| 2014-11-30 16:07:22 | 1ST REVIEW: FBC 2010 |
| | |
| | YOU HAVE PROVIDED DESIGN PRESSURES FOR EXPOSURE C. |
| | PLEASE PROVIDE DESIGN PRESSURES BASED ON EXPOSURE D: |
| | |
| | 1609.4.3 EXPOSURE CATEGORIES. |
| | AN EXPOSURE CATEGORY SHALL BE DETERMINED IN ACCORDANCE |
| | WITH THE FOLLOWING: |
| | |
| | EXPOSURE B. FOR BUILDINGS WITH A MEAN ROOF HEIGHT OF |
| | LESS THAN OR EQUAL TO 30 FEET, EXPOSURE B SHALL APPLY |
| | WHERE THE GROUND SURFACE ROUGHNESS AS DEFINED BY |
| | SURFACE ROUGHNESS B PREVAILS IN THE UPWIND DIRECTION |
| | FOR A DISTANCE OF AT LEAST 1,500 FT (457 M). FOR |
| | BUILDINGS WITH A MEAN ROOF HEIGHT GREATER THAN 30 FEET, |
| | EXPOSURE B SHALL APPLY WHERE SURFACE ROUGHNESS B |
| | PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT |
| | LEAST 2,600 FEET (792 M) OR 20 TIMES THE HEIGHT OF THE |
| | BUILDING, WHICHEVER IS GREATER. |
| | |
| | EXPOSURE C. EXPOSURE C SHALL APPLY FOR ALL CASES WHERE |
| | EXPOSURES B OR D DO NOT APPLY. |
| | |
| | EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE GROUND |
| | SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D, |
| | PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT |
| | LEAST 5,000 FEET (1524 M) OR 20 TIMES THE HEIGHT OF THE |
| | BUILDING, WHICHEVER IS GREATER. EXPOSURE D SHALL EXTEND |
| | INLAND FROM THE SHORELINE FOR A DISTANCE OF 600 FEET |
| | (183 M) OR 20 TIMES THE HEIGHT OF THE BUILDING, |
| | WHICHEVER IS GREATER FROM AN EXPOSURE D CONDITION AS |
| | DEFINED IN THE PREVIOUS SENTENCE. |
| | |
| | ADDITIONALLY, PLEASE INDICATE THE SELECTED IS IT ORIEL |
| | TYPE, UNEQUAL LITES, OR EQUAL LITES . PLEASE INDICATE |
| | BY MARKING THE PRODUCT APPROVAL OR OTHERWISE. ALSO, |
| | INDICATE ON THE PRODUCT APPROVAL, OR OTHERWISE, HOW YOU |
| | FOLLOWED THE INSTRUCTIONS ON SHEET 1 OF 9 FOR THE |
| | MULLION, AND SHOW THE SELECTED ANCHOR OPTION YOU ARE |
| | CHOOSING. |
| | |
| | THE APPLICATION STATES A VALUE OF $2,800.00 HOWEVER, |
| | THERE IS A CONTRACT ATTACHED INDICATING A VALUE OF |
| | $4,200.00 THE VALUE WILL BE ADJUSTED TO $4,200.00. |
| | |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | |