Plan Review Details - Permit 14110845
Plan Review Stops For Permit 14110845
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-01-22 Cont ID  
Sent By jgomez Date 2016-01-22 Time 15:38 Rev Time 0.00
Received By jgomez Date 2016-01-22 Time 15:37 Sent To  
Notes
2016-01-22 15:38:37 
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-12-28 Cont ID  
Sent By jgomez Date 2015-12-28 Time 12:23 Rev Time 0.00
Received By jgomez Date 2015-12-28 Time 12:23 Sent To  
Notes
2015-12-28 12:25:44RESIDENTIAL (R3) ADDITION, FOURTH BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1-PROVIDE DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE
 WITH THE NEW ROOF CROSS VENTILATION AS REQUIRED BY SEC.
 R806 OF 2010 FBC-RESIDENTIAL. (REPEAT COMMENT).
 RESPONSE:
 ENGINEER STATED ON TYPICAL WALL SECTION ON SHEET S-300
 THAT "ATTIC TO BE UNVENTED SPACE AS PER FBC-RESIDENTIAL
 SECTION 806.4". SPECIFICATIONS SHOWN ON THE TYPICAL
 WALL SECTION DON'T COMPLY WITH SEC. R806.4 FOR AN
 UNVENTED ATTIC ASSEMBLY. THE LOCATION OF THE INSULATION
 IS INCORRECT. SEE SEC. R806.4 AND REVISE AS REQUIRED.
 AND, CLEARLY SPECIFY WHICH OPTION OF ITEM #4 OF SEC.
 R806.4 IS GOING TO BE INSTALLED.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED SHEET. DON'T STAPPLE OLD
 COPY TO PLANS. SUBMITT OLD COPIES FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-11-25 Cont ID  
Sent By jgomez Date 2015-11-25 Time 16:05 Rev Time 0.00
Received By jgomez Date 2015-11-25 Time 16:05 Sent To  
Notes
2015-11-25 16:08:46RESIDENTIAL (R3) ADDITION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 NOTE:
 NEW SET OF DRAWINGS SUBMITTED DONE BY ANOTHER ENGINEER
 OF RECORD.
  
 1- SHEET S-000: CODE REFERENCED ON THE WIND LOADING
 (MWFRS) DOESN'T MATCH CODE REFERENCED ON THE WIND
 LOADING (C&C). REVISE AS REQUIRED TO MATCH. NOTE: THE
 CODE UNDER WHICH THE REVIEWS ARE DONE FOR THIS PROJECT
 IS THE 2010 FBC.
  
 2- PROVIDE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE NEW ROOF CROSS VENTILATION AS
 REQUIRED BY SEC. R806 OF 2010 FBC-RESIDENTIAL.
 INFORMATION SHOWN ON THE TYPICAL WALL SECTION ON SHEET
 S-300 IS NOT CLEAR. IT'S NOT CLEAR IF ENGINEER OF
 RECORD IS DESIGNING AN UNVENTED ATTIC OR A VENTED
 ATTIC. NOT CLEAR WHY SPECIFYING RIGID BOARD R-5
 INSULATION ABOVE ROOF SHEATHING AND R-30 BATT
 INSULATION BETWEEN ROOF JOISTS. AND, THERE ARE
 SPECIFICATIONS FOR "PROTECTED ROOF VENTS FOR ROOF CROSS
 VENTILATION". ON THE OTHER HAND, THE WAY THE CROSS
 VENTILATION IS SPECIFIED DOESN'T PROVIDE CROSS
 VENTILATION. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- FOUNDATION SCHEDULE ON SHEET S-301 IS MISSING ONE
 DIMENSION FOR FOOTING WF-1. PROVIDE COMPLETE
 INFORMATION. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- ROOF FRAMING PLAN ON SHEET S-101: SPECIFY SPACING OF
 2X12 JOISTS. SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 5- BASED ON THE EXTERIOR ELEVATIONS SHOWN ON SHEET
 S-200, THERE DOESN'T SEEM TO BE 24" CLEAR CRAWL SPACE
 AS SHOWN ON TYPICAL WALL SECTION ON SHEET S-300.
 CLARIFY AS REQUIRED. CLEARLY PROVIDE THE CRAWL SPACE
 CLEARANCE THAT MATCHES EXTERIOR ELEVATIONS. THIS IS
 IMPORTANT BECAUSE THE FLOOR JOIST NEED TO COMPLY WITH
 THE WOOD DECAY PROTECTION AS REQUIRED BY SEC. R317.1 OF
 2010 FBC-RESIDENTIAL IF THE CLEARANCE IS LESS THAN 18"
 . ON THE OTHER HAND, THE EXTERIOR WOOD DECK MAY
 REQUIRED GUARDRAILS. SEE SEC. R312 OF 2010
 FBC-RESIDENTIAL.
  
