Plan Review Details - Permit 14120007
Plan Review Stops For Permit 14120007
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-03-18 Cont ID  
Sent By jgomez Date 2015-03-18 Time 12:08 Rev Time 0.00
Received By jgomez Date 2015-03-18 Time 12:08 Sent To  
Notes
2015-03-18 12:10:22RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PLANS SUBMITTED STILL SHOW ADDITIONAL BEDROOM IN THE
 REAR STRUCTURE. ACCORDING TO PROPERTY OWNER, THERE WILL
 BE NO ADDITIONAL BEDROOM AT THIS TIME. NEED TO REVISE
 PLANS AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- REVISE THE COMPONENTS AND CLADDING DESIGN PRESSURES
 SHOWN ON THE DESIGN PARAMETERS ON SHEET 2 OF 3. THOSE
 PRESSURES DON'T MEET THE DESIGN PRESSURES FOR EXPOSURE
 "C" FOR WINDOWS/DOORS LOCATED ON THE END ZONES. REVISE
 AS REQUIRED. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
 ***NOTE: PLANS WERE REVISED FOR EXPOSURE "B". THIS
 PROPERTY IS NOT LOCATED IN EXPOSURE "B". REVISE AS
 REQUIRED AND MAKE SURE DESIGN PRESSURES CORRESPOND TO
 EXPOSURE "C". REVISE ORIGINAL DRAWINGS. HAND REVISONS
 ARE NOT ACCEPTABLE.
  
 3- OWNER/AGENT TO SIGN AND DATE THE ENERGY
 CALCULATIONS. SEC. 103.2.3.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS..
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-29 Cont ID  
Sent By jgomez Date 2014-12-29 Time 12:42 Rev Time 0.00
Received By jgomez Date 2014-12-29 Time 12:41 Sent To  
Notes
2014-12-29 13:05:16RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1-DETACHED BEDROOM. AFTER PLANS ARE REVISED BRING THEM
 TO PALM BEACH COUNTY (2300 N. JOG RD.) TO VERIFY IF
 IMPACT FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE. REQUIRED BY
 THE COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND
 DEVELOPMENT CODE.
  
 2- DETACHED BEDROOM #4 WINDOW DOESN'T COMPLY WITH THE
 EGRESS MIN. HEIGHT REQUIREMENTS OF SEC. R310.1.2 OF
 2010 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 3-- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 4- REVISE THE COMPONENTS AND CLADDING DESIGN PRESSURES
 SHOWN ON THE DESIGN PARAMETERS ON SHEET 2 OF 3. THOSE
 PRESSURES DON'T MEET THE DESIGN PRESSURES FOR EXPOSURE
 "C" FOR WINDOWS/DOORS LOCATED ON THE END ZONES. REVISE
 AS REQUIRED. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-03-20 Cont ID  
Sent By skennedy Date 2015-03-20 Time 14:36 Rev Time 0.00
Received By skennedy Date 2015-03-20 Time 14:36 Sent To  
Notes
2015-03-20 14:37:461ST REVIEW: FBC 2010
  
 SEE PREVIOUS ELECTRICAL AND CURRENT BUILDING COMMENTS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-31 Cont ID  
Sent By sciard Date 2014-12-31 Time 08:26 Rev Time 0.00
Received By sciard Date 2014-12-31 Time 08:26 Sent To  
Notes
2014-12-31 08:34:131. N.E.C. 210.12 (B). ARC-FAULT PROTECTION FOR ALL NEW
 BRANCH CIRCUITS SERVING AREAS AS SPECIFIED IN THIS CODE
 SECTION.
 2. PANEL SCHEDULE TO SHOW WIRE SIZE AND OCPD FOR ALL
 CIRCUITS LISTED.
 3. N.E.C. 210.70 (A) (1). IDENTIFY SWITCH CONTROLLED
 LIGHT OR RECEPTACLE IN NEW BEDROOM.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-20 Cont ID  
Sent By skennedy Date 2015-03-20 Time 14:32 Rev Time 0.00
Received By skennedy Date 2015-02-23 Time 10:52 Sent To  
Notes
2015-02-24 10:52:49RE-SUBMITTAL SENT TO R7 BIN FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-31 Cont ID  
Sent By sciard Date 2014-12-31 Time 08:26 Rev Time 0.00
Received By sciard Date 2014-12-01 Time 08:53 Sent To  
Notes
2014-12-02 08:58:12R17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2015-03-18 Cont ID  
Sent By jgomez Date 2015-03-18 Time 14:35 Rev Time 0.00
Received By jgomez Date 2015-03-18 Time 14:35 Sent To  
Notes
2015-03-18 14:37:213/18/15 TALKED TO OWNER (GUSTAVO REYES). HE SAID HE'S
 NOT DOING THE DETACHED BEDROOM IN THE EXISTING GARAGE.
 JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-12-29 Cont ID  
Sent By jgomez Date 2014-12-29 Time 13:09 Rev Time 0.00
Received By jgomez Date 2014-12-29 Time 13:09 Sent To  
Notes
2014-12-29 13:13:231-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-03-18 Cont ID  
Sent By jgomez Date 2015-03-18 Time 13:53 Rev Time 0.00
Received By jgomez Date 2015-03-18 Time 13:53 Sent To  
Notes
2015-03-18 13:58:41RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE A/C EQUIPMENT SIZING CALCULATIONS:
 A) CALCULATIONS NEED TO BE DONE ON THE ACTUAL
 ORIENTATION OF THE BUILDING. FRONT DOOR DOESN'T FACE
 NORTH. SEC. 403.6.1 OF 2010 FBC-ENERGY CONSERVATION.
 SEE PLANS AND REVISE AS REQUIRED.
  
