| 2014-12-19 12:16:02 | ****CORRECTIONS**** |
| | REVISED TO ADDRESS CONCERNS RAISED BY APPLICANT |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. FBC 107, PLANS ARE DIFFICULT TO READ DUE TO THE SIZE |
| | OF FONT AND PLAN PAGE SIZE. FBC 107 REQUIRES A MINIMUM |
| | OF 1/8" SCALE. A SMALLER SCALE THAN 1/8" FOR THE |
| | LOCATION PLAN WOULD BE ACCEPTABLE AS LONG AS IT IS |
| | EASILY LEGIBLE. THE PLAN SUBMITTED HAS A LOT OF TEXT |
| | AND DETAIL UNNECESSARY FOR THIS JOB. THE TEXT DESCIBING |
| | THE WORK IS IN RED, ON TOP OF OTHER TEXT OR GRAPHICS. |
| | THE STRUCTURAL DETAILS ARE SMALL AND DIFFICULT TO READ |
| | EASILY. |
| | |
| | AS THIS IS A COMMERCIAL BUILDING, WE ARE REQUIRED TO |
| | RETAIN (AND PROVIDE UPON REQUEST) THE PLANS. FOR PLAN |
| | REVIEW, INSPECTIONS, AND RECORDS RETENTION, |
| | LEGIBLE/READABLE PLANS ARE REQUIRED. |
| | |
| | 2. PLEASE LABEL THE DETAILS. THEY SHOULD BE LABELED |
| | PLAN, SECTION, WITH A SECTION INDICATOR THROUGH A |
| | PLANTER DETAL. |
| | |
| | 3. PER ANA MARIA APONTE, PLANNER, PLEASE REVISE PLAN TO |
| | MORE CLEARLY SHOW INTENT. IT APPEARS THAT SOME PLANTERS |
| | ARE BEING MODIFIED TO HAVE THE DEPTH DECREASED, WHICH |
| | IS ACCEPTABLE (FOR EXAMPLE, PLANTER CAPPING TYPE D). |
| | PLANTER CAPPING TYPE A APPEARS TO SHOW THAT THIS |
| | PLANTER WILL NOT BE MADE SHALLOWER, BUT THE CONCRETE |
| | WILL BE FLUSH WITH THE TOP OF THE PLANTER, ELIMINATING |
| | THE PLANTER. PER ANA MARIA APONTE, THIS WOULD REQUIRE |
| | REVIEW. IF YOU NEED FURTHER CLARIFICATION, SHE CAN BE |
| | CONTACTED AT 561-822-1439. |
| | |
| | |
| | |
| | |
| | |