Plan Review Details - Permit 14120164
Plan Review Stops For Permit 14120164
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-12-17 Cont ID  
Sent By jwitmer Date 2014-12-17 Time 09:54 Rev Time 0.00
Received By jwitmer Date 2014-12-17 Time 09:54 Sent To  
Notes
2014-12-17 09:55:16PARKING ACCESSIBILITY SHEET C-4.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-12-31 Cont ID  
Sent By dhayes Date 2014-12-31 Time 13:18 Rev Time 0.00
Received By dhayes Date 2014-12-31 Time 13:18 Sent To  
Notes
2014-12-31 13:40:0812/31/2014
 PROJECT: DUNKIN DONUTS
 PERMIT#: 14120164
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2NDELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 1) 505.2.4 EXTERIOR LIGHTING CONTROLS.
 PROVIDE AUTOMATED CONTROLS CAPABLE OF TURNING OFF
 EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT IS AVAILABLE
 OR WHEN THE LIGHTING IS NOT REQUIRED DURING NIGHTTIME
 HOURS. LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN
 OPERATION SHALL BE CONTROLLED BY EITHER A COMBINATION
 OF A PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL
 TIME SWITCH. A TIMER IS INDICATED ON THE PLAN BUT IT
 MUST BE VERIFIED TO MEET THE CRITERIA OF THE FBC-ENERGY
 505.2
  
 2) 2010 FBC-BUILDING SECTION 1609
 PROVIDE ENGINEERED WIND LOAD CALCULATIONS FOR ALL NEW
 LIGHT POLES INCLUDING ATTACHED LUMINAIRE INDICATING
 COMPLIANCE WITH THE FBC 1609. PRIOR TO FINAL
 INSPECTION.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-05 Cont ID  
Sent By dhayes Date 2014-12-05 Time 13:50 Rev Time 0.00
Received By dhayes Date 2014-12-05 Time 08:06 Sent To  
Notes
2014-12-05 13:50:4012/5/2014
 PROJECT: DUNKIN DONUTS
 PERMIT#: 14120164
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) 2010 WPB AMENDMENTS TO FBC 107.2.1
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE IN DETAIL THE LOCATION, NATURE AND EXTENT
 OF THE WORK PROPOSED. PROVIDE A LIGHTING CIRCUITRY
 DIAGRAM INDIACTING THE WIRING METHOD, THE ELECTRICAL
 PANEL USED PLUS IT'S LOCATION, THE CIRCUIT NUMBER(S)
 USED AND SHOWN ON THE PLAN, THE SIZE AND TYPE OF
 CONDUCTORS PROPOSED.
  
 2) 505.2.4 EXTERIOR LIGHTING CONTROLS.
 PROVIDE AUTOMATED CONTROLS CAPABLE OF TURNING OFF
 EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT IS AVAILABLE
 OR WHEN THE LIGHTING IS NOT REQUIRED DURING NIGHTTIME
 HOURS. LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN
 OPERATION SHALL BE CONTROLLED BY EITHER A COMBINATION
 OF A PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL
 TIME SWITCH.
  
 3) 2010 FBC-BUILDING SECTION 1609
 PROVIDE ENGINEERED WIND LOAD CALCULATIONS FOR ALL NEW
 LIGHT POLES INCLUDING ATTACHED LUMINAIRE INDICATING
 COMPLIANCE WITH THE FBC 1609.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-02-10 Cont ID  
Sent By cranford Date 2015-02-10 Time 13:55 Rev Time 0.00
Received By cranford Date 2015-02-10 Time 13:55 Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2014-12-18 Cont ID  
Sent By cranford Date 2014-12-18 Time 13:31 Rev Time 0.00
Received By cranford Date 2014-12-18 Time 13:26 Sent To I
Notes
2014-12-18 13:31:35ALSO REVIEWED UNDER ENGINEERING DEVELOPMENT APPROVAL
 E14120022

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2015-03-04 Time   Rev Time 0.00
Received By   Date 2015-02-13 Time   Sent To  
Notes
2015-02-18 08:28:50INCOMING SENT TO ZONING BOX.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-02-10 Cont ID  
Sent By llouie Date 2015-02-10 Time 13:58 Rev Time 0.00
Received By cranford Date 2015-01-20 Time 15:57 Sent To Z
Notes
2015-01-20 16:03:06INCOMING SENT TO ZONING.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-31 Cont ID  
Sent By dhayes Date 2014-12-31 Time 13:20 Rev Time 0.00
Received By dhayes Date 2014-12-23 Time   Sent To Z
Notes
2014-12-23 16:52:55INCOMING SENT TO ZONING.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-18 Cont ID  
Sent By cranford Date 2014-12-18 Time 13:31 Rev Time 0.00
Received By cranford Date 2014-12-04 Time 08:19 Sent To  
Notes
2014-12-05 08:06:18B06

Review Stop Z ZONING
Rev No 4 Status P Date 2015-02-26 Cont ID  
Sent By llouie Date 2015-02-26 Time 15:29 Rev Time 0.00
Received By llouie Date 2015-02-18 Time 15:29 Sent To E
Notes
2015-02-26 15:33:11** ZONING PROVISIO **
  
 1.) THE NEW LIGHT POLE FIXTURE AT THE NORTHEAST PORTION
 OF THE PROPERTY SHALL BE SETBACK 5 FT. FROM THE
 PROPERTY LINE (SEE RED MARKING IN PLANS).
  
 (REFERENCE: ZBA CASE NO. 3307)
  
 NOTE: STATUS CHANGE FROM "F" TO "P" WILL OCCUR ONCE A
 LANDSCAPE PERMIT, SHOWING NO CONFLICT WITH LOCATION OF
 LIGHT POLE FIXTURES, HAS BEEN SUBMITTED.)
  
 CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.

Review Stop Z ZONING
Rev No 3 Status F Date 2015-01-23 Cont ID  
Sent By cranford Date 2015-02-10 Time 13:58 Rev Time 0.00
Received By llouie Date 2015-01-23 Time 15:48 Sent To  
Notes
2015-01-23 15:52:00** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) REPEAT COMMENT 12/15/14 AND 12/24/14: ANY OPERATION
 OR ACTIVITY PRODUCING GLARE SHALL BE CONDUCTED SO THAT
 DIRECT OR INDIRECT LIGHT FROM THE SOURCE SHALL NOT
 CAUSE ILLUMINATION IN EXCESS OF 0.5 FOOT CANDLES WHEN
 MEASURED IN A RESIDENTIAL DISTRICT. SUBMITTED PLAN DOES
 NOT COMPLY WITH THIS ZLDR STANDARD. [ZLDR S.94-310(D)]
  
 2.) REPEAT COMMENT 12/15/14 AND 12/24/14: LANDSCAPING
 IMPROVEMENTS (AS REQUIRED BY THE CONDITIONED IN THE
 FINAL ORDER FOR ZBA CASE NO. 3307) SHALL BE SUBMITTED
 AND REVIEWED AS A SEPARATE PERMIT PRIOR TO THE APPROVAL
 OF THIS PERMIT. THERE SHALL BE NO CONFLICT WITH THE
 LOCATION OF THE PROPOSED LIGHT FIXTURES.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  
 NOTE:
  
 1/23/15 - LANDSCAPE PLANS SUBMITTED WITH PERMIT
 #14120164 RE-SUBMITTAL. CALLED AND SPOKE TO MIKE
 VENTURA, CONTRACTOR FOR THE PROJECT. INFORMED MR.
 VENTURA THAT A SEPARATE LANDSCAPE PERMIT IS REQUIRED
 FOR THE LANDSCAPING. LIGHTING ISSUES REMAIN
 OUTSTANDING. LANDSCAPE PLANS TRAVELING WITH PERMIT
 #14120164 UNTIL CONTRACTOR CAN PICK-UP PLANS FOR NEW
 PERMIT SUBMITTAL.

Review Stop Z ZONING
Rev No 2 Status F Date 2014-12-24 Cont ID  
Sent By dhayes Date 2014-12-31 Time 13:20 Rev Time 0.00
Received By llouie Date 2014-12-24 Time 12:32 Sent To E
Notes
2014-12-24 12:33:10** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) REPEAT COMMENT 12/15/14: ANY OPERATION OR ACTIVITY
 PRODUCING GLARE SHALL BE CONDUCTED SO THAT DIRECT OR
 INDIRECT LIGHT FROM THE SOURCE SHALL NOT CAUSE
 ILLUMINATION IN EXCESS OF 0.5 FOOT CANDLES WHEN
 MEASURED IN A RESIDENTIAL DISTRICT. SUBMITTED PLAN DOES
 NOT COMPLY WITH THIS ZLDR STANDARD. [ZLDR S.94-310(D)]
  
 2.) REPEAT COMMENT 12/15/14: LANDSCAPING IMPROVEMENTS
 (AS REQUIRED BY THE CONDITIONED IN THE FINAL ORDER FOR
 ZBA CASE NO. 3307) SHALL BE SUBMITTED AND REVIEWED AS A
 SEPARATE PERMIT PRIOR TO THE APPROVAL OF THIS PERMIT.
 THERE SHALL BE NO CONFLICT WITH THE LOCATION OF THE
 PROPOSED LIGHT FIXTURES.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-15 Cont ID  
Sent By llouie Date 2014-12-15 Time 13:38 Rev Time 0.00
Received By llouie Date 2014-12-15 Time 13:38 Sent To  
Notes
2014-12-15 13:44:18** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) ALL OUTDOOR LIGHTING SHALL BE SHIELDED TO REDUCE
 GLARE AND SHALL BE ARRANGED TO REFLECT LIGHT OR GLARE
 AWAY FROM ALL RESIDENTIAL DISTRICTS, ADJACENT
 RESIDENCES, OR PUBLIC THROUGHFARES. [ZLDR S.94-309(A)]
  
 2.) ANY OPERATION OR ACTIVITY PRODUCING GLARE SHALL BE
 CONDUCTED SO THAT DIRECT OR INDIRECT LIGHT FROM THE
 SOURCE SHALL NOT CAUSE ILLUMINATION IN EXCESS OF 0.5
 FOOT CANDLES WHEN MEASURED IN A RESIDENTIAL DISTRICT.
 SUBMITTED PLAN DOES NOT COMPLY WITH THIS ZLDR STANDARD.
 [ZLDR S.94-310(D)]
  
 3.) LANDSCAPING IMPROVEMENTS (AS REQUIRED BY THE
 CONDITIONED IN THE FINAL ORDER FOR ZBA CASE NO. 3307)
 SHALL BE SUBMITTED AND REVIEWED AS A SEPARATE PERMIT.
 THERE SHALL BE NO CONFLICT WITH THE LOCATION OF THE
 PROPOSED LIGHT FIXTURES.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  