Plan Review Details - Permit 14120367
Plan Review Stops For Permit 14120367
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-12 Cont ID  
Sent By skennedy Date 2014-12-12 Time 11:36 Rev Time 0.00
Received By skennedy Date 2014-12-12 Time 11:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-12-11 Cont ID  
Sent By scaldero Date 2014-12-11 Time 13:31 Rev Time 0.00
Received By scaldero Date 2014-12-11 Time 13:31 Sent To E
Notes
2014-12-11 13:36:26PERMIT #14120367
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO:
  
 1) WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
 2) ALL TENANT SPACES IN THIS BUILDING MUST BE TIED INTO
 THE MASTER FIRE ALARM PANEL FOR THE BUILDING. EACH
 TENANT SPACE WILL BE INTERCONNECTED AND UPON ACTIVATION
 OF AN ALARM IN ANY ONE SPACE, ALL SPACES WILL HAVE
 THEIR NOTIFICATION DEVICES ACTIVATE. AN FACP IN A
 TENANT SPACES WILL HAVE THE "RESET" AND "SILENCE"
 FUNCTIONS DEACTIVATED. RESET AND SILENCE OF AN ALARM IS
 LIMITED TO THE MASTER PANEL FOR THE BUILDING AND MAY
 ONLY BE DONE BY A LICENSED FIRE ALARM TECHNICIAN.
 SHOULD IT BE FOUND THAT TENANTS ARE ACCESSING THE
 PANELS IN THE TENANT SPACES AND/OR USING THE "RESET" OR
 "SILENCE" FUNCTIONS, THE OFFICE OF THE FIRE MARSHAL MAY
 REQUIRE THAT THE TENANT FACP BE REMOVED.
  
 3) FIRE ALARM CIRCUIT BREAKER TO BE MARKED IN RED AND
 IDENTIFIED AS "FIRE ALARM." PROVIDE CIRCUIT BREAKER
 LOCK FOR DEDICATED BRANCH CIRCUIT.
  
 4) PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 5) A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-12 Cont ID  
Sent By skennedy Date 2014-12-12 Time 11:36 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved