Plan Review Details - Permit 14120236
Plan Review Stops For Permit 14120236
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-04-01 Cont ID  
Sent By wjolin Date 2015-04-01 Time 16:38 Rev Time 0.00
Received By wjolin Date 2015-04-01 Time 16:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-01-07 Cont ID  
Sent By wjolin Date 2015-01-07 Time 13:48 Rev Time 0.00
Received By wjolin Date 2015-01-07 Time 11:05 Sent To  
Notes
2015-01-07 13:29:416601 NORTH JOG ROAD - ASH MANAGEMENT BUILDING
 TRACKING #14120236
 PERMIT #13100957
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE AN ADDRESS OF 6701 NORTH JOG ROAD
 WHICH IS ALREADY ASSIGNED TO THE MAINTENANCE BUILDING.
  
 THESE PLANS WERE SUBMITTED AS AS-BUILT REVISIONS TO
 SPRINKLER PERMIT #13100957; HOWEVER, NO REVISION
 TRIANGLES OR DELTAS COULD BE LOCATED ON THE PLANS
 INDICATING WHAT HAS BEEN CHANGED.
  
 CROKER MODEL 5040 IS NOT A PRESSURE REDUCING TYPE ANGLE
 VALVE. THE PRESSURE-REGULATING DEVICE SHALL BE PROVIDED
 WITH INLET AND OUTLET PRESSURE GAUGES (NFPA 14 SECTION
 7.2.2).
  
 STANDPIPE DESIGN: SEVERAL 1-1/2" HOSE VALVES APPEAR TO
 HAVE PRESSURES THAT WILL EXCEED 100 PSI. PER NFPA 14
 SECTION 7.2.3.1, WHERE THE RESIDUAL PRESSURE AT A
 1-1/2" OUTLET ON A HOSE CONNECTION AVAILABLE FOR
 TRAINED PERSONNEL USE EXCEEDS 100 PSI, AN APPROVED
 PRESSURE-REGULATING DEVICE SHALL BE PROVIDED TO LIMIT
 THE RESIDUAL PRESSURE TO 100 PSI. ALSO PER NFPA 14
 SECTION 7.2.3.2, AN APPROVED PRESSURE-REGULATING DEVICE
 SHALL BE PROVIDED TO LIMIT STATIC AND RESIDUAL
 PRESSURES AT THE OUTLET OF THE HOSE CONNECTION TO 100
 PSI FOR 1-1/2" HOSE CONNECTIONS AVAILABLE FOR TRAINED
 PERSONNEL USE AND 175 PSI FOR OTHER HOSE CONNECTIONS.
  
 TO AVOID PRESSURE REGULATING DEVICES I WOULD RECOMMEND
 A TRUE CLASS I STANDPIPE SYSTEM (2-1/2 FDVS ONLY) AND
 ELIMINATE THE 1-1/2" FDVS WITH HOSE AND REEL BECAUSE
 FIRE DEPARTMENT PERSONNEL WILL NOT USE THIS EQUIPMENT.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-04 Cont ID  
Sent By hmoser Date 2015-04-04 Time 08:51 Rev Time 0.00
Received By hmoser Date 2015-03-26 Time 10:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-08 Cont ID  
Sent By hmoser Date 2015-01-08 Time 09:39 Rev Time 0.00
Received By hmoser Date 2014-12-22 Time 10:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-04-04 Cont ID  
Sent By hmoser Date 2015-04-04 Time 08:51 Rev Time 0.00
Received By hmoser Date 2015-04-04 Time 08:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-01-08 Cont ID  
Sent By hmoser Date 2015-01-08 Time 09:38 Rev Time 0.00
Received By hmoser Date 2015-01-08 Time 09:09 Sent To  
Notes
2015-01-08 09:39:12SEE FIRE REVIEW HM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-04-09 Cont ID  
Sent By skennedy Date 2015-04-09 Time 12:12 Rev Time 0.00
Received By skennedy Date 2015-04-06 Time 09:09 Sent To  
Notes
***NONE***