Plan Review Details - Permit 14120546
Plan Review Stops For Permit 14120546
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-02-13 Cont ID  
Sent By JWITMER Date 2015-02-13 Time 15:58 Rev Time 0.00
Received By jwitmer Date 2015-02-13 Time 15:33 Sent To  
Notes
2015-02-13 16:00:32BUILDING PLAN REVIEW
 PERMIT: 14120546
 ADD: 1781 PALM BEACH LAKES # W233
 CONT: TBD
 TEL: (561)373-3902
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. FEB. 13/ 2015
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A400 DETAIL 3 & 4 SHOW THE ACCESSIBLE BENCH,
 WHAT THE DETAIL IS MISSING IS COMPLIANCE WITH FL ACC.
 CODE 903.4 BACK SUPPORT.
 THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE
 AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 INCHES
 (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A POINT 2
 INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE TO A
 POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM)
 MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED
 HORIZONTALLY.
  
 2) SHEET A104 THE FLOOR PLAN INDICATES A CASH WRAP BUT
 THERE ARE NO PLANS SHOWING COMPLIANCE WITH;
 2010 FL ACCESSIBILITY CODE 904.4 SALES AND SERVICE
 COUNTERS. SALES COUNTERS AND SERVICE COUNTERS SHALL
 COMPLY WITH 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION
 OF THE COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE
 SALES OR SERVICE COUNTER TOP.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-15 Cont ID  
Sent By jwitmer Date 2015-01-15 Time 16:02 Rev Time 0.00
Received By jwitmer Date 2015-01-15 Time 15:39 Sent To  
Notes
2015-01-15 16:02:43BUILDING PLAN REVIEW
 PERMIT: 14120546
 ADD: 1781 PALM BEACH LAKES # W233
 CONT: TBD
 TEL: (561)373-3902
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JAN. 15/ 2015
 ACTION: DENIED
  
 1) THE COVER SHEET INDICATES A OCCUPANT LOAD OF 123
 WHICH REQUIRES 2 EXITS. THE 2ND EXIT IS THROUGH THE
 STOREAGE ROOM, PLEASE PROVIDE COMPLIANCE WITH :
  
 2010 FBC-B SECTION 1014.2 EGRESS THROUGH INTERVENING
 SPACES. EGRESS THROUGH INTERVENING SPACES SHALL COMPLY
 WITH THIS SECTION.
 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
 EXCEPTIONS:
  
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
  
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
  
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
  
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
  
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN
 THE REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL
 AREA TO THE EXIT WITHOUT OBSTRUCTIONS.
  
 2) SHEET A400 DETAIL 3 & 4 SHOW THE ACCESSIBLE BENCH,
 WHAT THE DETAIL IS MISSING IS COMPLIANCE WITH FL ACC.
 CODE 903.4 BACK SUPPORT.
 THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE
 AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 INCHES
 (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A POINT 2
 INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE TO A
 POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM)
 MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED
 HORIZONTALLY.
  
 3) SHEET A104 THE FLOOR PLAN INDICATES A CASH WRAP BUT
 THERE ARE NO PLANS SHOWING COMPLIANCE WITH;
 2010 FL ACCESSIBILITY CODE 904.4 SALES AND SERVICE
 COUNTERS. SALES COUNTERS AND SERVICE COUNTERS SHALL
 COMPLY WITH 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION
 OF THE COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE
 SALES OR SERVICE COUNTER TOP.
  
 4) SHEET A106 INDICATES ROOF FRAMING FOR ADDITIONAL
 ROOF TOP AIR HANDLERS, SHEET MP 001 INDICATES THERE ARE
 (2) EXISTING UNITS, SHEET MP101 ONLY SHOWS (2) DOWN
 UNITS? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-02-12 Cont ID  
Sent By DHAYES Date 2015-02-12 Time 15:02 Rev Time 0.00
Received By dhayes Date 2015-02-12 Time 13:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-01-26 Cont ID  
Sent By dhayes Date 2015-01-26 Time 12:08 Rev Time 0.00
Received By dhayes Date 2015-01-26 Time 10:55 Sent To  
Notes
2015-01-26 12:08:261/26/2015
 PROJECT: BROOKS BROTHERS
 PERMIT#: 14120546
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) SHEET E001.
 ADD NOTE TO ELECTRICAL RISER DIAGRAM INDICATING THE
 REQUIREMENT FOR ARC FLASH PROTECTION WARNING LABELS.
 NEC 110.16, 110.22
 VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A
 FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL
 CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
 CLARIFY THE INSTALLATION OF A MCB IN PANEL RP2. THE
 RISER DIGRAM INDICATES PANEL RP2 IS MLO ONLY. THE PANEL
 SCHEDULE CALLS FOR A MCB REMOVE THE INCONSISTANCY. NEC
 450.3(B)
 CLARIFY AND PROVIDE ADDITIONAL DETAIL FOR THE
 INSTALLATION OF THE GROUNDING OF THE RELOCATED 75KVA
 TRANSFORMER.
  
