| 2014-12-11 17:51:28 | RE-ROOF, BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC |
| | |
| | 1- PROVIDE SIGNED AND SEALED RAS 117 FOR NAIL ENHANCING |
| | AT PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL |
| | LIMITATION #7 ON LAST PAGE OF BUILT UP ROOF SYSTEMS |
| | OVER WOOD DECKS NOA 13-1022.15 SUBMITTED. NEED THE |
| | CALCULATIONS TO MEET THE DESIGN PRESSURES OF SEC. 1609 |
| | OF 2010 FBC. |
| | ***NOTE: PROVIDE 2 COPIES WITH ORIGINAL SEAL AND |
| | SIGNATURE AS REQUIRED BY CHAPTER 471 FL. ST. |
| | |
| | 2- GEORGIA- PACIFIC INSULATION NOA 01-0820.07 SUBMITTED |
| | EXPIRED ON 02/02/02. NEED TO PROVIDE CURRENT NOA (2 |
| | COPIES) AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION TO |
| | INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND |
| | PROFIT AND DESIGN PROFESSIONAL FEES. VALUATION WAS |
| | UPDATED TO $12,374. THE PERMIT FEE BALANCE IS $329.48. |
| | |
| | 4- SKETCH SUBMITTED SHOWS 130 L.F. OF ALUMINUM |
| | GUARDRAIL AND CONCRETE POSTS. THIS IS NOT PART OF THE |
| | SCOPE OF WORK OF A ROOFING CONTRACTOR. NEED SEPARATE |
| | PERMIT WITH COMPLETE INFORMATION UNDER A SEPARATE |
| | PERMIT. SEC. 489.113 FL. ST. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |