Plan Review Details - Permit 14120355
Plan Review Stops For Permit 14120355
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-01-20 Cont ID  
Sent By JWITMER Date 2015-01-20 Time 10:38 Rev Time 0.00
Received By jwitmer Date 2015-01-20 Time 10:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-12 Cont ID  
Sent By jwitmer Date 2014-12-12 Time 09:08 Rev Time 0.00
Received By jwitmer Date 2014-12-12 Time 07:45 Sent To  
Notes
2014-12-12 09:08:23BUILDING PLAN REVIEW
 PERMIT: 14120355
 ADD: 1703 PALM BEACH LAKES BLVD # H-03
 CONT: DUFFY SOUTHEAST
 TEL: (???)373-3902
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. DEC. 12/12/14
 ACTION: DENIED
  
 1A) NOTE: PALM BEACH OUTLET MALL: BEFORE PLAAN
 SUBMITTAL TO THE BUILDING DEPARTMENT, THE PLANS ARE
 SUPPOSE TO HAVE THE STAMPED LANDLORD APPROVAL BY NEW
 ENGLAND DEVELOPMNT PALM BEACH OUTLETS SKE GROUP TENANT
 COORDINATOR.
  
 1B) THE OWNERS NOTIRIZED SIGNATURE IS MISSING ON THE
 PERMIT APPLICATION.
  
 2) PLEASE REVIEW THE OCCUPANT LOAD FOUND ON THE LIFE
 SAFETY SHEET A.02 INDICATES INDICATES 25 OCCUPANTS
 SERVED BY THE FRONT ENTRY. THE COVER SHEET SHOWS 1057
 SQ. FT. MERCANTILE/ 30= 36 OCCUPANTS
 295 SQ. FT. BOH / 300= 1 OCCUPANT
 TOTAL OCCUPANT LOAD 37 OCCUPANTS SEE 2010 FBC-B TABLE
 1004.1.1. PLEASE CORRECT.
  
 3) SHEET A 4.1:
 3A) DISCREPANCY IN PLANS DETAILS 2 & 3 BOTH REFERANCE
 SEE DETAIL1/ A2.3, THIS SHEET IS NOT FOUND IN THE SET
 OF PLANS NOR IN THE SHEET INDEX. 107.2.1.3 ADDTIONAL
 INFORMATION REQUIRED.
  
 3B) DISCREPANCY IN PLANS DETAILS 1 VERSES 3, DETAIL # 3
 IS A FOOT SHORTER AT 6'-3" THAN DETAIL # 1 DOES NOT
 COMPLY WITH 2010 FL ACCESS. CODE 604.3.2.
  
 3C) SECTION ELEVATION DETAILS 2 & 3 INDICATE THE GRAB
 RAILS TO BE SET AT THE MAXIMUM HEIGTH OF 36 INCHES,
 NOTE AS DEPICTED THEY ARE SHOWN AT 36 INCHES TO THE
 CENTER LINE OF THE GRAB BAR. 2010 FL ACCESS. CODE 609.4
 THE HEIGTH MEASUREMENT IS TAKEN AT THE TOP OF THE GRAB
 BAR, THE TOP OF THE GRASPING SURFACE.
  
 3D) THE WATER CLOSET DOES NOT SHOW THE FLUSH CONTROL,
 IF A HAND FLUSH CONTROL IT MUST BE ON THE OPEN SIDE
 (TRANSFER SIDE), 2010 FBC-ACCESSIBILITY 604.6.
  
