQUIRING THE DOUBLE DOORS |
| | AT EACH END THAT LEADS INTO THE R2 OCCUPANCY TO HAVE 1 |
| | ? HOUR OPENING PROTECTIVE, FBC-B TABLE 715.4. |
| | 11) 2ND REQUEST. RESPONSE INDICATES THEY ARE DOING |
| | NOTHING WITH THIS SECTION. THIS IS THE PORTION OF THE |
| | PROJECT WHICH IS A LEVEL II ALTERATION SHOWING WORK IN |
| | THE EXISTING KITCHEN EXISTING HALL, LAUNDRY AND HOUSE |
| | KEEPING/ STORAGE. PAGE 11/ A1.3 PARTIAL FLOOR PLANS |
| | SHOW THE LEVEL II AREA OF ALTERATION. THE 2010 FBC-B |
| | 705.2 EXCEPTION # 2 STATES MEANS OF EGRESS CONFORMING |
| | TO THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, |
| | BUILDING AND THE FLORIDA FIRE PREVENTION CODE UNDER |
| | WHICH THE BUILDING WAS CONSTRUCTED SHALL BE CONSIDERED |
| | COMPLIANT MEANS OF EGRESS IF, IN THE OPINION OF THE |
| | CODE OFFICIAL, THEY DO NOT CONSTITUTE A DISTINCT HAZARD |
| | TO LIFE. |
| | THERE IS NO FIRE BARRIERS BETWEEN THE R1 OCCUPANCY AND |
| | THE KITCHEN AS WELL AS THE REMAINDER OF THE ORIGINAL |
| | BUILDING. THE 2010 FBC-B TABLE 1018.1 REQUIRES FIRE |
| | RATED CORRIDORS AND (2) MEANS OF EGRESS TABLE 1015.1. |
| | 12) COMPLIED. OPENINGS % OF OPENINGS FROM PROPERTY LINE |
| | 13) 2ND REQUEST. THE 500 SERIES WALL SECTIONS SHOW THE |
| | USE OF ICYNENE SPRAY INSULATION, MINIMUM OF R-19. |
| | PLEASE PROVIDE COMPLIANCE WITH 2603.4.1.6 PROTECTION |
| | AGAINST IGNATION. PROVIDE THE MANUFACTURERS TEST REPORT |
| | AND CIRCLE THE SUB-SYSTEM THE DESIGNER OF RECORD WISHES |
| | TO USE. |
| | THERMAL BARRIER REQUIREMENTS 2603.4. ALSO PROVIDE THE |
| | EVALUATION REPORT FOR THIS PRODUCT WITH INSTALATION |
| | INSTRUCTIONS, CIRCLE THE SUB-SYSTEM THAT WILL BE USED |
| | FOR THIS APPLICATION AND THE MAXIMUM AMOUNTS THIS |
| | INSTALLATION CAN BE APPLIED IN THICKNESS. |
| | |
| | 14) SHEET SP1.0: |
| | 14A) 2ND REQUEST. THE RESPONSE INDICATES THAT THE PORT |
| | COCHERE IS FOR DELIVERIES . BY THE DEFINITION OF PORT |
| | COCHERE . A ROOFED STRUCTURE COVERING A DRIVEWAY AT THE |
| | ENTRANCE OF A BUILDING TO PROVIDE SHELTER WHILE |
| | ENTERING OR LEAVING A VEHICLE. A PASSAGEWAY THROUGH A |
| | BUILDING OR SCREEN WALL DESIGNED TO LET VEHICLES PASS |
| | FROM THE STREET TO AN INTERIOR COURTYARD. |
| | THE PORT COCHERE IS A COVERED DROP OFF AREA , IT WILL |
| | NEED TO MEET THE EQUIVALENT FACILITATION 2010 FBC-B |
| | EQUIVALENT OR GREATER ACCESSIBILITY AND USABILITY. THE |
| | LOADING ZONE MUST BE UNDER THE PORTCOCHERE OR SHOW |
| | EQUIVALENCY. THE PLANS WILL ALSO NEED TO SHOW THE |
| | LOADING ZONE IN FRONT OF THE PORT COCHERE. THE |
| | PASSENGER LOADING ZONE NEEDS TO COMPLY WITH BOTH |
| | SECTIONS OF THE 2010 FL ACCESS. CODE 503.2 VEHICLE |
| | PULL-UP SPACE AND 503.3 AN ACCESS AISLE. |
| | 14B) 2ND REQUEST. THE VERTICAL DISTANCE REQUIRED FOR |
| | THE PASSENGER LOADING ZONE IS 114 INCHES MINIMUM 2010 |
| | FL ACCESS. CODE 503.5. |
| | |
| | 14C)2ND REQUEST. THE RESPONSE STATED THERE WOULD BE NO |
| | PUBLIC T BUS SERVICE, THAT IS NOT WHAT WAS REQUESTED. |
| | WILL THERE BE EITHER A BUS OR VAN SERVICE THAT WILL |
| | SHUTTLE FAMILIES FROM QUANTUM HOUSE TO THE MAIN |
| | HOSPITAL CAMPUS? 2010 FL ACCESS. CODE 209.2.2 BUS |
| | LOADING ZONES. IN BUS LOADING ZONES RESTRICTED TO USE |
| | BY DESIGNATED OR SPECIFIED PUBLIC TRANSPORTATION |
| | VEHICLES, EACH BUS BAY, BUS STOP, OR OTHER AREA |
| | DESIGNATED FOR LIFT OR RAMP DEPLOYMENT SHALL COMPLY |
| | WITH 810.2. BUS BOARDING AND ALIGHTING AREAS. |
| | |
| | 14D-E)COMPLIED. |
| | 15) COMPLIED |
| | 16A) PROVISO: SHEET A-7.0 LAUNDRY DETAILS DO NOT SHOW |
| | ANY VENDING MACHINES FOR SOAP POWDER IF OFFERED THE |
| | MACHINES NEED TO BE AT A ELEVATION IN COMPLIANCE WITH |
| | REACH RANCGES ACCESS. CODE 308 AND OPERABLE PARTS |
| | ACCESS. |
| | |
| | 16B) PROVISO: THE HEIGHT OF THE WASHER AND DRYER ARE TO |
| | MEET THE REQUIREMENTS OF ACCESS. CODE 611.4 AND |
| | OPERABLE PARTS, INCLUDING DOORS, LINT SCREENS, AND |
| | DETERGENT AND BLEACH COMPARTMENTS SHALL COMPLY WITH |
| | 309. |
| | |
| | 17) COMPLIED |
| | 18) SHEET A7.2 PLEASE SHOW COMPLIANCE WITH FL ACCESS. |
| | CODE TRANSIENT LODGING GUEST ROOMS: |
| | 18A) 806.2.4 TOILET AND BATHING FACILITIES. |
| | |
| | 18B)806.3 GUEST ROOMS WITH COMMUNICATION FEATURES. |
| | |
| | 18C) 2ND REQUEST. GUEST ROOMS REQUIRED TO PROVIDE |
| | COMMUNICATION FEATURES SHALL COMPLY WITH 806.3. |
| | IN GUEST ROOMS REQUIRED TO HAVE ACCESSIBLE |
| | COMMUNICATION FEATURES, CONSIDER ENSURING COMPATIBILITY |
| | WITH ADAPTIVE EQUIPMENT USED BY PEOPLE WITH HEARING |
| | IMPAIRMENTS. TO ENSURE COMMUNICATION WITHIN THE |
| | FACILITY, AS WELL AS ON COMMERCIAL LINES, PROVIDE |
| | TELEPHONE INTERFACE JACKS THAT ARE COMPATIBLE WITH BOTH |
| | DIGITAL AND ANALOG SIGNAL USE. IF AN AUDIO HEADPHONE |
| | JACK IS PROVIDED ON A SPEAKER PHONE, A CUTOFF SWITCH |
| | CAN BE INCLUDED IN THE JACK SO THAT INSERTION OF THE |
| | JACK CUTS OFF THE SPEAKER. IF A TELEPHONE-LIKE HANDSET |
| | IS USED, THE EXTERNAL SPEAKERS CAN BE TURNED OFF WHEN |
| | THE HANDSET IS REMOVED FROM THE CRADLE. FOR HEADSET OR |
| | EXTERNAL AMPLIFICATION SYSTEM COMPATIBILITY, A STANDARD |
| | SUBMINIATURE JACK INSTALLED IN THE TELEPHONE WILL |
| | PROVIDE THE MOST FLEXIBILITY. |
| | |
| | 18D-E) COMPLIED |
| | |
| | 18F)(A) 2ND REQUEST. FL ACC CODE 224.2 GUEST ROOMS WITH |
| | MOBILITY FEATURES. IN TRANSIENT LODGING FACILITIES, |
| | GUEST ROOMS WITH MOBILITY FEATURES COMPLYING WITH 806.2 |
| | SHALL BE PROVIDED IN ACCORDANCE WITH TABLE 224.2. |
| | MINIMUM NUMBER OF REQUIRED ROOMS WITHOUT ROLL-IN |
| | SHOWERS. |
| | |
| | 18F)(B) 18F)(A) 2ND REQUEST. FL ACC CODE 224. GUEST |
| | ROOMS WITH COMMUNICATION FEATURES. IN TRANSIENT LODGING |
| | FACILITIES, GUEST ROOMS WITH COMMUNICATION FEATURES |
| | COMPLYING WITH 806.3 SHALL BE PROVIDED IN ACCORDANCE |
| | WITH TABLE 224.4. |
| | 19) COMPLIED. |
| | 20) PLEASE SHOW COMPLIANCE WITH 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| | ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| | CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| | EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| | OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| | THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| | ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | 21) 2ND REQUEST. UL U-419 DOES NOT PROVIDE A STC |
| | RATING. PLEASE SHOW COMPLIANCE WITH 1207.3 |
| | STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. |
| | |
| | 22) COMPLIED. IMPACT FEES. |
| | 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |