Plan Review Details - Permit 14110798
Plan Review Stops For Permit 14110798
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-01-08 Cont ID  
Sent By jwitmer Date 2015-01-08 Time 15:26 Rev Time 0.00
Received By jwitmer Date 2015-01-08 Time 15:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-04 Cont ID  
Sent By jwitmer Date 2014-12-04 Time 10:30 Rev Time 0.00
Received By jwitmer Date 2014-12-04 Time 08:53 Sent To  
Notes
2014-12-04 10:29:59BUILDING PLAN REVIEW
 PERMIT: 14110798
 ADD: 915 S. DIXIE HWY.
 CONT: OVERLAND
 TEL: (561)683-3210
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. DEC. 04/ 2014
 ACTION: DENIED
  
 1A) SHEET 3 OF 4 THE MEETING ROOM SHOWS THE SCOPE OF
 WORK IN THE MEETING ROOM AS WELL AS IN THE LOCKER ROOM.
 THE DOOR THAT LEADS FROM THE MEETING ROOM DOES NOT HAVE
 THE REQUIRED 18 INCHES ON THE LATCH SIDE OF THE DOOR.
 PLEASE SEE 2010 FL ACC. CODE 404.2.4.1 & TABLE
 404.2.4.1.
  
 1B) THE DOOR THAT LEADS FROM THE LOCKER ROOM TO THE
 EXISTING OFFICE ONLY HAS LESS THAN1 FOOT CLEARANCE FROM
 THE LOCKER TO THE EDGE OF THE DOOR, LATCH SIDE.
 NOTE THE PLANS DO NOT INDICATE IF THERE IS A DOOR
 CLOSER AND LATCH ON THIS DOOR? SEE 2010 FL. ACCESS.
 CODE FIGURE 404.2.4.1 (C).
  
 1C) THE PERMIT INDICATES THE PERMIT VALUE OF
 $80,000.00, THE 2010 FL ACCESS. CODE 202.4.1
 DISPROPORTIONATE COST REQUIRES 20% OF THE CONTRACT
 VALUE TO BE ACCESSIBLE UPGRADES AND IN THIS ORDER:
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 1D) THE SAME PLAN ALSO INDICATES A LOCKER ROOM, WITH
 BENCHES, PLEASE SHOW COMPLIANCE WITH THE 2010 FL
 ACCESS. CODE 803.1-803.5.
  
 2) SHEET 4 OF 4 THE REMODELED RESTROOMS, PLEASE PROVIDE
 THE LOCATION OF THESE RESTROOMS WITHIN THE BUILDING AND
 ON WHICH FLOOR THEY ARE LOCATED. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2A) THE FLOOR PLAN SHOWS GRAB RAILS TO BE USED IN
 CONJUNCTION WITH THE WATER CLOSET. THE PLANS LACKS:
 2A)(1) THE LOCATION OF THE SIDE WALL GRAB BAR, ACCESS.
 CODE 604.5.1
 2A)(2) THE LOCATION OF THE REAR WALL GRAB BAR, ACCESS.
 CODE 604.5.2.
  
 2B) PLEASE PROVIDE COMPLIANCE WITH 2010 FL ACCESS. CODE
 609.8 STRUCTURAL STRENGTH REQUIREMENTS.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-02-13 Cont ID  
Sent By dhayes Date 2015-02-13 Time 15:31 Rev Time 0.00
Received By dhayes Date 2015-02-13 Time 15:20 Sent To  
Notes
2015-02-13 15:32:36 
 NEC 422.51
 VENDING MACHINE OUTLETS REQUIRE GFI PROTECTION.
  
 FIRE ALARM BY SEPARATE PERMIT.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-01-08 Cont ID  
Sent By dhayes Date 2015-01-08 Time 16:41 Rev Time 0.00
Received By dhayes Date 2015-01-08 Time 16:26 Sent To  
Notes
2015-01-08 16:41:371/8/2015
 PROJECT: PB MOTOR CARS
 PERMIT#: 14110798
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE REVISED ELECTRICAL RISER DIAGRAM WITH WIRE
 SIZES , GROUNDING ELECTRODE SYSTEM WITH ELECTRODES AND
 ELECTRODE CONDUCTOR SIZES.
  
 2) PROVIDE CIRCUITRY ON THE FLOOR PLAN TO COINCIDE WITH
 THE CIRCUITRY IN THE PANEL SCHEDULES PROVIDED.
  
 3) PROVIDE THE REQUIRED GFI WITHIN SIGHT OF MECHANICAL
 EQUIPMENT. NEC 210.63 SEE 210.8(A)(3),
  
 4) ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GROUND FAULT CIRCUIT INTERRUPTER PROTECTION. NEC 422.52
  
 5) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR FIRE ALARM, NETWORK, DATA, AND,
 COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-11-21 Cont ID  
Sent By dhayes Date 2014-11-21 Time 11:03 Rev Time 0.00
Received By dhayes Date 2014-11-21 Time 11:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-01-06 Cont ID  
Sent By pleduc Date 2015-01-06 Time   Rev Time 0.00
Received By pleduc Date 2015-01-02 Time 12:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-11-25 Cont ID  
Sent By pleduc Date 2014-11-25 Time   Rev Time 0.00
Received By pleduc Date 2014-11-25 Time 12:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-02-13 Cont ID  
Sent By dhayes Date 2015-02-13 Time 15:32 Rev Time 0.00
Received By dhayes Date 2015-02-09 Time 07:13 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-13 Cont ID  
Sent By tklarge Date 2015-01-13 Time 13:20 Rev Time 0.00
Received By tklarge Date 2014-12-30 Time 08:44 Sent To  
Notes
2014-12-31 08:45:49B25
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-04 Cont ID  
Sent By jwitmer Date 2014-12-04 Time 10:30 Rev Time 0.00
Received By jwitmer Date 2014-11-20 Time 11:02 Sent To  
Notes
2014-11-21 11:30:28B03

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-12-03 Cont ID  
Sent By rbergsma Date 2014-12-03 Time   Rev Time 0.50
Received By rbergsma Date 2014-12-03 Time   Sent To  
Notes
2014-12-03 13:43:15ADDED DUCT SMOKE DETECTOR TO M-1, A/H CFM = 2100 ,
 APPROVED AS NOTED

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-02-11 Cont ID  
Sent By dhayes Date 2015-02-13 Time 15:32 Rev Time 0.00
Received By tklarge Date 2015-02-11 Time 11:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-01-13 Cont ID  
Sent By tklarge Date 2015-01-13 Time 13:19 Rev Time 0.00
Received By tklarge Date 2015-01-13 Time 13:11 Sent To  
Notes
2015-01-13 13:19:531) THE PLANS ONLY SHOW A MEN'S RESTROOM BEING
 RENOVATED. IS THERE A FEMALE RESTROOM BEING RENOVATED?
 IF SO, SUBMIT PLANS FOR THAT RESTROOM RENOVATION. 2ND
 REQUEST.
 2) INDICATE ON THE PLANS THE SPECIFIC SCOPE OF WORK TO
 BE DONE TO THIS RESTROOM. IS IT NEW OR EXISTING? ARE
 JUST THE PLUMBING FIXTURES BEING REPLACED? THE PLANS
 ARE VAGUE AS TO THE SCOPE OF WORK BEING DONE. WPB
 AMEND. TO 2010 FBC SEC.107.2.1.2ND REQUEST.
 3) MOUNTING HEIGHTS SHALL COMPLY WITH THE 2010 FL.
 ACCESSIBILITY CODE. CHAPTER 3 AND CHAPTER 6. THE GRAB
 BARS SHALL BE MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT THE CENTERLINE AS SHOWN. THE TOILET PAPER
 DISPENSER SHALL BE A MAXIMUM OF 48 INCHES ABOVE THE
 FINISH FLOOR MEASURED TO THE TOP OF THE DISPENSER PER
 FAC SEC.604.7.
 5) SHOW THE REQUIRED CLEAR FLOOR SPACES FOR THE
 LAVATORY AND THE WATER CLOSET ON THE PLANS. COMPLY WITH
 FAC SECS.306 & 604.2ND REQUEST.
 6) THE DRINKING FOUNTAIN/WATER COOLER CANNOT BE LOCATED
 IN THE RESTROOM PER THE 2010 FPC SEC. 410.2.2ND
 REQUEST.
 7) SHT. M-1 - SIZE ALL SECTIONS OF THE VENT SYSTEM.
 COMPLY WITH FPC TABLE 916.1. 2ND REQUEST.
 8) SIZE THE WET SECTION OF ALL WASTE /SOIL STACKS.TABLE
 710.1. 2ND REQUEST.
 9) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS PER
 FPC SEC. 708.3.4.2ND REQUEST.
 10) SUBMIT A WATER RISER DIAGRAM FOR ANY CHANGES BEING
 MADE TO THE PIPING SYSTEM. WPB AMEND. TO 2010 FBC SEC.
 107.3.5.1.3. 2ND REQUEST
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-27 Cont ID  
Sent By tklarge Date 2014-11-27 Time 05:19 Rev Time 0.00
Received By tklarge Date 2014-11-26 Time 11:30 Sent To  
Notes
2014-11-27 05:19:341) SUBMIT AN OVERALL FLOOR PLAN THAT SHOWS THE LOCATION
 OF THE RESTROOMS BEING RENOVATED. WPB AMEND. TO 2010
 FBC SEC.107.2.1.
 2) THE PLANS ONLY SHOW A MEN'S RESTROOM BEING
 RENOVATED. IS THERE A FEMALE RESTROOM BEING RENOVATED?
 IF SO, SUBMIT PLANS FOR THAT RESTROOM RENOVATION.
 3) INDICATE ON THE PLANS THE SPECIFIC SCOPE OF WORK TO
 BE DONE TO THIS RESTROOM. IS IT NEW OR EXISTING? ARE
 JUST THE PLUMBING FIXTURES BEING REPLACED? THE PLANS
 ARE VAGUE AS TO THE SCOPE OF WORK BEING DONE. WPB
 AMEND. TO 2010 FBC SEC.107.2.1.
 4) SUPPLY ELEVATION DETAILS FOR THE MOUNTING HEIGHTS OF
 ALL APPURTENANCES AND FIXTURES IN THE RESTROOM.
 MOUNTING HEIGHTS SHALL COMPLY WITH THE 2010 FL.
 ACCESSIBILITY CODE. CHAPTER 3 AND CHAPTER 6.
 5) SHOW THE REQUIRED CLEAR FLOOR SPACES FOR THE
 LAVATORY AND THE WATER CLOSET ON THE PLANS. COMPLY WITH
 FAC SECS.306 & 604.
 6) THE DRINKING FOUNTAIN/WATER COOLER CANNOT BE LOCATED
 IN THE RESTROOM PER THE 2010 FPC SEC. 410.2.
 7) SHT. M-1 - SIZE ALL SECTIONS OF THE VENT SYSTEM.
 COMPLY WITH FPC TABLE 916.1.
 8) SIZE THE WET SECTION OF ALL WASTE /SOIL STACKS.TABLE
 710.1.
 9) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS PER
 FPC SEC. 708.3.4.
 10) SUBMIT A WATER RISER DIAGRAM FOR ANY CHANGES BEING
 MADE TO THE PIPING SYSTEM. WPB AMEND. TO 2010 FBC SEC.
 107.3.5.1.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  