| 2014-12-12 14:30:50 | REVISION BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE FLOOR PLAN AND COMPLETE SPECIFICATIONS FOR |
| | THE SECOND FLOOR TERRACE. SEC. 107.3.5.3(5) CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 2- PROVIDE COMPLETE WALL SECTION FROM FOUNDATION THRU |
| | SECOND FLOOR TERRACE. SEC. 105.3.5.3(5) CITY |
| | AMENDMENTS. |
| | |
| | 3- FOOTING FOR STEEL COLUMN "G" DOESN'T MEASURE 42" X |
| | 42" AS SPECIFIED ON THE FOOTING SCHEDULE. PROVIDE |
| | COMPLETE SECTION DETAIL SHOWING FOOTING AND EXISTING |
| | HOUSE FOUNDATION. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 4- FOUNDATION PLAN: |
| | A) FOOTING SIZE SPECIFIED ON FOUNDATION PLANS DOESN'T |
| | MATCH FOOTING SIZE SHOWN ON THE FOOTING SCHEDULE. |
| | REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | B) STEEL COLUMN SIZE AND SPECS SPECIFIED ON FOUNDATION |
| | PLANS DOESN'T MATCH SIZE AND SPECS SHOWN ON THE COLUMN |
| | SCHEDULE. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | 5- SHEET S-1 SUBMITTED CALLS FOR "MEZZ LOADS". THERE IS |
| | NOT MEZZANINE SHOWN ON PLANS. CLARIFY/REVISE AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 6- DESIGN LOADS SHOW INFORMATION FOR ROOFS LOADS AND |
| | FOR FLOOR TRUSSES. FRAMING PLAN SPECIFIES ROOF TRUSSES. |
| | ORIGINAL PLANS CALLED FOR A TERRACE. REVISE DESIGN |
| | INFORMATION AND FRAMING PLANS AS REQUIRED TO MATCH. |
| | KEEP IN MIND MATERIALS TO BE USED IN THE TERRACE. SEC. |
| | R301 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | CONSTRUCTION AND INSTALLATION OF THE TERRACE GUARDRAIL |
| | AS REQUIRED BY TABLE R301.5 AND SEC. R312 OF 2010 |
| | FBC-RESIDENTIAL. |
| | ***NOTE: ALSO PROVIDE DETAILS AND SPECS FOR ATTACHMENT |
| | OF GUARDRAIL POSTS TO THE SIDES WHERE THERE IS NOT LVL |
| | BEAM. |
| | |
| | 8- REVISE DESIGN SPECIFICATIONS NOTE #2 TO MATCH DESIGN |
| | CRITERIA SPECIFIED ON THE LOWER LEFT CORNER OF SHEET |
| | S-1. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ALL THE SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| | CONNECTOR OR ENGINEER TO LIST FLORIDA PRODUCT APPROVAL |
| | NUMBER NEXT THE THE SPECIFIED CONNECTOR. |
| | |
| | B) UNDERLAYMENT SPECIFIED FOR THE TERRACE FLOOR. NOTE: |
| | KEEP IN MIND MATERIAL SPECIFIED FOR THE TERRACE |
| | FINISHES FLOOR. ALSO, IF THE UNDERLAYMENT REQUIRES NAIL |
| | ENHANCING TO MEET THE DESIGN PRESSURES, THEN PROVIDE |
| | SUCH CALCULATIONS. |
| | |
| | ****NOTE: PROVIDE CORRECT CONTRACTOR'S LICENCE NUMBER |
| | SHOWN ON SHEET S-1. |
| | |