 2) SHEET E101. PLEASE CLARIFY HOW THE SITE SIGNAGE IS
 PROPOSED TO BE CONTROLED AND REMOVE THE CONFLICTING
 NOTES. WPB AMENDMENTS TO FBC 107.3
 A.) LIGHTING CONTROL NOTES. SITE SIGNAGE- TIMECLOCK:
 ADDITIONAL TIMECLOCK FOR SITE SIGNAGE. (NOT APPLICABLE
 TO THIS PROJECT.)
 B.) KEY NOTES: 10) NEW JUNCTION BOX FOR STORE FRONT
 SIGNAGE. COORDINATE REQUIREMENTS WITH PROJECT MANAGER.
 ROUTE ELECTRICAL CIRCUIT THROUGH TIMECLOCK.
 C.) SEE LIGHTING CONTROL SCHEMATIC THIS SHEET. THE
 SCHEMATIC DOES INDICATE PERIMETER DISPLAY LIGHTING AND
 SIGN ON CHANNEL 1 OF PROPOSED TIMECLOCK ON CIRCUIT RP
 28.
 D.) HOWEVER UNDER CONTROL DESCRIPTION NOTES SAYS
 TIMECLOCK FOR SITE SIGNAGE (NOT USED.)
  
 3) SHEET E102
 VERIFY AND INDICATE THE EXISTING OUTLETS FOR THE
 EXISTING ELECTRIC DRINKING FOUNTAINS SHALL BE GFI
 PROTECTED. NEC 422.52
  
 4) SHEET E102A
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR AUDIO/VIDEO. ACCESS/EGRESS CONTROL,
 SECURITY, CCTV, NETWORK, DATA, AND, COMMUNICATION
 SYSTEMS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-01-26 Cont ID  
Sent By scaldero Date 2015-01-26 Time 16:41 Rev Time 0.00
Received By scaldero Date 2015-01-26 Time 16:30 Sent To  
Notes
2015-01-26 16:40:54PERMIT #14120546
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO:
 PER NFPA 101, SECTION 36.2.5.11 EXIT ACCESS IN CLASS A
 AND CLASS B MERCANTILE OCCUPANCIES THAT ARE PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.1.1(1), AND
 EXIT ACCESS IN ALL CLASS C MERCANTILE OCCUPANCIES,
 SHALL BE PERMITTED TO PASS THROUGH STOREROOMS, PROVIDED
 THAT ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1)NOT MORE THAN 50 PERCENT OF EXIT ACCESS SHALL BE
 PROVIDED THROUGH THE STOREROOM.
 (2)THE STOREROOM SHALL NOT BE SUBJECT TO LOCKING.
 (3)THE MAIN AISLE THROUGH THE STOREROOM SHALL BE NOT
 LESS THAN 44 IN. (1120 MM) WIDE.
 (4)THE PATH OF TRAVEL THROUGH THE STOREROOM SHALL BE
 DEFINED, DIRECT, AND CONTINUOUSLY MAINTAINED IN AN
 UNOBSTRUCTED CONDITION.
  
 ADDITIONAL EMERGENCY LIGHTING MAY BE NEEDED FOR
 DRESSING ROOMS AREA. TO BE DETERMINED IN THE FIELD.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-15 Cont ID  
Sent By tklarge Date 2015-02-15 Time 05:07 Rev Time 0.00
Received By tklarge Date 2015-02-05 Time 07:36 Sent To  
Notes
2015-02-06 07:38:34B31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-05 Cont ID  
Sent By hmoser Date 2015-02-05 Time 07:56 Rev Time 0.00
Received By hmoser Date 2014-12-16 Time 14:32 Sent To  
Notes
2014-12-16 16:17:17B31.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-12-16 Cont ID  
Sent By jwitmer Date 2014-12-16 Time 16:25 Rev Time 0.00
Received By jwitmer Date 2014-12-16 Time 16:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-02-05 Cont ID  
Sent By hmoser Date 2015-02-05 Time 07:56 Rev Time 0.00
Received By hmoser Date 2015-02-05 Time 06:33 Sent To  
Notes
2015-02-05 07:55:38PASS PROVISO
 REFER TO SECTION 1509.7 MECHANICAL UNITS
 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805- 6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-02-15 Cont ID  
Sent By TKLARGE Date 2015-02-15 Time 05:07 Rev Time 0.00
Received By tklarge Date 2015-02-15 Time 04:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-12-20 Cont ID  
Sent By tklarge Date 2014-12-20 Time 11:44 Rev Time 0.00
Received By tklarge Date 2014-12-20 Time 11:26 Sent To  
Notes
2014-12-20 11:44:20TOILET FACILITIES SHALL BE PROVIDED FOR MALES AND
 FEMALES PER THE 2010 FBC SEC.403.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-01-16 Cont ID  
Sent By eschneid Date 2015-01-16 Time 13:25 Rev Time 0.25
Received By eschneid Date 2015-01-16 Time 13:25 Sent To  
Notes
***NONE***