 6- PROVIDE COMPLETE SPECIFICATIONS FOR TYPE OF CRAWL
 SPACE ACCESS DOOR. SEC. 107.2.1 CITY AMENDMENTS.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 F.A.C. 61G20-3.002(33) FOR:
 A) CRAWL SPACE ACCESS DOOR AS SHOWN ON PLANS.
  
 8- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ABOVE PRODUCT APPROVAL. SEC.
 107.3.4.1 OF CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED SHEET. DON'T STAPPLE OLD
 COPY TO PLANS. SUBMITT OLD COPIES FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-08-24 Cont ID  
Sent By jgomez Date 2015-08-24 Time 14:00 Rev Time 0.00
Received By jgomez Date 2015-08-24 Time 14:00 Sent To  
Notes
2015-08-24 13:59:51RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 NOTE:
 PLEASE REMOVE FROM THE DRAWINGS THE NUMBERS THAT
 IDENTIFY EACH COMMENT FROM THE FIRST CHECKLIST. THIS
 NUMBERS CREATE CONFUSION. ANY REVISIONS TO THE PLANS
 ARE USUALLY MARKED AS A CLOUD AND THE NUMBER OF THE
 REVISION IS INSIDE A SMALL TRIANGLE. IN THIS CASE IT
 WOULD BE REVISION #1.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ROOF
 DRAINAGE SHOWING COMPLIANCE WITH THE ROOF DRAINAGE SEC.
 R903.4 OF 2010 FBC-RESIDENTIAL. SPECIFY SIZE OF ROOF
 DRAIN OR SCUPPER. SPECIFY SIZE OF DOWNSPOUT.
  
 ***RESPONSE: INFORMATION SHOWN ON THE SOUTH ELEVATION
 IS INCORRECT. SCUPPERS SHALL BE PLACED LEVEL WITH THE
 ROOF SURFACE. PROVIDE COMPLETE DETAIL/SECTION THRU THE
 SCUPPERS.
  
 3- ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT AWAY
 FROM THE STRUCTURE. REVISE PLANS AS REQUIRED.
  
 ***RESPONSE: DOWNSPOUTS WERE REVISED BUT ARE MISSING
 THE SPLASH BLOCKS.
  
 4- NEED TO SPECIFY OVERFLOW SCUPPERS SIZE AND LOCATION
 AS REQUIRED BY SEC. R903.4.1 OF 2010 FBC-RESIDENTIAL.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 5- PROVIDE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE NEW ROOF CROSS VENTILATION AS
 REQUIRED BY SEC. R806 OF 2010 FBC-RESIDENTIAL.
  
 ***RESPONSE: NEED TO SPECIFY SPACING OF THE VENTS
 SPECIFIED ON THE WALL SECTION ON SHEET S-2.
  
 6- NEW WOOD DECK SHOWN ON FOUNDATION PLAN ON SHEET S-2:
 A)PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 THAT MATCH THE PROPOSED WOOD DECK.
  
 ***RESPONSE: (1) SPECIFY HOW MUCH EMBEDMENT IS REQUIRED
 FOR THE 3/4" EXPANSION BOLTS SPECIFIIED TO FASTEN THE
 2X10 WOOD LEDGER. (2) SPECIFY THE DEPTH OF THE PRE FAB
 CONCRETE PADS. (3) SPECIFY THE CONNECTORS AT THE ENDS
 OF THE (2)2X10 BEAMS. (4) CLARIFY WHAT ARE THE BLACK
 SQUARES SHOWN ON TOP OF THE 12"X12" PRE FAB PADS?. SEC.
 R301.1 OF 2010 FBC-RESIDENTIAL.
  
 B) PROVIDE MANUFACTURER'S COMPLETE SPECIFICATIONS (2
 COPIES) FOR THE 12" X 12" PRE-FAB CONC. PADS SPECIFIED
 ON FOUNDATION PLAN TO VERIFY COMPLIANCE WITH SEC. R301.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 7- FLOOR FRAMING PLAN ON SHEET S-2: CLEARLY SPECIFY
 SIZES AND LOCATION OF ALL UNDER-FLOOR SPACE VENTILATION
 OPENINGS SHOWING COMPLIANCE WITH SEC R408 OF 2010
 FBC-RESIDENTIAL. AND CLEARLY SPECIFY THE SIZE OF CRAWL
 SPACE ACCESS OPENING.
  
