Plan Review Details - Permit 14110844
Plan Review Stops For Permit 14110844
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-12-31 Cont ID  
Sent By sgraham Date 2014-12-31 Time 16:43 Rev Time 0.00
Received By dhayes Date 2014-12-31 Time 16:35 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-05 Cont ID  
Sent By dhayes Date 2014-12-05 Time 16:33 Rev Time 0.00
Received By dhayes Date 2014-12-05 Time 16:10 Sent To  
Notes
2014-12-05 16:32:4912/5/2014
 PROJECT: GENERATOR REPLACEMENT
 PERMIT#: 14110844
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE RISER DIGRAM TO INDICATE ATS UTILITY (NORMAL
 SIDE) FEED. BACK UP GENERATOR FEEDER IS CURRENTLY DRAWN
 TO CONNECT DIRECTLY TO ANOTHER 350AMP MCB AND THERE IS
 NO INDICATION OF WHAT IS FEEDING THE UTILITY SIDE OF
 THE ATS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-12-19 Cont ID  
Sent By pleduc Date 2014-12-19 Time   Rev Time 0.00
Received By pleduc Date 2014-12-19 Time 12:12 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-12-01 Cont ID  
Sent By pleduc Date 2014-12-01 Time   Rev Time 0.00
Received By pleduc Date 2014-12-01 Time 13:46 Sent To E
Notes
2014-12-01 13:56:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE REVIEW GAS REVIEW COMMENTS AND RESUBMIT.
  
 FIRE PREVENTION BUREAU DOES NOT HAVE ADDITIONAL
 COMMENTS.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-12-19 Cont ID  
Sent By tklarge Date 2014-12-19 Time 09:37 Rev Time 0.00
Received By tklarge Date 2014-12-19 Time 06:49 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-11-26 Cont ID  
Sent By tklarge Date 2014-11-26 Time 06:52 Rev Time 0.00
Received By tklarge Date 2014-11-26 Time 06:47 Sent To  
Notes
2014-11-26 06:52:431) SUBMIT MANUF. SPEC. SHEETS/INSTALLATION MANUAL FOR
 THE GENERATOR. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SHT. E-2 NOTE #6 STATES THAT THE LP GAS LINE IS TO
 BE EXTENDED. INDICATE THE LINEAL FOOTAGE THAT THE GAS
 LINE WILL BE EXTENDED AND THE TYPE OF PIPE TO BE USED.
 SUBMIT A GAS RISER DIAGRAM SHOWING THE BTU LOAD OF THE
 GENERATOR, THE TOTAL DISTANCE FROM THE LP TANK TO THE
 GENERATOR, PSI OF THE GAS AND LOCATION OF ALL
 REGULATORS. NFPA 58.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-14 Cont ID  
Sent By dhayes Date 2015-01-14 Time 08:41 Rev Time 0.00
Received By dhayes Date 2014-12-18 Time 12:31 Sent To  
Notes
2014-12-18 12:32:14RE-SUBMITTAL SENT TO TIM LARGE FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-05 Cont ID  
Sent By dhayes Date 2014-12-05 Time 16:33 Rev Time 0.00
Received By dhayes Date   Time   Sent To  
Notes
2014-11-21 15:35:33ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2015-01-14 Cont ID  
Sent By sgraham Date 2015-01-14 Time 08:39 Rev Time 0.00
Received By sgraham Date 2015-01-14 Time 08:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-11-24 Cont ID  
Sent By sgraham Date 2014-11-24 Time 15:24 Rev Time 0.00
Received By sgraham Date 2014-11-24 Time 15:24 Sent To E
Notes
***NONE***