Plan Review Details - Permit 14110692
Plan Review Stops For Permit 14110692
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-12-07 Cont ID  
Sent By jgomez Date 2015-12-07 Time 12:11 Rev Time 0.00
Received By jgomez Date 2015-12-07 Time 12:11 Sent To E
Notes
2015-12-07 12:13:16 
 NOTE:
 THERE ARE TWO OPTIONS TO EXPEDITE THE PERMIT ISSUANCE:
 (1) PERMIT MAY BE ISSUED WITH A PROVISO. OWNER/BUILDER
 WILL ADDRESS COMMENTS AFTER THE PERMIT IS ISSUED. FEES
 WILL APPLY OR (2)OWNER/BUILDER TO ADDRESS COMMENTS
 BEFORE ISSUING THE PERMIT. OWNER/BUILDER TO NOTIFY THIS
 OFFICE WITH PREFERRED OPTION.
  
  
 RESIDENTIAL (R3) ADDITION FOURTH BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- NEW ENERGY CALCULATIONS SUBMITTED:
 A) THIS PROJECT WAS IS BEING REVIEWED UNDER THE 2010
 FBC. FORM R405-2014 SUBMITTED IS FOR THE 2014 CODE.
 NEED TO PROVIDE FORM FOR 2010 FBC. SEE PLANS AND SEC.
 103.2.1.1.2 OF 2010 FBC- ENERGY CONSERVATION.
  
 B) CLARIFY WHY SPECIFYING R-3.3 FOR CONCRETE BLOCK WALL
 IN ITEM #9(A) IF PLANS CALL FOR R-4.2?. SEC.
 103.2.1.1.2 OF 2010 FBC- ENERGY CONSERVATION.
  
 C) ITEM #15 IS TAKING THE CROSS VENTILATION CREDIT.
 SHOW HOW COMPLYING WITH THE CROSS VENTILATION CREDIT AS
 REQUIRED BY SEC. 405.6.4 OF 2010 FBC- ENERGY
 CONSERVATION.
  
 D) WALLS AND WINDOWS ORIENTATION SHOWN ON PAGE 3 OF 4
 DON'T MATCH PLANS. REVISE AS REQUIRED. SEC. 103.2.1.1.2
 OF 2010 FBC- ENERGY CONSERVATION.
  
 E) NEW FRENCH DOORS BY THE NEW SITTING AREA NEED TO BE
 CONSIDERED IN THE GLAZING AREA AS REQUIRED BY SEC.
 405.5.3 OF 2010 FBC- ENERGY CONSERVATION.
  
 F) WINDOWS OVERHANG DEPTH AND SEPARATION SHOWN ON PAGE
 3 OF 4 DON'T MATCH PLANS. SEC. 103.2.1.1.2 OF 2010 FBC-
 ENERGY CONSERVATION.
  
 FOR YOUR INFORMATION: LABEL FOR WINDOWS AND DOORS
 SHOWING THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE
 ENERGY CALCULATIONS ON ITEM #7 WILL BE REQUIRED WHEN
 THE ENERGY CALCULATIONS ARE NOT USING THE DEFAULT
 FACTOR FOR GLAZING.
  
 ****PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-08-10 Cont ID  
Sent By jgomez Date 2015-08-10 Time 18:46 Rev Time 0.00
Received By jgomez Date 2015-08-10 Time 18:44 Sent To  
Notes
2015-08-10 18:59:20RESIDENTIAL (R3) ADDITION THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE INSULATION R-VALUE SPECIFIED ON THE
 ENERGY CALCULATIONS FOR MASONRY WALLS ON ITEM #9. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 ***NOTE: COORDINATE PLANS AND ENERGY CALCULATIONS TO
 AVOID CONFLICTS AND MORE UNECESARY DELAYS.
  
 2- ENERGY CALCULATIONS SUBMITTED:
 A) CLARIFY IF CALCULATIONS ARE DONE FOR THE ENTIRE
 HOUSE OR JUST FOR THE ADDITION. INFORMATION SUBMITTED
 APPLIES TO ENTIRE HOUSE ON SOME AREAS, BUT ONLY FOR THE
 ADDITION IN OTHER AREAS. REVISE AS REQUIRED. PROVIDE
 EITHER INFORMATION FOR JUST THE ADDITION OR FOR ENTIRE
 HOUSE, BUT DON'T MIX BOTH. SEC. 103.2.2 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED).
  
 B) ENERGY CALCULATIONS ARE MISSING THE GLASS AREA OF
 THE SLIDING GLASS DOORS. SEC. 405.5.3 OF 2010
 FBC-ENERGY CONSERVATION. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 C) REVISE THE WINDOWS OVERHANG SEPARATION TO MATCH
 PLANS SUBMITTED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION. (REPEAT COMMENT. NOT ADDRESSED).
  
 D) NEW COMMENTS: A) WHY THE SPACES ON PAGE 2 OF 5
 DOESN'T SPECIFY THE KITCHEN IF SUPPOSEDLY THE
 CALCULATIONS ARE FOR ENTIRE HOUSE?. B) WHY THE SECOND
 FLOOR IS ON SLAB ON GRADE? SEE FLOORS ON PAGE 2 OF 5.
 SEC. 103.2.1.1.1 OF 2010 FBC-ENERGY CONSERVATION.
  
  
 NOTE: WINDOWS AND DOORS LABELS SHOWING U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS ON
 ITEM #7 WILL BE REQUIRED WHEN NOT DEFAULT FACTORS ARE
 USED IN THE CALCULATIONS.
  
 ****PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-02-26 Cont ID  
Sent By skennedy Date 2015-03-02 Time 14:21 Rev Time 0.00
Received By jgomez Date 2015-02-26 Time 09:19 Sent To E
Notes
2015-02-26 09:20:11RESIDENTIAL (R3) ADDITION SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE INSULATION R-VALUE SPECIFIED ON THE
 ENERGY CALCULATIONS FOR MASONRY WALLS ON ITEM #9. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. (REPEAT
 COMMENT. DRAWINGS OR ENERGY CALCULATIONS WERE NOT
 REVISED. NOTE: THERE WERE ENERGY CALCULATIONS SUBMITTED
 FOR A NEW SINGLE FAMILY RESIDENCE IN MARTIN COUNTY).
  
 2- ENERGY CALCULATIONS SUBMITTED ARE FOR A DIFFERENT
 PROJECT IN MARTIN COUNTY. THE FOLLOWING ITEMS FORM
 PREVIOUS CHECKLIST NEED TO BE ADDRESSED:
  
 A) CLARIFY IF CALCULATIONS ARE DONE FOR THE ENTIRE
 HOUSE OR JUST FOR THE ADDITION. INFORMATION SUBMITTED
 APPLIES TO ENTIRE HOUSE ON SOME AREAS, BUT ONLY FOR THE
 ADDITION IN OTHER AREAS. REVISE AS REQUIRED. PROVIDE
 EITHER INFORMATION FOR JUST THE ADDITION OR FOR ENTIRE
 HOUSE, BUT DON'T MIX BOTH. SEC. 103.2.2 OF 2010
 FBC-RESIDENTIAL.
 ***NOTE: PROVIDE ONLY THE CALCULATIONS THAT PERTAIN TO
 FORM 405-10 TO AVOID CONFUSION OR CONFLICTS.
  
 B) ENERGY CALCULATIONS ARE MISSING THE GLASS AREA OF
 THE SLIDING GLASS DOORS. SEC. 405.5.3 OF 2010
 FBC-ENERGY CONSERVATION.
  
 C) REVISE THE WINDOWS OVERHANG SEPARATION TO MATCH
 PLANS SUBMITTED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-RESIDENTIAL.
  
 ****PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-15 Cont ID  
Sent By jgomez Date 2014-12-15 Time 12:55 Rev Time 0.00
Received By jgomez Date 2014-12-15 Time 12:33 Sent To  
Notes
2014-12-15 14:04:35RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY BUILDING (2300 N.
 JOG RD.) TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK
 COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES
 ARE DUE. REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION WAS UPDATED TO $51,955. THE VALUATION TO
 INCLUDE ALL LABOR, MATERIALS. CONTRACTOR'S OVERHEAD AND
 PROFIT AND ALL DESIGN PROFESSIONAL FEES AS REQUIRED BY
 SEC. 109.3 CITY AMENDMENTS TO FBC.
  
 3- IT LOOKS LIKE THE THE EXISTING EXTERIOR WALL TO BE
 REMOVED TO ALLOW FOR THE NEW SITTING AREA IS A LOAD
 BEARING WALL. THERE ARE NO DETAILS OR SPECIFICATIONS ON
 PLANS SHOWING HOW THE LOADS ARE SUPPORTED. PROVIDE
 INFORMATION ADDRESSING THIS ISSUE. SEC. R301 OF 2010
 FBC-RESIDENTIAL.
  
