| 2014-12-07 09:58:50 | BUILDING PLAN REVIEW |
| | PERMIT: 14120178 |
| | ADD: 600 OKEECHOBEE BLVD |
| | CONT: THERMA SEAL ROOF SYSTEMS |
| | TEL: (561) 223-2096 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SUN. DEC. 07/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2) TO DATE THERE HAS BEEN NO SUBMITTALS IN REGARDS TO |
| | THE INSULATING CONCRETE ROOF DECK. THE FOLLOWING |
| | REQUIREMENTS WOULD NEED TO SHOW CODE COMPLIANCE FOR THE |
| | USE OF A LIGHTWEIGHT INSULATING ROOF DECK SYSTEM: |
| | |
| | 1917.1.3 CELLULAR/AGGREGATE (HYBRID) LIGHTWEIGHT |
| | INSULATING CONCRETE. |
| | INSULATED CONCRETE FORMULATED BY COMBINING PREFORMED |
| | FOAM WITH LOW DENSITY AGGREGATES TO IMPART PROPERTIES |
| | OF BOTH AGGREGATE AND CELLULAR LIGHTWEIGHT INSULATING |
| | CONCRETE. IT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH |
| | OF 200 PSI (1379 KPA) WHEN TESTED IN COMPLIANCE WITH |
| | ASTM C 495 AND C 796. |
| | |
| | 1917.1.4 WALKABILITY. |
| | A TERM DEFINING THE ABILITY OF LIGHTWEIGHT INSULATING |
| | CONCRETE TO WITHSTAND ANTICIPATED CONSTRUCTION FOOT |
| | TRAFFIC DURING THE ROOF MEMBRANE APPLICATION WITHOUT |
| | SIGNIFICANT INDENTATIONS IN THE LIGHTWEIGHT INSULATING |
| | CONCRETE SURFACE. |
| | |
| | 1917.2 INSPECTION. |
| | |
| | 1917.2.1 |
| | APPLICATION OF ALL LIGHTWEIGHT INSULATING CONCRETE ROOF |
| | DECKS SHALL BE BY APPLICATORS APPROVED BY THE |
| | LIGHTWEIGHT INSULATING CONCRETE DECK MANUFACTURER. |
| | PRODUCT APPROVAL SHALL BE REQUIRED FOR ALL LIGHTWEIGHT |
| | INSULATING CONCRETE SYSTEMS. |
| | |
| | 1917.2.2 |
| | THE PERMIT HOLDER SHALL NOTIFY THE BUILDING OFFICIAL 48 |
| | HOURS PRIOR TO THE POURING OF LIGHTWEIGHT INSULATING |
| | CONCRETE. |
| | |
| | 1917.2.3 |
| | THE PERMIT HOLDER SHALL MAKE AVAILABLE TO THE BUILDING |
| | OFFICIAL A JOB LOG WITH THE FOLLOWING MINIMUM ITEMS. |
| | 1. CAST DENSITY RECORDINGS/HOUR. |
| | 2. PRODUCT EVALUATION FOR APPLICATION. |
| | 3. DATE AND JOB LOCATIONS IDENTIFIED. |
| | 4. RESULTS OF ANY FIELD TEST CONDUCTED. |
| | |
| | 1917.2.4 |
| | ONCE THE ROOF DECK SYSTEM CAN SUPPORT FOOT TRAFFIC, THE |
| | BUILDING OFFICIAL SHALL HAVE CLEAR ACCESS AND CLEAR |
| | PATH AT HIS OPTION FOR INSPECTION OF LIGHTWEIGHT |
| | INSULATING CONCRETE. |
| | |
| | 1917.3 TESTING. |
| | THE BUILDING OFFICIAL MAY REQUIRE TESTS OF THE |
| | LIGHTWEIGHT INSULATING CONCRETE TO CONFIRM THE FASTENER |
| | WITHDRAWAL RESISTANCE, COMPRESSIVE STRENGTH OR DRAINAGE |
| | ABILITY. |
| | |
| | THE STRUCTURAL ROOF DECK HAS NOT EVEN BEEN POURED |
| | YET!!!! IT WOULD APPEAR THE WRONG PRODUCT APPROVAL HAS |
| | BEEN SUBMITTED, NOA 13-0129.16 PAGE 21 OF 39 HAS BEEN |
| | SUBMITTED WHICH INDICATES THE USE OF RIGID INSULATION |
| | PANELS AND A TOP COAT OF 2 ? INCHES OF CONCRECEL. |
| | PLEASE NOTE SHEET A12.19 DETAILS 2 & 3 BOTH SHOW THE |
| | USE OF LIGHTWEIGHT INSULATING CONCRETE, IN NEITHER OF |
| | THE DETAILS DOES THE DETAILS SHOW THE USE OF RIGID |
| | INSULATION PANELS, NOTE IF THIS PRODUCT IS TO BE USED, |
| | THE VARIOUS ROOF DETAILS THROUGHOUT THE PLANS WILL NEED |
| | TO SHOW THE RIGID INSULATION BOARDS AS A REVISION, PLUS |
| | A LAYOUT SHEET OF THE PANELS, SHOWING THE THICKNESS OF |
| | THE PANELS & SLOPE TO THE POINT OF DRAINAGE, |
| | ATTACHMENT OF PANELS AND MEETING THE REQUIREMENTS OF |
| | SECTION 1917 FOR LIGHTWEIGHT CONCRETE. |
| | |
| | 3) PLEASE PROVIDE DOCUMENTATION WHERE THE PLANTATION |
| | ROOF TILE (NOA 10-1201.01) IS GOING TO BE INSTALLED ON |
| | THE BUILDING, THE MEAN ROOF HEIGHT, SLOPE AND ROOF ZONE |
| | AND ASSOCIATED PRESSURES FOR ALL ROOF ZONES. THE |
| | DESIGNER OF RECORD (ENGINEER) AGAIN HAS NOT REVIEWED |
| | THIS SYSTEM FOR CODE COMPLIANCE FOR THE MOMENT OF OVER |
| | TURNING PER SECTION 1609.5.3. |
| | |
| | 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| | CONSTRUCTION DOCUMENTS SHALL |
| | ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING |
| | SYSTEM, MATERIALS, FASTENING |
| | REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| | RATING THAT ARE REQUIRED TO BE |
| | INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| | INDICATE COMPLIANCE WITH THE WIND |
| | CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT |
| | BY AN ARCHITECT OR ENGINEER FOR THE |
| | SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| 2014-12-07 09:57:41 | BUILDING PLAN REVIEW |
| | PERMIT: |
| | ADD: |
| | CONT: |
| | TEL: (561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SUN. DEC. 07/2014 |
| | ACTION: DENIED |
| | |
| | 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2) TO DATE THERE HAS BEEN NO SUBMITTALS IN REGARDS TO |
| | THE INSULATED CONCRETE ROOF DECKING. THE FOLLOWING |
| | REQUIREMENTS WOULD NEED TO SHOW CODE COMPLIANCE FOR THE |
| | USE OF A LIGHTWEIGHT INSULATING ROOF DECK SYSTEM: |
| | 1917.1.3 CELLULAR/AGGREGATE (HYBRID) LIGHTWEIGHT |
| | INSULATING CONCRETE. |
| | INSULATED CONCRETE FORMULATED BY COMBINING PREFORMED |
| | FOAM WITH LOW DENSITY AGGREGATES TO IMPART PROPERTIES |
| | OF BOTH AGGREGATE AND CELLULAR LIGHTWEIGHT INSULATING |
| | CONCRETE. IT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH |
| | OF 200 PSI (1379 KPA) WHEN TESTED IN COMPLIANCE WITH |
| | ASTM C 495 AND C 796. |
| | |
| | 1917.1.4 WALKABILITY. |
| | A TERM DEFINING THE ABILITY OF LIGHTWEIGHT INSULATING |
| | CONCRETE TO WITHSTAND ANTICIPATED CONSTRUCTION FOOT |
| | TRAFFIC DURING THE ROOF MEMBRANE APPLICATION WITHOUT |
| | SIGNIFICANT INDENTATIONS IN THE LIGHTWEIGHT INSULATING |
| | CONCRETE SURFACE. |
| | |
| | 1917.2 INSPECTION. |
| | |
| | 1917.2.1 |
| | APPLICATION OF ALL LIGHTWEIGHT INSULATING CONCRETE ROOF |
| | DECKS SHALL BE BY APPLICATORS APPROVED BY THE |
| | LIGHTWEIGHT INSULATING CONCRETE DECK MANUFACTURER. |
