Plan Review Details - Permit 14120014
Plan Review Stops For Permit 14120014
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-20 Cont ID  
Sent By rmcdouga Date 2015-06-20 Time 11:15 Rev Time 0.00
Received By rmcdouga Date 2015-06-20 Time 08:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-29 Cont ID  
Sent By rmcdouga Date 2014-12-29 Time 15:21 Rev Time 0.00
Received By rmcdouga Date 2014-12-29 Time 11:14 Sent To  
Notes
2014-12-29 13:58:59PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE TWO
 NEW IMPACT RATED EXTERIOR FRENCH DOORS AND SIDE-LITE
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. DCA RULE 9N-3 AND FBC 107.3.4
  
 2) THERE ARE TWO DIFFERENT PLAN SHEETS MARKED A2.1.
 PLEASE CORRECT.
  
 3) ADDRESS THE TRUSS REVIEW COMMENTS THAT ARE LISTED
 UNDER THE R REVIEW STOP.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-29 Cont ID  
Sent By rmcdouga Date 2014-12-29 Time 13:27 Rev Time 0.00
Received By rmcdouga Date 2014-12-29 Time 11:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2015-06-29 Cont ID  
Sent By rmcdouga Date 2015-06-29 Time 14:03 Rev Time 0.00
Received By rmcdouga Date 2015-06-29 Time 13:49 Sent To  
Notes
2015-06-29 13:50:44ROUTED TO MCDOUGALL/CC

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-20 Cont ID  
Sent By rmcdouga Date 2015-06-20 Time 11:15 Rev Time 0.00
Received By rmcdouga Date 2015-05-28 Time 15:19 Sent To  
Notes
2015-05-28 15:19:20TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-29 Cont ID  
Sent By rmcdouga Date 2014-12-29 Time 15:24 Rev Time 0.00
Received By rmcdouga Date 2014-12-02 Time 13:56 Sent To  
Notes
2014-12-02 13:59:18R18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-06-29 Cont ID  
Sent By rmcdouga Date 2015-06-29 Time 14:03 Rev Time 0.00
Received By rmcdouga Date 2015-06-29 Time 14:03 Sent To  
Notes
2015-06-29 14:05:07MU 2015 - 15238 NO FEES WERE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-06-20 Cont ID  
Sent By rmcdouga Date 2015-06-20 Time 08:46 Rev Time 0.00
Received By rmcdouga Date 2015-06-20 Time 08:46 Sent To  
Notes
2015-06-20 08:46:16DUE TO THE ADDITION OF MORE CONDITIONED FLOOR SPACE AN
 IMPACT FEE REVIEW IS REQUIRED. BEFORE A PERMIT TO
 CONSTRUCT CAN BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. UPON APPROVAL, ONE SET OF PLANS
 SHALL BE SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY
 FOR AN IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE
 STAMP AND A COPY OF THE PAID RECEIPT MUST BE RETURNED
 TO THE CITY BUILDING DEPARTMENT BEFORE THE BUILDING
 PERMIT CAN BE ISSUED. FOR INFORMATION CALL PALM BEACH
 COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-12-29 Cont ID  
Sent By rmcdouga Date 2014-12-29 Time 13:24 Rev Time 0.00
Received By rmcdouga Date 2014-12-29 Time 11:14 Sent To  
Notes
2014-12-29 13:25:33DUE TO THE ADDITION OF MORE CONDITIONED FLOOR SPACE AN
 IMPACT FEE REVIEW IS REQUIRED. BEFORE A PERMIT TO
 CONSTRUCT CAN BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. UPON APPROVAL, ONE SET OF PLANS
 SHALL BE SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY
 FOR AN IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE
 STAMP AND A COPY OF THE PAID RECEIPT MUST BE RETURNED
 TO THE CITY BUILDING DEPARTMENT BEFORE THE BUILDING
 PERMIT CAN BE ISSUED. FOR INFORMATION CALL PALM BEACH
 COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-12-29 Cont ID  
Sent By rmcdouga Date 2014-12-29 Time 13:27 Rev Time 0.00
Received By rmcdouga Date 2014-12-29 Time 11:14 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2015-06-20 Cont ID  
Sent By rmcdouga Date 2015-06-20 Time 11:15 Rev Time 0.00
Received By rmcdouga Date 2015-06-20 Time 08:46 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2014-12-29 Cont ID  
Sent By rmcdouga Date 2014-12-29 Time 13:59 Rev Time 0.00
Received By rmcdouga Date 2014-12-29 Time 13:59 Sent To  
Notes
2014-12-29 14:42:24TRUSS DRAWING REVIEW
  
 DENIED
  
 1) THE TRUSS LAYOUT IS REQUIRED TO BE REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD FOR THE PROJECT. FAC
 61G15-31.003
 2) THERE IS A SEPARATE SIGNED AND SEALED DRAWING OF
 TRUSS A2 THAT APPEARS TO SHOW THAT THE TRUSS IS TO BE
 FIELD MODIFIED TO CREATE A CATHEDRAL CEILING IN THE
 BATHROOM. THE SIGNATURE ON THE DRAWING IS A COPY AND IS
 NOT ACCEPTABLE. THE ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE IS REQUIRED. FAC 61G15-23.002
 3) THE APPROVED PLANS SHOW A WOOD FRAME GABLE END WITH
 A TOP PLATE. THE GABLE END WALL SECTION ON SHEET A2.1
 (WHICH SHOULD BE A2.0) SHOWS BRACING AND TRUSSES WITH
 BOTTOM CORDS THAT ARE LEVEL WITH THE JOINT IN THE
 EXTERIOR FRAME WALL AND THE GABLE FRAMING. BECAUSE THE
 GABLE END WALL IS NOT BALLOON FRAMED, THE PLANS WILL
 NEED TO BE REVISED TO SHOW HOW THE HINGE EFFECT AT THE
 END WALL WILL BE ADDRESSED IF THE TRUSSES ARE MODIFIED.
 FBC 2318.1.8.2 & FBC 107.2.1
 4) THE GABLE END WALL IS REQUIRED TO BE FIREBLOCKED
 WHERE THE VAULTED CEILING INTERSECTS THE WALL. FCB-R
 302.11
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By sgraham Date   Time   Rev Time 0.00
Received By sgraham Date 2014-12-05 Time 08:50 Sent To  
Notes
***NONE***