| 2014-12-05 09:51:38 | BUILDING PLAN REVIEW |
| | PERMIT: 14120124 |
| | ADD: 101 N. CLEMATIS ST. SUITE # 509 |
| | CONT: MARCINKO & RAPPA CONST. |
| | TEL: (561)310-4658 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. DEC. 05/ 2014 |
| | ACTION: BUILDING PROVISO |
| | |
| | SHEET 1 THE INTERIOR DEMO & FLOOR PLAN INDICATES THE |
| | REMOVAL OF INTERIOR WALLS. THE PLANS DO NOT INDICATE IF |
| | THE FLOORS ARE GOING TO BE REPAIRED OR REPLACED IN THE |
| | ROOMS WHERE WORK OCCURS. IF THE FLOORS ARE GOING TO BE |
| | REPAIRED JUST IN FILLED THEN NO FLOOR INSULATION IS |
| | REQUIRED. |
| | IF THE FLOORING IS TO BE REMOVED IN THE ROOMS WHERE THE |
| | WALLS WERE REMOVED THEN COMPLIANCE WITH FLOOR |
| | INSULATION IS REQUIRED. PLEASE REVIEW THESE CODE |
| | REQUIREMENTS IF APPLICABLE AND SUBMIT A REVISION TO THE |
| | BUILDING DEPARTMENT FOR TO REVIEW FOR CODE COMPLIANCE: |
| | |
| | 2010 FBC-B; |
| | 1) 603.1 ALLOWABLE MATERIALS. |
| | COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS |
| | OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING |
| | APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1 |
| | THROUGH 603.1.3: |
| | 2.EXCEPTION (2).INSULATION INSTALLED BETWEEN A FINISHED |
| | FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| | SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 200. |
| | |
| | 2) 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |