Plan Review Details - Permit 14120514
Plan Review Stops For Permit 14120514
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-03-19 Cont ID  
Sent By jgomez Date 2015-03-19 Time 07:17 Rev Time 0.00
Received By jgomez Date 2015-03-18 Time 18:09 Sent To  
Notes
2015-03-18 18:22:21BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- A) FLOOD VENTS: "AT LEAST TWO OPENINGS ON DIFFERENT
 SIDES OF EACH ENCLOSED AREA" ARE REQUIRED BY SEC.
 R322.2.2 OF 2010 FBC-RESIDENTIAL. REVISE PLANS AS
 REQUIRED.
 B) PROVIDE COMPLETE INFORMATION FOR THE DESIGN OF THE
 FLOOD VENTS. SEE FEMA TECHNICAL BULLETIN 1 FOR LOCATION
 AND DESIGN REQUIREMENTS OF FLOOD VENTS.
 C) PROVIDE ICC FLOOD VENTS EVALUATION REPORT (2
 COPIES).
  
 2- WINDOW #19 NEEDS TO COMPLY WITH LIFE SAFETY ISSUES
 OF SEC. R612.2 OF 2010 FBC-RESIDENTIAL. REVISE BUILDING
 SECTION A-A/A4 AND SECOND FLOOR ELECTRICAL PLAN.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) USP TRUSS CONNECTOR TC-4 (HGAM10). FL819 IS NOT FOR
 2010 CODE VERSION. PROVIDE 2010 CODE VERSION OR APPLY
 FOR LOCAL PRODUCT APPROVAL.
  
 B) PRECAST LINTELS. NOA 12-0209.13 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-02-27 Cont ID  
Sent By jgomez Date 2015-02-27 Time 08:13 Rev Time 0.00
Received By jgomez Date 2015-02-26 Time 18:52 Sent To  
Notes
2015-02-26 18:54:34 
 *********REVIEW IN PROGRESS....
  
 VERY IMPORTANT NEW COMMENT:
 REVISED SURVEY SHOWING THE PROPOSED DRAINAGE FLOW
 DIRECTIONAL ARROW ALSO SHOWS THE GARAGE WITH A FINISHED
 FLOOR ELEVATION OF 7.05". THIS PROPERTY IS LOCATED IN
 FLOOD ZONE A5 WITH A BASED FLOOD ELEVATION OF 7.0'. THE
 MIN. GARAGE FINISH FLOOR ELEVATION REQUIRED IS 7.6".
 OTHERWISE COMPLY WITH THE REQUIREMENTS OF SEC. R322 OF
 2010 FBC. REVISE ALL PLANS AS REQUIRED.
  
 FROM PREVIOUS COMMENTS:
 1- SHEET A-2: WINDOW #19 BY THE SITTING AREA NEEDS TO
 COMPLY WITH LIFE SAFETY ISSUES OF SEC. R612.2 OF 2010
 FBC-RESIDENTIAL. REVISE PLANS AS REQUIRED. NOT
 ADDRESSED CORRECTLY. LIFE-SAFETY ISSUE IS FALLING FROM
 WINDOW NOT SAFETY GLASS.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SHINGLES SELF ADHERING UNDERLAYMENT AS SPECIFIED ON
 PLANS. NOA 11-0815.05 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. NEED CURRENT NOA.
  
 B) ALL USP STRUCTURAL CONNECTORS SPECIFIED ON PLANS AND
 SECTION/DETAILS. PROVIDE PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR LIST THE
 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE SPECIFIED
 CONNECTOR.
 NOTE: THERE ARE TWO SITE SPECIFIC CONNECTORS SHOWN ON
 SHEET S-4. NEED TO PROVIDE COMPLETE ENGINEERING PACKAGE
 FOR SITE SPECIFIC CONNECTORS APPROVAL. AND, THE
 ENGINEER (JAMES F. COLLINS JR.) NEED TO USE CURRENT
 SEAL THAT READS "LICENSE" INSTEAD OF "CERTIFICATE" AS
 REQUIRED BY FLORIDA BOARD OF PROFESSIONAL ENGINEERS
 WHEN SUBMITTING ENGINEERING PACKAGE FOR SITE SPECIFIC
 APPROVAL.
  
 C) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 D) ROOF SHINGLES. NOA 13-0419.04 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA.
  