 ***RESPONSE: LOCATION OF OPENINGS DON'T COMPLY WITH
 SEC. R408.2. AND, CLARIFY NOTE SHOWN ON THE FLOOR
 FRAMIING PLAN: WHAT'S "24"X24" CRAWL SPACE LOCATION"?
 IS THIS THE ACCES TO THE CRAWL SPACE? REVISE AS
 REQUIRED TO CLARIFY.
  
 8- WALL SECTION ON SHEET S-2:
 A) SPECIFY STUCCO THICKNESS. TABLE R702.1(1) OF 2010
 FBC-RESIDENTIAL.
  
 ***RESPONSE: REVISE THICKNESS. 5/8" THICKNESS IS
 INCORRECT. SEE TABLE R702.1(1).
  
 B) SPECIFY HOW ARE THE TWO BOTTOM PLATES ATTACHED TO
 THE STEM WALL TO SHOW COMPLIANCE WITH SEC. R601.2 OF
 2010 FBC-RESIDENTIAL.
  
 ***RESPONSE: CLARIFY HOW MUCH EMBEDMENT IS REQUIRED FOR
 THE 3/4" D. X 16" THRU BOLT. LENGTH OF THE ANCHOR
 SPECIFIED MAY BE TOO SHORT.
  
 9- WINDOW AND DOOR FRAMING DETAILS ON SHEET S-2: REVISE
 INFORMATION TO MATCH PROPOSED CONSTRUCTION. SEC.
 107.2.1 CITY AMENDMENTS.
  
 ***RESPONSE: SIMPSON SPH4Z CONNECTOR DOESN'T FIT ON A
 2X6 STUD. REVISE AS REQUIRED. ALSO, COORDINATE
 INFORAMTION WITH INFORMATION SHOWN ON THE WALL SECTION.
 SEE NUMBER OF BOTTOM PLATES, CONNECTORS, ETC.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 F.A.C. 61G20-3.002(33) FOR:
 A) FLAT ROOF: NOA 13-0424.14 SUBMITTED EXPIRED ON
 11/06/14. NEED TO PROVIDE CURRENT NOA.
 IN ADDITION: (1) CLEARLY IDENTIFY WHICH APPROVED
 ASSEMBLY IS GOING TO BE INSTALLED. AND, PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED.
  
 ***RESPONSE: (1) SPECIFY WHICH APPROVED ASSEMBLY FROM
 NOA 12-0716.18 SUBMITTED IS GOING TO BE INSTALLED. AND,
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA.
 NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CAN NOT BE
 USED..
 (2) INFORMATION SHOWN ON SHEET S-2 ABOVE THE ROOF
 FRAMING PLAN DOESN'T MATCH NOA SUBMITTED AND IS FOR AN
 NOA THAT EXPIRED ON NOV. OF 2013.
  
 B) DOUBLE FRENCH DOOR AS SHOWN ON PLANS. AND, SPECIFY
 SIZE OF REVISED DOOR. (CHANGED FROM BIFOLD TO FRENCH
 DOOR).
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND ALL DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR ENGINEER MAY LIST THE FLORIDA PRODUCT
 APPROVAL NEXT TO THE SPECIFIED CONNECTOR.
  
 ***RESPONSE: NEED TO PROVIDE FLORIDA PRODUCT APPROVAL
 FOR ALL CONNECTORS SPECIFIED ON ALL DETAILS, FRAMING
 PLANS AND WALL SECTION. THERE ARE SOME CONNECTORS THAT
 ARE NOT LISTED ON THE FLORIDA PRODUCT APPROVAL PACKAGE
 SUBMITED AT THIS TIME.
  
 D) CRAWL SPACE ACCESS DOOR AS SHOWN ON PLANS.
  
 ***NOTE: CLARIFY WHY SUBMITTING SINGLE HUNG WINDOWS NOA
 11-0426.03. PLANS DON'T SPECIFY THIS TYPE OF WINDOW.
  
 11- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC.
 107.3.4.1 OF CITY AMENDMENTS. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 ***PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT TO
 EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-19 Cont ID  
Sent By jgomez Date 2014-12-19 Time 10:27 Rev Time 0.00
Received By jgomez Date 2014-12-19 Time 09:53 Sent To  
Notes
2014-12-19 10:48:47RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS
 CODE: 2010 FBC.
  
 1 BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND
 DEVELOPMENT CODE.
  
 2- SHEET S-1:
 A) CONSTRUCTION OF NEW WALL ADJACENT TO THE EXISTING
 WALL IS NOT CLEAR. PROVIDE CLEAR WALL SECTION FROM
 FOOTING TO ROOF PARAPET AND PROVIDE CLEAR
 SPECIFICATIONS. HOW IS THE NEW WALL ATTACHED TO
 EXISTING WALL. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 B) REVISE THE TYPE OF ALTERATION SPECIFIED UNDER THE
 SCOPE OF WORK BUILDING CODES INFORMATION. THIS IS NOT
 ALTERATION LEVEL 3. THIS IS AN ADDITION. SEC. 407 OF
 2010 FBC-EXISTING BUILDING.
  
 C) REVISE/CLARIFY THE DESIGN LOADS INFORMATION SHOWN ON
 THE RIGHT BOTTOM OF DRAWING S-1. SPECIFY ROOF LOADS FOR
 TYPE OF PROPOSED ROOF (FLAT) AND FOR FLOOR JOISTS (NOT
 FLOOR TRUSSES). SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 D) SPECIFY ROOF SLOPE. SEC. R905.11.1 OF 2010
 FBC-RESIDENTIAL.
  
 3- EXISTING WINDOW IN MASTER BEDROOM IS PROPOSED TO BE
 REMOVED TO ALLOW FOR THE NEW MASTER BATHROOM ADDITION.
 CLEARLY IDENTIFY ON PLANS HOW IS THE ALTERED MASTER
 BEDROOM COMPLYING WITH THE EGRESS REQUIREMENTS OF SEC.
 R310 OF 2010 FBC-RESIDENTIAL.
  
 4- IDENTIFY ON PLANS THE ROOM LOCATED ON THE RIGHT HAND
 SIDE OF EXISTING BATHROOM. IS THIS A BEDROOM?.
 ACCORDING TO PLANS THE WINDOWS IN THIS ROOM ARE GOING
 TO BE REPLACED. SPECIFY TYPE AND SIZE OF EXISTING
 WINDOW AND PROPOSED TYPE AND SIZE TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. R310 OF 2010
 FBC-RESIDENTIAL.
  
 5- THERE WAS A WINDOW ON THE EXISTING BATHROOM THAT IS
 PROPOSED TO BE BLOCKED TO ALLOW FOR THE NEW MASTER
 BATHROOM ADDITION. CLEARLY SPECIFY ON PLANS HOW IS THIS
 BATHROOM COMPLYING WITH THE MECHANICAL VENTILATION
 REQUIRED BY SEC. R303.3 OF 2010 FBC-RESIDENTIAL.
  
 6- SPECIFY CARBON MONOXIDE ALARMS IN ALL SLEEPING ROOMS
 AS REQUIRED BY SEC. R315 OF 2010 FBC-RESIDENTIAL.
  
 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ROOF
 DRAINAGE SHOWING COMPLIANCE WITH THE ROOF DRAINAGE SEC.
 R903.4 OF 2010 FBC-RESIDENTIAL. SPECIFY SIZE OF ROOF
 DRAIN OR SCUPPER. SPECIFY SIZE OF DOWNSPOUT.
 INFORMATION SHOWN ON THE SOUTH ELEVATION IS NOT CLEAR.
 WHAT'S A "BRAKE METAL LEADER BOX & DOWNSPOUT." ??? WHY
 IS IT SHOWN ABOVE THE FINISH ROOF LINE? ???
  
 8- ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT AWAY
 FROM THE STRUCTURE. REVISE PLANS AS REQUIRED.
  
 9- NEED TO SPECIFY OVERFLOW SCUPPERS SIZE AND LOCATION
 AS REQUIRED BY SEC. R903.4.1 OF 2010 FBC-RESIDENTIAL.
  
 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE GUARDRAILS SHOWN ON THE NEW WOOD
 DECK SHOWING COMPLIANCE WITH THE LIVE LOADS OF TABLE
 R301.5 AND SEC. R312 OF 2010 FBC-RESIDENTIAL.
  
 11- REVISE/CLARIFY INFORMATION ON INTERIOR PARTITION
 DETAIL ON SHEET S-1:
 A) THERE IS NOT EXISTING CONCRETE SLAB. THIS IS AN
 ADDITION. SEE FLOOR FRAMING PLAN AND REVISE THE
 FLOORING AND BASE PLATE FASTENING SPECIFICATIONS. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 B) CLARIFY NOTE STATING "8D RING SHANK NAILS AT EA.
 TRUSS OR 24" O.C. MAX". CLEARLY SPECIFY TOP PLATE
 FASTENING TO THE 2X12 ROOF RAFTER. SPECIFICATIONS TO
 MATCH INFORMATION SHOWN ON THE ROOF FRAMING PLAN. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 12- PROVIDE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE NEW ROOF CROSS VENTILATION AS
 REQUIRED BY SEC. R806 OF 2010 FBC-RESIDENTIAL.
  
 13- NEW WOOD DECK SHOWN ON FOUNDATION PLAN ON SHEET
 S-2:
 A)PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 THAT MATCH THE PROPOSED WOOD DECK. INFORMATION
 SUBMITTED IS GENERIC DOESN'T MATCH PROPOSED DECK AND IS
 MISSING ALL THE STRUCTURAL INFORMATION. CLEARLY SPECIFY
 ALL MEMBERS SIZES (POSTS, BEAMS, ETC)AND SPACING,
 NUMBER OF FRAMING MEMBERS AT THE PERIMETER, ALL
 FASTENERS, ETC. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 B) PROVIDE MANUFACTURER'S COMPLETE SPECIFICATIONS (2
 COPIES) FOR THE 12" X 12" PRE-FAB CONC. PADS SPECIFIED
 ON FOUNDATION PLAN TO VERIFY COMPLIANCE WITH SEC. R301.
  
 14- FOUNDATION PLAN ON SHEET S-2: CLARIFY WHY IS THERE
 AN OPENING SHOWN ON THE SOUTH SIDE WALL OF THE STEM
 WALL. WHAT IS THIS OPENING FOR?. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 15- FLOOR FRAMING PLAN ON SHEET S-2: :
 A) CLEARLY SPECIFY SIZES AND LOCATION OF ALL
 UNDER-FLOOR SPACE VENTILATION OPENINGS SHOWING
 COMPLIANCE WITH SEC R408 OF 2010 FBC-RESIDENTIAL. AND
 CLEARLY SPECIFY THE SIZE OF CRAWL SPACE ACCESS OPENING.
  
 B) PROVIDE SPECIFICATIONS FOR THE TYPE OF FLOOR JOIST
 TO BE USED TO SHOW COMPLIANCE WITH PROTECTION OF WOOD
 AS REQUIRED BY SEC. R317 OF 2010 FBC-RESIDENTIAL.
  
 16- WALL SECTION ON SHEET S-2:
 A) SPECIFY STUCCO THICKNESS. TABLE R702.1(1) OF 2010
 FBC-RESIDENTIAL.
  
 B) SPECIFY 2 LAYERS OF WATER RESISTANT BARRIER AS
 REQUIRED BY SEC. R703.6.3 OF 2010 FBC-RESIDENTIAL.
  
 C) SPECIFY HOW ARE THE TWO BOTTOM PLATES ATTACHED TO
 THE STEM WALL TO SHOW COMPLIANCE WITH SEC. R601.2 OF
 2010 FBC-RESIDENTIAL.
  
 D) SPECIFY THE HORIZONTAL REINFORCEMENT FOR STEM WALL
 "U" BLOCK. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 E) PROVIDE COMPLETE SPECIFICATIONS FOR THE FASTENING OF
 THE PARAPET WALL. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 17- WINDOW FRAMING DETAIL AND DOOR FRAMING DETAIL ON
 SHEET S-2: REVISE INFORMATION TO MATCH PROPOSED
 CONSTRUCTION. REVISE THE FLOOR TYPE, STUDS SIZES, ROOF
 FRAMING, ETC. SEC. 107.2.1 CITY AMENDMENTS.
  
 18- ROOF FRAMING DETAIL ON SHEET S-2: SPECIFY THE ROOF
 SHEATHING NAIL TYPE AND SIZE AND SPACING AS REQUIRED BY
 SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL.
  
 19- INFORMATION ON PLANS NEED TO MATCH INFORMATION ON
 THE ENERGY CALCULATIONS SUBMITTED. SPECIFY INSULATION
 OVER CRAWL SPACE. REVISE R VALUE FOR EXTERIOR WALLS.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 20- PROVIDE MANUFACTURER SPECS FOR THE WINDOWS AND
 DOORS U-FACTOR AND SHGC FACTOR SHOWING COMPLIANCE WITH
 THE VALUES SPECIFIED ON THE ENERGY CALCULATIONS
 SUBMITTED. SEC. R103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 21- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE ENERGY CALCULATIONS FOR THE ADDITION ONLY OR
 FOR ENTIRE HOUSE. DON'T MIX MATCH BOTH. COOLING AND
 HEATING INFORMATION SHOWN ON ITEMS #12 AND #13 DON'T
 CORRESPOND TO THE ADDITION ALONE. REVISE AS REQUIRED.
 SEC. 101.4.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) REVISE FLOOR TYPE INFORMATION ON ITEM #8. THERE IS
 NO CONCRETE SLAB ON GRADE. SEE PLANS. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 C) REVISE UNDER ATTIC INFORMATION ON ITEM # 10.
 COORDINATE WITH PLANS IF ATTIC VENTILATION IS PROVIDED
 OR NOT. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 D) REVISE THE WINDOWS OVERHANG SEPARATION TO MATCH
 ACTUAL SEPARATION SHOWN ON PLANS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 E) WALLS INFORMATION ON PAGE 3 OF 5 IS MISSING THE
 SOUTH WALL INFORMATION. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 F) WINDOWS AREA ON PAGE 3 OF 5 DOESN'T MATCH ACTUAL
 WINDOW AREA. SEE PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 ****NOTE: THIS IS A CONTRIBUTING HISTORIC HOUSE. IT'S
 EXEMPT FROM THE ENERGY CODE. ENERGY CALCULATIONS ARE
 NOT REQUIRED. IF YOU ARE GOING TO SUBMIT THEM, THEN
 MAKE ABOVE CORRECTIONS.
  
 22- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) FLAT ROOF: NOA 13-0424.14 SUBMITTED EXPIRED ON
 11/06/14. NEED TO PROVIDE CURRENT NOA.
 IN ADDITION: (1) CLEARLY IDENTIFY WHICH APPROVED
 ASSEMBLY IS GOING TO BE INSTALLED. AND, PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED.
  
 B) BIFOLD EXTERIOR DOOR AS SHOWN ON PLANS.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND ALL DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR ENGINEER MAY LIST THE FLORIDA PRODUCT
 APPROVAL NEXT TO THE SPECIFIED CONNECTOR.
  
 23- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 107.3.4.1 OF CITY
 AMENDMENTS.
  
 24- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION WAS UPDATED TO $24,000. THE VALUATION TO
 INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND
 PROFIT AND ALL DESIGN PROFESSIONAL FEES AS REQUIRED BY
 SEC. 109.3 CITY AMENDMENTS. THE PERMIT FEE BALANCE IS
 $556.80.
  
 ***PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT TO
 EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-09-24 Cont ID  
Sent By skennedy Date 2015-09-24 Time 17:36 Rev Time 0.00
Received By skennedy Date 2015-09-24 Time 17:36 Sent To  
Notes
2015-08-24 11:20:44NEW DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-27 Cont ID  
Sent By skennedy Date 2014-12-27 Time 12:33 Rev Time 0.00
Received By skennedy Date 2014-12-27 Time 12:33 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2015-11-18 Cont ID  
Sent By gjohnson Date 2015-11-18 Time 14:29 Rev Time 0.00
Received By gjohnson Date 2015-11-18 Time 14:29 Sent To  
Notes
2015-11-18 14:29:21REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  
 GAS COMMENTS:
 1.GAS NOT REVIEWED UNDER THIS PERMIT SEPERATE PERMIT
 REQUIRED FOR GAS
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-09-25 Cont ID  
Sent By gjohnson Date 2015-09-25 Time 14:22 Rev Time 0.00
Received By gjohnson Date 2015-09-25 Time 14:22 Sent To  
Notes
2015-09-25 14:27:45 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  
 GAS COMMENTS:
  
  
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
 6. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 .
 8. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 9. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE
 OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF THE
 TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  
  
2015-08-25 13:55:36SEE REVISED SHEET E-1.

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2015-12-03 Cont ID  
Sent By fmittner Date 2015-12-03 Time 11:12 Rev Time 0.00
Received By fmittner Date 2015-12-03 Time 11:12 Sent To  
Notes
2015-11-25 16:02:59NEW SET OF PLANS SUBMITTED. DIFFERENT ENGINEER OF
 RECORD.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-10-06 Cont ID  
Sent By fmittner Date 2015-10-06 Time 16:35 Rev Time 0.00
Received By fmittner Date 2015-10-06 Time 16:35 Sent To  
Notes
2015-08-24 11:19:55NEW DRAWINGS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-11-21 Cont ID  
Sent By fmittner Date 2014-11-21 Time 15:59 Rev Time 0.00
Received By fmittner Date 2014-11-21 Time 15:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2016-01-26 Cont ID  
Sent By jgomez Date 2016-01-26 Time 11:44 Rev Time 0.00
Received By jgomez Date 2016-01-26 Time 11:42 Sent To  
Notes
2016-01-26 11:42:25IMPACT FEES. JG

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-01-22 Cont ID  
Sent By jgomez Date 2016-01-22 Time 15:37 Rev Time 0.00
Received By jgomez Date 2016-01-15 Time 15:05 Sent To  
Notes
2016-01-19 15:05:42RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-12-28 Cont ID  
Sent By jgomez Date 2015-12-28 Time 18:56 Rev Time 0.00
Received By jgomez Date 2015-12-09 Time 10:07 Sent To  
Notes
2015-12-10 10:07:25RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-03 Cont ID  
Sent By lmarchan Date 2015-12-03 Time 13:54 Rev Time 0.00
Received By lmarchan Date 2015-11-16 Time 09:28 Sent To  
Notes
2015-11-18 09:28:17RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-11 Cont ID  
Sent By skennedy Date 2015-10-11 Time 13:08 Rev Time 0.00
Received By skennedy Date 2015-08-07 Time 15:58 Sent To  
Notes
2015-08-25 09:32:378/25/15 PLANS SENT TO R3 SHELF FOR REVIEW. JG.
2015-08-07 16:00:14JGOMEZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-27 Cont ID  
Sent By skennedy Date 2014-12-27 Time 12:36 Rev Time 0.00
Received By skennedy Date 2014-11-21 Time 09:59 Sent To  
Notes
2014-11-22 09:59:59R15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 6 Status P Date 2016-01-26 Cont ID  
Sent By jgomez Date 2016-01-26 Time 11:43 Rev Time 0.00
Received By jgomez Date 2016-01-26 Time 11:42 Sent To  
Notes
2016-01-26 11:44:35$236.59 PAID. MU-2016-1855.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status F Date 2016-01-22 Cont ID  
Sent By jgomez Date 2016-01-22 Time 16:28 Rev Time 0.00
Received By jgomez Date 2016-01-22 Time 16:28 Sent To  
Notes
2016-01-22 16:28:321- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2015-12-28 Cont ID  
Sent By jgomez Date 2015-12-28 Time 18:55 Rev Time 0.00
Received By jgomez Date 2015-12-28 Time 18:55 Sent To  
Notes
2015-12-28 18:56:141- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-11-25 Cont ID  
Sent By jgomez Date 2015-11-25 Time 18:43 Rev Time 0.00
Received By jgomez Date 2015-11-25 Time 18:43 Sent To  
Notes
2015-11-25 18:43:471- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-08-25 Cont ID  
Sent By jgomez Date 2015-08-25 Time 08:47 Rev Time 0.00
Received By jgomez Date 2015-08-25 Time 08:47 Sent To  
Notes
2015-08-25 08:47:341- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-12-19 Cont ID  
Sent By jgomez Date 2014-12-19 Time 10:24 Rev Time 0.00
Received By jgomez Date 2014-12-19 Time 10:24 Sent To  
Notes
2014-12-19 10:26:441- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-11-30 Cont ID  
Sent By jgomez Date 2015-11-30 Time 10:50 Rev Time 0.00
Received By jgomez Date 2015-11-30 Time 10:50 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-08-25 Cont ID  
Sent By jgomez Date 2015-08-25 Time 08:48 Rev Time 0.00
Received By jgomez Date 2015-08-25 Time 08:48 Sent To  
Notes
2015-08-25 08:58:18RESIDENTIAL (R3) ADDITION SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PERSON RESPONSIBLE FOR THE M.1 DRAWING TO PROVIDE
 NAME AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY
 AMENDMENTS TO FBC. (REPEAT COMMENT. NOT ADDRESSED).
  
 2- A) EQUIPMENT INFORMATION IS NOT CLEAR. DRAWINGS S-1
 AND E-1 SHOW ONE A/C UNIT. DRAWING M.1 SUBMITTED SHOWS
 TWO A/C UNITS. COORDINATE ALL PLANS AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS. (REPEAT COMMENT.
 MECHANICAL PLAN AND ENGINEER'S PLANS DON'T MATCH.
 INFORMATION NEEDS TO BE COORDINATED TO AVOID
 UNNECESSARY DELAYS AND CONFLICTS.)
  
 B) MECHANICAL PLAN CALLS FOR TWO "EXISTING A.H.U.".
 THIS IS MISLABELED. AIR HANDLER UNITS ARE LOCATED
 INSIDE THE HOUSE. COMPRESSORS ARE THE ONES THAT ARE
 LOCATED OUTSIDE. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- MECHANICAL PLAN DOESN'T SHOW LOCATION OF THE EXHAUST
 FAN FOR THE NEW BATHROOM AND FOR THE EXISTING BATHROOM
 WHICH WINDOW WAS CLOSED. REVISE AS REQUIRED. A/C PLANS
 AND ENGINEER'S PLANS NEED TO MATCH. . SEC. 107.2.1 CITY
 AMENDMENTS.
  
 4- INFORMATION SHOWN ON THE MECHANICAL PLAN M.1 AND
 INFORMATION SHOWN ON THE ELECTRICAL PLAN ON SHEET E-1
 DOESN'T MATCH. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-22 Cont ID  
Sent By jgomez Date 2014-12-22 Time 12:06 Rev Time 0.00
Received By jgomez Date 2014-12-22 Time 12:05 Sent To  
Notes
2014-12-22 12:18:50RESIDENTIAL (R3) ADDITION MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PERSON RESPONSIBLE FOR THE M.1 DRAWING TO PROVIDE
 NAME AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 2- EQUIPMENT INFORMATION IS NOT CLEAR. DRAWINGS S-1 AND
 E-1 SPECIFY TWO A/C UNITS. ONE AS EXISTING AND THE
 OTHER ONE AS PROPOSED. DRAWING M.1 SUBMITTED SPECIFIES
 "EXISTING A.H.U." FOR BOTH UNITS. COORDINATE ALL PLANS
 AS REQUIRED TO MATCH. CLEARLY, IDENTIFY WHAT'S NEW AND
 WHAT'S EXISTING. SEC. 107.2.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-12-12 Cont ID  
Sent By gjohnson Date 2015-12-12 Time 07:06 Rev Time 0.00
Received By gjohnson Date 2015-12-12 Time 07:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-11-18 Cont ID  
Sent By gjohnson Date 2015-11-18 Time 15:15 Rev Time 0.00
Received By gjohnson Date 2015-11-18 Time 15:15 Sent To  
Notes
2015-11-18 14:38:26REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
 1.2ND REQUEST PLEASE PROVIDE CALCULATIONS FOR ROOF
 SCUPPERS AND DOWN SPOUTS.
 PER WPB AMEND TO FBC SEC 107.2.1

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-08-27 Cont ID  
Sent By gjohnson Date 2015-08-27 Time 15:42 Rev Time 0.00
Received By gjohnson Date 2015-08-27 Time 15:42 Sent To  
Notes
2015-08-27 15:55:401ST REVIEW: FBC 2010
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  
 COMMENTS:
 1. SUBMIT CALCULATIONS FOR ROOF SCUPPERS AND
 DOWNSPOUTS.
 PER WPB AMEND. SEC 107.2.1.3
 2.SUBMIT WATER PIPE RISER DIAGRAM.
 PER WPB AMEND. SEC107.3.5.3(11)
 3.SUPPLY SPECS FOR TANKLESS WATER HEATER.
 PER WPB AMEND. SEC 107.2.1.3
 4.SEPARATE PERMIT MUST BE PULLED BY LICENSED CONTRACTOR
 FOR GAS.
 PER WPB AMEND. 105.1
  
2015-08-24 11:23:13NEW DRAWINGS SUBMITTED. SEE ALSO REVISED SHEET E-1. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-11-27 Cont ID  
Sent By tklarge Date 2014-11-27 Time 06:50 Rev Time 0.00
Received By tklarge Date 2014-11-27 Time 06:33 Sent To  
Notes
2014-11-27 06:51:41WATER RISER DIAGRAM REQD. @ 2ND ROUGH.

Review Stop Z ZONING
Rev No 3 Status P Date 2015-12-03 Cont ID  
Sent By fmittner Date 2015-12-03 Time 11:12 Rev Time 0.00
Received By fmittner Date 2015-12-03 Time 11:12 Sent To  
Notes
2015-11-25 16:03:16NEW SET OF PLANS SUBMITTED. DIFFERENT ENGINEER OF
 RECORD.

Review Stop Z ZONING
Rev No 2 Status P Date 2015-10-06 Cont ID  
Sent By fmittner Date 2015-10-06 Time 16:35 Rev Time 0.00
Received By fmittner Date 2015-10-06 Time 16:35 Sent To  
Notes
2015-08-24 11:24:08NEW DRAWINGS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2014-11-21 Cont ID  
Sent By fmittner Date 2014-11-21 Time 15:58 Rev Time 0.00
Received By fmittner Date 2014-11-21 Time 15:58 Sent To  
Notes
***NONE***