 2- SIZE OF TRANSFER DUCTS SPECIFIED ON THE A/C PLAN FOR
 ALL BEDROOMS DON'T COMPLY WITH THE BALANCE RETURN AIR
 SEC. M1602.4 OF 2010 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-29 Cont ID  
Sent By jgomez Date 2014-12-29 Time 17:32 Rev Time 0.00
Received By jgomez Date 2014-12-29 Time 17:32 Sent To  
Notes
2014-12-29 17:52:49RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE A/C EQUIPMENT SIZING CALCULATIONS. SHOW THE
 MANUFACTURER AND MODEL NUMBER AS REQUIRED BY SEC. 403.6
 OF 2010 FBC-ENERGY CONSERVATION.
 NOTE: SEPARATE CALCULATIONS REQUIRED FOR THE MAIN HOUSE
 AND FOR THE DETACHED BEDROOM.
  
 2- A/C PLAN TO SPECIFY ALL CFM'S AND GRILL SIZES . SEC.
 107.3.5.3(10) OF CITY AMENDMENTS TO FBC.
  
 3- A/C PLAN TO SHOW COMPLIANCE WITH THE BALANCED RETURN
 AIR AS REQUIRED BY SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL. SPECIFY ALL DUCT AND GRILL SIZES.
  
 4- SPECIFY VENTILATION FOR THE BATHROOMS AS REQUIRED BY
 SEC. M1507 OF 2010 FBC-RESIDENTIAL.
  
 5- NEW DETACHED BEDROOM STRUCTURE. SHOW ON PLANS HOW
 PROVIDING HEATING TO ALL HABITABLE ROOMS AS REQUIRED BY
 SEC. R303.8 OF 2010 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-03-07 Cont ID  
Sent By tklarge Date 2015-03-07 Time 03:55 Rev Time 0.00
Received By tklarge Date 2015-03-07 Time 03:30 Sent To  
Notes
2015-03-07 03:55:501) SUBMIT A NARRATIVE THAT CLEARLY DESCRIBES THE SCOPE
 OF WORK TO BE DONE.THE APPLICATION WORK DESCRIPTION
 STATES "RENOVATION PER PLANS TO ADDRESS INSPECTOR RED
 TAG." THIS DESCRIPTION IS VAGUE. THE SUB PERMITS STATE
 "PER MASTER PERMIT " WHICH AGAIN IS VAGUE AND
 INCONCLUSIVE. SUBMIT A COPY OF THE RED TAG ALONG WITH
 THE NARRATIVE EXPLAINING ALL WORK TO BE DONE.WPB AMEND.
 TO 2010 FBC 107.2.1., 107.3.5.3.
 2) THE PLANS HAVE THE 2ND BEDROOM CROSSED OUT WITH
 N.I.C. NOTED ON THE PLANS YET THE PLUMBING RISER IS
 STILL ON THE PLANS. CLARIFY. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
2015-02-24 10:53:14NEW DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-12-06 Cont ID  
Sent By tklarge Date 2014-12-06 Time 08:09 Rev Time 0.00
Received By tklarge Date 2015-03-07 Time 03:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-03-04 Cont ID  
Sent By sgraham Date 2015-03-04 Time 09:52 Rev Time 0.00
Received By sgraham Date 2015-03-04 Time 09:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-05 Cont ID  
Sent By sgraham Date 2014-12-05 Time 10:02 Rev Time 0.00
Received By sgraham Date 2014-12-05 Time 10:02 Sent To  
Notes
2014-12-05 10:05:4712/5/14 ZONING FAILED.
  
 1. THE DETACHED GARAGE CAN NOT BE USED AS A RENTAL
 UNIT, NO KITCHEN WILL BE ALLOWED, THE ZONING FOR THIS
 ADDRESS IS SF7, ONE FAMILY TO THE PROPERTY.
 THE GARAGE MAY BE USED AS A BEDROOM WITH ONLY A BATH,