 4) SHEETS A6.1 & A7.1 THE CASH WRAP PLEASE SHOW
 COMPLIANCE WITH 2010 FL ACCESS. CODE 904.4 SALES AND
 SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-19 Cont ID  
Sent By dhayes Date 2014-12-19 Time 13:59 Rev Time 0.00
Received By dhayes Date 2014-12-19 Time 13:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-01-26 Cont ID  
Sent By scaldero Date 2015-01-26 Time 11:59 Rev Time 0.00
Received By scaldero Date 2015-01-26 Time 11:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-12-11 Cont ID  
Sent By scaldero Date 2014-12-11 Time 13:48 Rev Time 0.00
Received By scaldero Date 2014-12-11 Time 13:48 Sent To  
Notes
2014-12-11 13:50:04PERMIT # 14120355
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR. IF ENTRY DOOR IS A DOUBLE DOOR,
 BOTH SIDES MUST BE EQUIPPED WITH LOCK INDICATORS.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
 ALL TENANT SPACES FOR THIS BUILDING MUST BE TIED INTO
 THE MASTER FIRE ALARM PANEL FOR THE BUILDING. EACH
 TENANT SPACE WILL BE INTERCONNECTED AND UPON ACTIVATION
 OF AN ALARM IN ANY ONE SPACE, ALL SPACES WILL HAVE
 THEIR NOTIFICATION DEVICES ACTIVATE. AN FACP IN A
 TENANT SPACES WILL HAVE THE "RESET" AND "SILENCE"
 FUNCTIONS DEACTIVATED. RESET AND SILENCE OF AN ALARM IS
 LIMITED TO THE MASTER PANEL FOR THE BUILDING AND MAY
 ONLY BE DONE BY A LICENSED FIRE ALARM TECHNICIAN.
 SHOULD IT BE FOUND THAT TENANTS ARE ACCESSING THE
 PANELS IN THE TENANT SPACES AND/OR USING THE "RESET" OR
 "SILENCE" FUNCTIONS, THE OFFICE OF THE FIRE MARSHAL MAY
 REQUIRE THAT THE TENANT FACP BE REMOVED.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-31 Cont ID  
Sent By skennedy Date 2015-01-31 Time 09:28 Rev Time 0.00
Received By skennedy Date 2015-01-12 Time 14:30 Sent To  
Notes
2015-01-14 14:30:54B21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-02 Cont ID  
Sent By hmoser Date 2015-01-02 Time 09:40 Rev Time  
Received By hmoser Date 2014-12-09 Time   Sent To  
Notes
2014-12-10 12:07:23INCOMING SENT TO B21. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-01-02 Cont ID  
Sent By hmoser Date 2015-01-02 Time 09:39 Rev Time 0.00
Received By hmoser Date 2015-01-02 Time 09:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-01-25 Cont ID  
Sent By TKLARGE Date 2015-01-25 Time 03:59 Rev Time 0.00
Received By tklarge Date 2015-01-24 Time 12:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-12-19 Cont ID  
Sent By tklarge Date 2014-12-19 Time 06:24 Rev Time 0.00
Received By tklarge Date 2014-12-19 Time 05:29 Sent To  
Notes
2014-12-19 06:24:421) A DRINKING FOUNTAIN IS REQUIRED PER 2010 FL.
 PLUMBING CODE TABLE 403.1 AND FOOTNOTE (E).A MINIMUM OF
 TWO DRINKING FOUNTAINS SHALL BE PROVIDED PER THE 2010
 FL. ACCESSIBILITY CODE SEC.211.2.
 2) SHT. A4.1 - ELEVATIONS # 2 & #3 - THE GRAB BAR SHALL
 BE MOUNTED AT 36" TO THE TOP OF THE BAR, NOT TO THE
 CENTER AS SHOWN.RESTROOM NOTES SPECIFY 36" TO TOP. 2010
 FL.ACCESSIBILITY CODE SEC.609.4.
 3) SHT. A4.1 - THE REAR GRAB BAR SHALL BE LOCATED IN
 ACCORDANCE WITH THE 2010 FL. ACCESSIBILITY CODE
 SEC.604.5.2.
 4) SHT. A4.1 - DETAIL 3 SHOWS A VERTICAL GRAB BAR. GRAB
 BARS SHALL BE INSTALLED IN THE HORIZONTAL POSITION PER
 THE FL. ACCESSIBILITY CODE SEC. 609.4.
 5) SHT. A4.1 - DETAIL #4- THE TOILET PAPER DISPENSER
 SHALL BE LOCATED 7 INCHES MINIMUM AND 9 INCHES MAXIMUM
 IN FRONT OF THE WATER CLOSET MESURED TO THE CENTERLINE
 OF THE DISPENSER.FAC SEC.604.7.
 6) THE FLUSH HANDLE SHALL BE LOCATED ON THE OPEN SIDE
 OF THE WATER CLOSET PER THE 2010 FAC SEC.604.6.
 7) SHT.A4.1 - DETAILS # 2 & #3 REFER TO SHT A2.3. THERE
 IS NO SUCH SHEET IN THIS SET OF PLANS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-01-29 Cont ID  
Sent By ESCHNEID Date 2015-01-29 Time 19:06 Rev Time 0.50
Received By eschneid Date 2015-01-29 Time 19:06 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-30 Cont ID  
Sent By eschneid Date 2014-12-30 Time 11:49 Rev Time 0.50
Received By eschneid Date 2014-12-30 Time 11:49 Sent To  
Notes
2014-12-30 11:59:27FAILED
  
 1) PALM BEACH MANAGEMENT STAMP REQUIRED ON THE PLANS.
  
 2) PROVIDE A SITE MAP SHOWING EXACTLY WHICH BUILDING
 THIS BAY IS IN. ZONING STAFF CAN NOT PROVIDE COMPLETE
 REVIEW OF THIS PERMIT WITHOUT THIS INFORMATION.
  
 3) THE PLANS INDICATE NEW ROOFTOP MECHANICAL EQUIPMENT
 (RTU-1 AND EF-1). PROVIDE LINE OF SIGHT DRAWINGS TO
 VERIFY THAT THIS EQUIPMENT (TO INCLUDE THE CURB IT SITS
 ON) IS SCREENED FROM VIEW IN ACCORDANCE WITH THE PALM
 BEACH OUTLETS DESIGN GUIDELINES.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.