Plan Review Details - Permit 14120124
Plan Review Stops For Permit 14120124
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-12-05 Cont ID  
Sent By jwitmer Date 2014-12-05 Time 09:51 Rev Time 0.00
Received By jwitmer Date 2014-12-05 Time 08:06 Sent To  
Notes
2014-12-05 09:51:38BUILDING PLAN REVIEW
 PERMIT: 14120124
 ADD: 101 N. CLEMATIS ST. SUITE # 509
 CONT: MARCINKO & RAPPA CONST.
 TEL: (561)310-4658
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. DEC. 05/ 2014
 ACTION: BUILDING PROVISO
  
 SHEET 1 THE INTERIOR DEMO & FLOOR PLAN INDICATES THE
 REMOVAL OF INTERIOR WALLS. THE PLANS DO NOT INDICATE IF
 THE FLOORS ARE GOING TO BE REPAIRED OR REPLACED IN THE
 ROOMS WHERE WORK OCCURS. IF THE FLOORS ARE GOING TO BE
 REPAIRED JUST IN FILLED THEN NO FLOOR INSULATION IS
 REQUIRED.
 IF THE FLOORING IS TO BE REMOVED IN THE ROOMS WHERE THE
 WALLS WERE REMOVED THEN COMPLIANCE WITH FLOOR
 INSULATION IS REQUIRED. PLEASE REVIEW THESE CODE
 REQUIREMENTS IF APPLICABLE AND SUBMIT A REVISION TO THE
 BUILDING DEPARTMENT FOR TO REVIEW FOR CODE COMPLIANCE:
  
 2010 FBC-B;
 1) 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 2.EXCEPTION (2).INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 2) 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-19 Cont ID  
Sent By dhayes Date 2014-12-19 Time 08:51 Rev Time 0.00
Received By dhayes Date 2014-12-19 Time 08:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-12-05 Cont ID  
Sent By pleduc Date 2014-12-05 Time   Rev Time 0.00
Received By pleduc Date 2014-12-05 Time 11:53 Sent To  
Notes
2014-12-05 12:30:13THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE. A
 NOTE IS PROVIDED STATING ADDITIONAL SPRINKLER HEADS ARE
 NOT NEEDED. A FIRE INSPECTOR SHALL VERIFY COVERAGE ON
 INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-19 Cont ID  
Sent By dhayes Date 2014-12-19 Time 08:51 Rev Time 0.00
Received By dhayes Date 2014-12-03 Time 11:31 Sent To  
Notes
2014-12-04 11:32:24SENT TO B3 BIN FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-12-13 Cont ID  
Sent By tklarge Date 2014-12-13 Time 02:39 Rev Time 0.00
Received By tklarge Date 2014-12-13 Time 02:17 Sent To  
Notes
2014-12-13 02:43:16****PROVISO****
 1) WASHING MACINE DRAIN SHALL CONNECT TO A MIN. 3 INCH
 WASTE STACK PER 2010 FL. PLBG. CODE SEC.406.3.
 2) HOT & COLD WATER CONNECTIONS TO EXIST. WATER RISERS.
 3) SHOCK ARRESTORS REQD. ON H & C WATER LINES PER FPC
 SEC. 604.9.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2014-12-11 Cont ID  
Sent By aaponta Date 2014-12-11 Time 13:47 Rev Time 0.00
Received By aaponte Date 2014-12-11 Time 13:47 Sent To  
Notes
2014-12-11 10:29:4512/11/14