Sent To |
|
|
| Notes |
| 2014-12-16 10:10:39 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) THE MAXIMUM DESIGN PRESSURE FOR THE ROOFING SYSTEM | | | SPECIFIED ON PAGE 14 OF NOA NO. 14-0224.03 IS -60 PSF. | | | THIS IS NOT ADEQUATE FOR ALL OF THE ROOF AREAS. SUBMIT | | | TWO SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | ENHANCED ROOF FASTENING AS REQUIRED BY GENERAL | | | LIMITATION NUMBER 7 ON PAGE 16 OF THE NOA. |
|
|
|