Plan Review Details - Permit 14120568
Plan Review Stops For Permit 14120568
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-08-12 Cont ID  
Sent By jwitmer Date 2015-08-12 Time 16:57 Rev Time 0.00
Received By jwitmer Date 2015-08-12 Time 15:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-05 Cont ID  
Sent By jwitmer Date 2015-06-05 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2015-06-05 Time 10:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-05 Cont ID  
Sent By jwitmer Date 2015-01-05 Time 15:29 Rev Time 0.00
Received By jwitmer Date 2015-01-05 Time 14:58 Sent To  
Notes
2015-01-05 15:29:40BUILDING PLAN REVIEW
 REVISION:14120568
 PERMIT: 12040748
 ADD:6651 N JOG RD
 CONT: KBR
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: MON. JAN. 05/2015
 ACTION: DENIED
  
 1) PLEASE SUBMIT THE REVIEWED SHEETS THAT PROVIDE THE
 PRESSURES FOR THE WINDOWS AND DOORS, THE LOCATION OF
 THE WINDOW AND DOORS ON THE BUILDING EITHER A WALL ZONE
 4 (INTERIOR) OR ZONE 5 A END ZONE. PLEASE CIRCLE THE
 SUB-SYSTEM, DOOR AND TYPE OF LOCKING MECHANISM OR
 WINDOW TYPE, GLAZING, SIZE OF THE UNIT, FASTENERS AND
 PRESSURES FOR UNIT.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.4 EXTERIOR WALL
 ENVELOPE. CONSTRUCTION DOCUMENTS FOR ALL BUILDINGS
 SHALL DESCRIBE THE EXTERIOR WALL ENVELOPE IN SUFFICIENT
 DETAIL TO DETERMINE COMPLIANCE WITH THIS CODE. THE
 CONSTRUCTION DOCUMENTS SHALL PROVIDE DETAILS OF THE
 EXTERIOR WALL ENVELOPE AS REQUIRED.. THE CONSTRUCTION
 DOCUMENTS SHALL INCLUDE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS THAT PROVIDE SUPPORTING DOCUMENTATION THAT
 THE PROPOSED PENETRATION AND OPENING DETAILS DESCRIBED
 IN THE CONSTRUCTION DOCUMENTS MAINTAIN THE WEATHER
 RESISTANCE OF THE EXTERIOR WALL ENVELOPE. THE
 SUPPORTING DOCUMENTATION SHALL FULLY DESCRIBE THE
 EXTERIOR WALL SYSTEM WHICH WAS TESTED, WHERE
 APPLICABLE, AS WELL AS THE TEST PROCEDURE USED.
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-08-12 Cont ID  
Sent By jwitmer Date 2015-08-12 Time 16:57 Rev Time 0.00
Received By jwitmer Date 2015-08-03 Time 15:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-05 Cont ID  
Sent By jwitmer Date 2015-06-05 Time 10:39 Rev Time 0.00
Received By jwitmer Date 2015-05-28 Time 07:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-05 Cont ID  
Sent By jwitmer Date 2015-01-05 Time 15:29 Rev Time 0.00
Received By jwitmer Date 2014-12-22 Time 11:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2015-09-16 Cont ID  
Sent By skennedy Date 2015-09-16 Time 15:09 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved