| Plan Review Stops For Permit 14110844 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2014-12-31 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2014-12-31 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-12-31 |
Time |
16:35 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-12-05 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-12-05 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-12-05 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2014-12-05 16:32:49 | 12/5/2014 | | | PROJECT: GENERATOR REPLACEMENT | | | PERMIT#: 14110844 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) REVISE RISER DIGRAM TO INDICATE ATS UTILITY (NORMAL | | | SIDE) FEED. BACK UP GENERATOR FEEDER IS CURRENTLY DRAWN | | | TO CONNECT DIRECTLY TO ANOTHER 350AMP MCB AND THERE IS | | | NO INDICATION OF WHAT IS FEEDING THE UTILITY SIDE OF | | | THE ATS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | | REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2014-12-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2014-12-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2014-12-19 |
Time |
12:12 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2014-12-01 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2014-12-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2014-12-01 |
Time |
13:46 |
Sent To |
E |
|
| Notes |
| 2014-12-01 13:56:40 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE REVIEW GAS REVIEW COMMENTS AND RESUBMIT. | | | | | | FIRE PREVENTION BUREAU DOES NOT HAVE ADDITIONAL | | | COMMENTS. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2014-12-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-12-19 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-12-19 |
Time |
06:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2014-11-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-11-26 |
Time |
06:52 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-11-26 |
Time |
06:47 |
Sent To |
|
|
| Notes |
| 2014-11-26 06:52:43 | 1) SUBMIT MANUF. SPEC. SHEETS/INSTALLATION MANUAL FOR | | | THE GENERATOR. WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 2) SHT. E-2 NOTE #6 STATES THAT THE LP GAS LINE IS TO | | | BE EXTENDED. INDICATE THE LINEAL FOOTAGE THAT THE GAS | | | LINE WILL BE EXTENDED AND THE TYPE OF PIPE TO BE USED. | | | SUBMIT A GAS RISER DIAGRAM SHOWING THE BTU LOAD OF THE | | | GENERATOR, THE TOTAL DISTANCE FROM THE LP TANK TO THE | | | GENERATOR, PSI OF THE GAS AND LOCATION OF ALL | | | REGULATORS. NFPA 58. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-01-14 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-01-14 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-12-18 |
Time |
12:31 |
Sent To |
|
|
| Notes |
| 2014-12-18 12:32:14 | RE-SUBMITTAL SENT TO TIM LARGE FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-12-05 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-12-05 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2014-11-21 15:35:33 | ROUTED TO ZONING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2015-01-14 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-01-14 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-01-14 |
Time |
08:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2014-11-24 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2014-11-24 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2014-11-24 |
Time |
15:24 |
Sent To |
E |
|
| Notes |
|
|