| | PRODUCT APPROVAL SHALL BE REQUIRED FOR ALL LIGHTWEIGHT |
| | INSULATING CONCRETE SYSTEMS. |
| | |
| | 1917.2.2 |
| | THE PERMIT HOLDER SHALL NOTIFY THE BUILDING OFFICIAL 48 |
| | HOURS PRIOR TO THE POURING OF LIGHTWEIGHT INSULATING |
| | CONCRETE. |
| | |
| | 1917.2.3 |
| | THE PERMIT HOLDER SHALL MAKE AVAILABLE TO THE BUILDING |
| | OFFICIAL A JOB LOG WITH THE FOLLOWING MINIMUM ITEMS. |
| | 1. CAST DENSITY RECORDINGS/HOUR. |
| | 2. PRODUCT EVALUATION FOR APPLICATION. |
| | 3. DATE AND JOB LOCATIONS IDENTIFIED. |
| | 4. RESULTS OF ANY FIELD TEST CONDUCTED. |
| | |
| | 1917.2.4 |
| | ONCE THE ROOF DECK SYSTEM CAN SUPPORT FOOT TRAFFIC, THE |
| | BUILDING OFFICIAL SHALL HAVE CLEAR ACCESS AND CLEAR |
| | PATH AT HIS OPTION FOR INSPECTION OF LIGHTWEIGHT |
| | INSULATING CONCRETE. |
| | |
| | 1917.3 TESTING. |
| | THE BUILDING OFFICIAL MAY REQUIRE TESTS OF THE |
| | LIGHTWEIGHT INSULATING CONCRETE TO CONFIRM THE FASTENER |
| | WITHDRAWAL RESISTANCE, COMPRESSIVE STRENGTH OR DRAINAGE |
| | ABILITY. |
| | |
| | THE STRUCTURAL ROOF DECK HAS NOT EVEN BEEN POURED |
| | YET!!!! IT WOULD APPEAR THE WRONG PRODUCT APPROVAL HAS |
| | BEEN SUBMITTED, NOA 13-0129.16 PAGE 21 OF 39 HAS BEEN |
| | SUBMITTED WHICH INDICATES THE USE OF RIGID INSULATION |
| | PANELS AND A TOP COAT OF 2 1/4 INCHES OC CONCRECEL. |
| | PLEASE NOTE SHEET A12.19 DETAILS 2 & 3 BOTH SHOW THE |
| | USE OF LIGHTWEIGHT INSULATING CONCRETE, IN NEITHER OF |
| | THE DETAILS DOES IT SHOW THE USE OF RIGID INSULATION |
| | PANELS, NOTE IF THIS PRODUCT IS TO BE USED, THE VARIOUS |
| | ROOF DETILS THROUGHOUT THE PLANS WILL NEED TO SHOW THE |
| | RIGID INSULATION PANELS AND ALSO WE WILL NEED A LAYOUT |
| | SHEET FOR THE THICKNESS OF THE PANELS. SLOPE TO THE |
| | POINT OF DRAINAGE PLUS THE MEETING THE REQUIREMENTS OF |
| | SECTION 1917 FOR LIGHT WEIGHT CONCRETE. |
| | |
| | 3) PLEASE PROVIDE DOCUMENTATION WHERE THE PLANTATION |
| | ROOF TILE (NOA: 10-1202.01) IS GOING TO BE INSTALLED ON |
| | THE BUILDING, THE MEAN ROOF HEIGHT, ROOF ZONE, AND |
| | ASSOCIATED PRESSURES FOR THIS ZONE. THE DESIGNER OF |
| | RECORD AGAIN HAS NOT REVIEWED THIS SYSTEM FOR CODE |
| | COMPLIANCE FOR THE MOMENT OF OVER TURNING PER SECTION |
| | 1609.5.3. |
| | |
| | 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| | CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| | DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| | FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND |
| | RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED. |
| | PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE |
| | COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE |
| | SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR |
| | ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH |
| | THE CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | . |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |