| 2014-12-10 07:27:10 | BUILDING PLAN REVIEW |
| | PERMIT: 14120169 |
| | ADD: 716 N. SAPODILLA AVE. |
| | CONT: NUJAK DEV. |
| | TEL: (561)847-3291 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. DEC. 10/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE A SURVEY, EXTERIOR DOORS CAN NOT |
| | SWING OVER THE PROPERTY LINES. 2010 FBC-B 3202.2 |
| | ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN HEIGHT. |
| | ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE |
| | AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE |
| | PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1 |
| | THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT OPEN OR |
| | PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| | |
| | 2) ALSO NOTE HOW FAR THE BUILDING IS FROM THE PROPERT |
| | LINE. 2010 FBC-B TABLE 705.8 MAXIMUM AREA OF EXTERIOR |
| | WALL OPENINGS BASED ON FIRE SEPARATION DISTANCE AND |
| | DEGREE OF OPENING PROTECTION. |
| | |
| | 3) THE PRODUCT APPROVAL SUBMITTED DOES NOT HAVE THE |
| | COVERSHEETS TO WHICH CODE THIS WAS APPROVED. SHEET # 3 |
| | INDICATES THIS REPORT EXPIRED 03/31/2010. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | |
| | 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 5) SHEET A-2 DOES NOT PROVIDE THE WIND DESIGN CRITERIA: |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 5.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | |
| | |