 E) NEW COMMENT: "FIBERGLASS SHINGLE ROOF ADHESIVE" AS
 SPECIFIED ON SHEET A-4 WALL SECTIONS.
  
 3- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS. SEC. SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 4- GEO-TECHNICAL REPORT SUBMITTED: REVISE PROJECT
 DESCRIPTION. PLANS SUBMITTED ARE FOR A TWO STORY
 CONCRETE BLOCK HOUSE NOT ONE STORY RESIDENCE. REVISE
 ANY RECOMMENDATIONS IF REQUIRED BY THE CORRECT SCOPE OF
 WORK. SEC. R401.2 OF 2010 FBC-RESIDENTIAL.
  
 5- TRUSS PACKAGE:
 A) TRUSS PACKAGE TO BE REVIEWED BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL.
 B) NEED ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 FL. ST.
 C) PROVIDE COMPLETE INFORMATION FOR THE ENGINEER OF
 RECORD. SEC. 61G15-31.003.
 D) TRUSS LAYOUT NEED TO BE SIGNED AND SEALED. SEC.
 61G15-31.003
  
 NOTE: PROPERTY IS LOCATED IN FLOOD ZONE A5. ELEVATION
 CERTIFICATES WILL BE REQUIRED DURING CONSTRUCTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-06 Cont ID  
Sent By jgomez Date 2015-01-06 Time 12:36 Rev Time 0.00
Received By jgomez Date 2015-01-06 Time 12:31 Sent To  
Notes
2015-01-06 12:46:18NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- A) DESIGNER OF RECORD TO SPECIFY ALL LIVE AND DEAD
 LOADS, INCLUDING THE ATTIC LIVE LOAD REQUIRED BY TABLE
 R301.5 OF 2010 FBC-RESIDENTIAL.
 NOTE: ALSO, TAKE INTO CONSIDERATION THE 1" GYPCRETE
 SLAB SPECIFIED ON TYPICAL 2 STORY WALL SECTION ON SHEET
 A-4.
  
 B) STRUCTURAL DRAWINGS TO SHOW THE ADDITIONAL 1"
 GYPCRETE SLAB. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 3- POWDER ROOM ON FIRST FLOOR NEEDS A DOOR THAT PROVIDE
 29" CLEAR OPENING AS REQUIRED BY SEC. R320 OF 2010
 FBC-RESIDENTIAL. REVISE SIZE AS REQUIRED.
  
 4- PROVIDE SPECIFICATIONS FOR DOOR LEADING FROM GARAGE
 TO THE INTERIOR OF THE HOUSE SHOWING COMPLIANCE WITH
 SEC. R302.5.1 OF 2010 FBC-RESIDENTIAL.
  
 5- REVISE ATTIC ACCESS SECTION SECTION ON SHEET A-2.
 OPENING TO COMPLY WITH SECTION R807 OF 2010 FBC.
  
 6- SHEET A-2: WINDOW #19 BY THE SITTING AREA NEEDS TO
 COMPLY WITH LIFE SAFETY ISSUES OF SEC. R612.2 OF 2010
 FBC-RESIDENTIAL. REVISE PLANS AS REQUIRED.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SHINGLES SELF ADHERING UNDERLAYMENT AS SPECIFIED ON
 PLANS.
  
 B) ALL USP STRUCTURAL CONNECTORS SPECIFIED ON PLANS AND
 SECTION/DETAILS. PROVIDE PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR LIST THE
 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE SPECIFIED
 CONNECTOR. NOTE: ONLY ONE OF THE FLORIDA PRODUCT
 APPROVAL NUMBERS LISTED ON THE TRUSS SCHEDULE IS
 CURRENT. NEED TO REVISE THE REST OF THEM. ALSO, PROVIDE
 THE PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR ON ALL OTHER DETAILS.
  
 C) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 D) ROOF SHINGLES. NOA 11-1122.04 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS TO FBC.
  
 9- TYPICAL WALL SECTIONS ON SHEET A-4: CLARIFY ROOFING
 MATERIAL. SHINGLES OR ROOF TILE. BOTH ARE SPECIFIED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 10- PROVIDE ICC EVALUATION REPORT (OR ANY OTHER
 APPROVED REPORT) FOR ICYNENE INSULATION AS SPECIFIED ON
 PLANS TO SHOW COMPLIANCE WITH SEC. R316 OF 2010
 FBC-RESIDENTIAL.
  
 11- PROVIDE HANDRAILS AND GUARDRAILS DETAILS SHOWING
 COMPLIANCE WITH THE LIVE LOADS OF TABLE R301.5 OF 2010
 FBC-RESIDENTIAL.
  
 12- PROVIDE SURFACE DRAINAGE PLAN SHOWING COMPLIANCE
 WITH SEC. R401.3 OF 2010 FBC-RESIDENTIAL.
  
 13- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES. VALUATION UPDATED TO $294,379. THE
 PERMIT FEE BALANCE IS $5065.67.
  
 14- GEO-TECHNICAL REPORT SUBMITTED:
 A) NEEDS THE ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 FL. ST.
  
 B) REVISE PROJECT DESCRIPTION. PLANS SUBMITTED ARE FOR
 A TWO STORY CONCRETE BLOCK HOUSE NOT ONE STORY
 RESIDENCE. SEC. R401.2 OF 2010 FBC-RESIDENTIAL.
  
 15- FOOTINGS SHOWN ON SHEET A-4 AND S-1 DON'T MATCH
 RECOMMENDATIONS SPECIFIED ON THE GEOTECHNICAL REPORT.
 SEE PAGE 8 OF 9 OF THE GEO-TECHNICAL REPORT FOR THE
 RECOMMENDED MIN. DEPTH BELOW FINISH GRADE AND
 STRUCTURAL SEPARATION BETWEEN FOOTINGS AND FLOOR SLAB.
 DESIGNER OF RECORD TO REVIEW REVISED REPORT (SEE
 COMMENT #14(B) ABOVE) AND PROVIDE MODIFICATIONS AS
 REQUIRED. ALSO, TAKE INTO CONSIDERATION THAT THIS
 PROPERTY IS LOCATED IN FLOOD ZONE A5. SEC. R401.2 OF
 2010 FBC-RESIDENTIAL.
  
 16- PROVIDE WINDOWS AND DOORS MANUFACTURER SPECS
 SHOWING COMPLIANCE WITH THE U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS. SEE SEC. 303.1.3
 OF 2010 FBC-ENERGY CONSERVATION.
 ***NOTE: THIS IS ONLY REQUESTED WHEN THE ENERGY
 CALCULATIONS USE FENESTRATION FACTORS OTHER THAN THE
 DEFAULT FACTORS. THIS WILL AVOID CONFLICTS OR DELAYS
 DURING CONSTRUCTION.
  
 17- REVISE ENERGY CALCULATIONS. THE STREET IS NOT LOT
 18 GREGORY RD. PROVIDE CORRECT ADDRESS AND PROVIDE
 COMPLETE INFORMATION INCLUDING OWNER, BUILDER NAME,
 PERMIT OFFICE AND JURISDICTION NUMBER. SEC. 103.2.1.1.2
 OF 2010 FBC-ENERGY CONSERVATION.
  
 18-TRUSS PACKAGE:
 A) TRUSS PACKAGE TO BE REVIEWED BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL.
 B) NEED ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 FL. ST.
 C) PROVIDE COMPLETE INFORMATION FOR THE ENGINEER OF
 RECORD. SEC. 61G15-31.003.
 D) TRUSS LAYOUT NEED TO BE SIGNED AND SEALED. SEC.
 61G15-31.003
 NOTE: TRUSS PACKAGE DOES NO NEED TO BE RE-SUBMITTED TO
 THIS OFFICE. AFTER ALL CORRECTIONS ARE DONE, TRUSS
 PACKAGE MAY BE DELIVERED TO THE BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
  
 19- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 DECORATIVE SHUTTERS SHOWN ON ELEVATIONS. SPECIFY
 MATERIALS AND COMPLETE INSTALLATION DETAILS TO SHOW
 COMPLIANCE WITH SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
  
 NOTE: PROPERTY IS LOCATED IN FLOOD ZONE A5. ELEVATION
 CERTIFICATES WILL BE REQUIRED DURING CONSTRUCTION.
  
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REMOVE AND REPLACE ANY REVISED SHEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-05 Cont ID  
Sent By dhayes Date 2015-03-05 Time 11:15 Rev Time 0.00
Received By dhayes Date 2015-03-05 Time 11:15 Sent To  
Notes
2015-03-05 11:23:001) ALL NEW 120-VOLT, SINGLE PHASE, 15 AND 20 AMP BRANCH
 CIRCUITS SUPPLYING OUTLETS INSTALLED IN THE DWELLING
 UNIT SHALL BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT
 INTERRUPTER FOR THE PROTECTION OF THE BRANCH CIRCUIT.
 NEC 210.12
  
 2) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 3) VERIFY THE WATER HEATER HAS THE REQUIRED ELECTRIC
 DISCONNECT. NEC 422.31
  
 4) SUFFICIENT ACCESS AND WORKING SPACE SHALL BE
 PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT
 TO PERMIT READY AND SAFE OPERATION AND MAINTENANCE OF
 SUCH EQUIPMENT. 110.26
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-02 Cont ID  
Sent By skennedy Date 2015-02-02 Time 15:33 Rev Time 0.00
Received By skennedy Date 2015-02-02 Time 15:33 Sent To  
Notes
2015-02-02 15:34:501ST REVIEW: FBC 2010
  
 ELECTRIC FAILED WITHOUT FULL REVIEW TO ALLOW APPLICANT
 TO RESUBMIT AS HE ELECTED TO DO SO WHILE VISITING THE
 OFFICE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-03-19 Cont ID  
Sent By jgomez Date 2015-03-19 Time 08:00 Rev Time 0.00
Received By jgomez Date 2015-03-09 Time   Sent To  
Notes
2015-03-09 17:39:05SENT TO J. GOMEZ'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-05 Cont ID  
Sent By dhayes Date 2015-03-05 Time 11:23 Rev Time 0.00
Received By dhayes Date 2015-02-02 Time 16:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-02 Cont ID  
Sent By skennedy Date 2015-02-02 Time 15:33 Rev Time 0.00
Received By skennedy Date 2014-12-12 Time 16:47 Sent To  
Notes
2014-12-12 16:47:09R23
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2015-03-19 Cont ID  
Sent By jgomez Date 2015-03-19 Time 12:09 Rev Time 0.00
Received By jgomez Date 2015-03-19 Time 12:09 Sent To  
Notes
2015-03-19 12:10:46$417.24 PAID. MU-2015-5399.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-03-19 Cont ID  
Sent By jgomez Date 2015-03-19 Time 07:54 Rev Time 0.00
Received By jgomez Date 2015-03-19 Time 07:53 Sent To  
Notes
2015-03-19 07:54:371-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES REVIEW. BRING BACK COUNTY STAMPED PLANS
 AND COPY OF PAID RECEIPT. COUNTY IMPACT FEE ORDINANCE
 OF THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-02-27 Cont ID  
Sent By jgomez Date 2015-02-27 Time 13:36 Rev Time 0.00
Received By jgomez Date 2015-02-27 Time 13:36 Sent To  
Notes
2015-02-27 13:37:031-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES REVIEW. BRING BACK COUNTY STAMPED PLANS
 AND COPY OF PAID RECEIPT. COUNTY IMPACT FEE ORDINANCE
 OF THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-01-06 Cont ID  
Sent By jgomez Date 2015-01-06 Time 12:51 Rev Time 0.00
Received By jgomez Date 2015-01-06 Time 12:51 Sent To  
Notes
2015-01-06 12:53:111-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES REVIEW. BRING BACK COUNTY STAMPED PLANS
 AND COPY OF PAID RECEIPT. COUNTY IMPACT FEE ORDINANCE
 OF THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-02-27 Cont ID  
Sent By jgomez Date 2015-02-27 Time 13:41 Rev Time 0.00
Received By jgomez Date 2015-02-27 Time 13:41 Sent To  
Notes
2015-02-27 13:50:26 
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-01-07 Cont ID  
Sent By jgomez Date 2015-01-07 Time 16:51 Rev Time 0.00
Received By jgomez Date 2015-01-07 Time 16:51 Sent To  
Notes
2015-01-07 16:52:00NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- A/C EQUIPMENT SIZING CALCULATIONS SUBMITTED ARE DONE
 FOR WORST CASE SCENARIO. SEC. 403.6 OF 2010 FBC-ENERGY
 CONSERVATION DOESN'T ALLOW WORST CASE SCENARIO.
 CALCULATIONS NEED TO BE REVISED BASED ON THE ACTUAL
 BUILDING ORIENTATION.
  
 ***NOTE: PROVIDE CORRECT ADDRESS. THIS IS NOT LOT 18
 GREGORY RD.
  
 2- A/C PLAN:
 A) PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 B) FAMILY ROOM NEEDS TO COMPLY WITH THE BALANCED RETURN
 AIR AS REQUIRED BY SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL. THIS ROOM CAN BE CLOSED WHEN ALL DOORS
 ARE CLOSED.
  
 C) SIZE OF TRANSFER DUCT SPECIFIED FOR THE MASTER
 BEDROOM DOESN'T COMPLY WITH SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL. NEED TO CONSIDER ALL THE SUPPLY AIR
 INTO THE MASTER SUITE, INCLUDING CLOSETS AND BATHROOM
 TO SIZE THE TRANSFER DUCT. REVISE SIZE AS REQUIRED.
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2015-03-19 Cont ID  
Sent By jgomez Date 2015-03-19 Time 10:00 Rev Time 0.00
Received By jgomez Date 2015-03-19 Time 10:00 Sent To  
Notes
2015-03-19 10:01:24BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- A) FLOOD VENTS: "AT LEAST TWO OPENINGS ON DIFFERENT
 SIDES OF EACH ENCLOSED AREA" ARE REQUIRED BY SEC.
 R322.2.2 OF 2010 FBC-RESIDENTIAL. REVISE PLANS AS
 REQUIRED.
 B) PROVIDE COMPLETE INFORMATION FOR THE DESIGN OF THE
 FLOOD VENTS. SEE FEMA TECHNICAL BULLETIN 1 FOR LOCATION
 AND DESIGN REQUIREMENTS OF FLOOD VENTS.
 C) PROVIDE ICC FLOOD VENT EVALUATION REPORT (2 COPIES)
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-12-20 Cont ID  
Sent By tklarge Date 2014-12-20 Time 10:00 Rev Time 0.00
Received By tklarge Date 2014-12-20 Time 09:36 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2015-03-19 Cont ID  
Sent By jgomez Date 2015-03-19 Time 07:55 Rev Time 0.00
Received By jgomez Date 2015-03-19 Time 07:55 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2015-02-27 Cont ID  
Sent By jgomez Date 2015-02-27 Time 13:39 Rev Time 0.00
Received By jgomez Date 2015-02-27 Time 13:39 Sent To  
Notes
2015-02-27 13:40:37PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY DCA
 RULE 9N-3 FOR:
  
 A) SHINGLES SELF ADHERING UNDERLAYMENT AS SPECIFIED ON
 PLANS. NOA 11-0815.05 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. NEED CURRENT NOA.
  
 B) ROOF SHINGLES. NOA 13-0419.04 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-01-07 Cont ID  
Sent By jgomez Date 2015-01-07 Time 16:48 Rev Time 0.00
Received By jgomez Date 2015-01-07 Time 16:48 Sent To  
Notes
2015-01-07 16:50:49PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY DCA
 RULE 9N-3 FOR:
  
 A) SHINGLES SELF ADHERING UNDERLAYMENT AS SPECIFIED ON
 PLANS. NOA 11-0815.05 WAS SUPERSEDED BY MIAMI-DADE.
 NEED CURRENT NOA.
  
 B) ROOF SHINGLES. NOA 13-0419.04 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-02-10 Cont ID  
Sent By sgraham Date 2015-02-10 Time 11:34 Rev Time 0.00
Received By sgraham Date 2015-02-10 Time 11:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-30 Cont ID  
Sent By sgraham Date 2014-12-30 Time 09:57 Rev Time 0.00
Received By sgraham Date 2014-12-30 Time 09:57 Sent To  
Notes
2014-12-30 09:59:4712/30/14 ZONING FAILED
  
 1. MAXIMUM BUILDING HEIGHT IS 30' FEET, BUT YOU MUST
 MEASURE FROM THE GRADE NOT THE FINISHED FLOOR. YOU A
 LITTLE OVER THE MAX ON THE ROOF


Account Summary | Usage Policy | Privacy Policy