 4- SHEET 4.1:
 A) ROOF FRAMING PLAN: 4" LONG TAPCONS MAY BE TOO SHORT
 TO HOLD (2)2 X 6 WOOD LEDGER. ENGINEER TO PROVIDE
 CALCULATIONS SHOWING THAT SPECIFIED TAPCON LENGTH WITH
 ONLY 1" EMBEDMENT INTO EXISTING WALL IS ADEQUATE TO
 SUPPORT THE LOADS. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 B) SLIDING GLASS DOORS AS SHOWN ON PLANS. PRODUCT
 APPROVAL SUBMITTED WAS FOR FIBERGLASS DOUBLE SWING
 DOORS.
  
 6- COMPONENTS AND CLADDING PRESSURE ZONES ON SHEET 5.1:
 ENGINEER TO REVISE THE CORNER DISTANCE "A". ACCORDING
 TO FOOTNOTE ON FIGURE R301.2(7) OF 2010 FBC-RESIDENTIAL
 THE DIMENSION FOR "A" IS 4 FEET IN ALL CASES, NOT 3
 FEET. REVISE AS REQUIRED.
  
 7- SHEET 6.1:
 A) TYPICAL WALL SECTION: SIZE OF FOOTING DOESN'T MATCH
 SIZE SPECIFIED ON THE FOUNDATION PLAN. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) CLARIFY ATTACHMENT OF (2)2 X 6 WOOD LEDGER TO
 EXISTING WALL. IS THE WOOD LEDGER GOING TO BE ATTACHED
 TO A CONCRETE BEAM OR TO A WOOD FRAMED WALL. THERE IS A
 NOTE ON SAME DRAWING SAYING THAT SECOND FLOOR WALL IS
 WOOD FRAMED. CLARIFY/REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 C) STUCCO SHALL BE NOT LESS THAN 3 COATS AS REQUIRED BY
 SEC. R702.2.2 OF 2010 FBC-RESIDENTIAL. REVISE AS
 REQUIRED.
 ***NOTE: THIS APPLIES ALSO TO TYPICAL COLUMN SECTION ON
 SAME DRAWING.
  
 D) STUCCO THICKNESS IS 7/8" MIN. AS REQUIRED BY TABLE
 R702.1(1) OF 2010 FBC-RESIDENTIAL. REVISE AS REQUIRED.
 ***NOTE: THIS APPLIES ALSO TO TYPICAL COLUMN SECTION ON
 SAME DRAWING.
  
 E) CLEARLY IDENTIFY THE 6" TERMITE INSPECTION CLEARANCE
 REQUIRED BY SEC. R704 OF 2010 FBC-RESIDENTIAL.
  
 F) SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R302.11 OF
 2010 FBC-RESIDENTIAL.
  
 8- SPECIFY CARBON MONOXIDE ALARMS FOR ALL SLEEPING
 ROOMS AS REQUIRED BY SEC. R315.1 OF 2010
 FBC-RESIDENTIAL.
  
 9- PROVIDE MANUFACTURER SPECS FOR WINDOWS AND DOORS
 U-FACTOR AND SHGC FACTOR SHOWING VALUES SPECIFIED ON
 ITEM #7 OF THE ENERGY CALCULATIONS SUBMITTED. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 10- PROVIDE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE INSULATION R-VALUE SPECIFIED ON THE
 ENERGY CALCULATIONS FOR MASONRY WALLS ON ITEM #9. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 11- ENERGY CALCULATIONS SUBMITTED:
 A) CLARIFY IF CALCULATIONS ARE DONE FOR THE ENTIRE
 HOUSE OR JUST FOR THE ADDITION. INFORMATION SUBMITTED
 APPLIES TO ENTIRE HOUSE ON SOME AREAS, BUT ONLY FOR THE
 ADDITION IN OTHER AREAS. REVISE AS REQUIRED. PROVIDE
 EITHER INFORMATION FOR JUST THE ADDITION OR FOR ENTIRE
 HOUSE, BUT DON'T MIX BOTH. SEC. 103.2.2 OF 2010
 FBC-RESIDENTIAL.
 ***NOTE: PROVIDE ONLY THE CALCULATIONS THAT PERTAIN TO
 FORM 405-10 TO AVOID CONFUSIN OR CONFLICTS.
  
 B) ENERGY CALCULATIONS ARE MISSING THE GLASS AREA OF
 THE SLIDING GLASS DOORS. SEC. 405.5.3 OF 2010
 FBC-ENERGY CONSERVATION.
  
 C) REVISE THE WINDOWS OVERHANG SEPARATION TO MATCH
 PLANS SUBMITTED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-RESIDENTIAL.
  
 ****PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE AND REPLACE ANY REVISED SHEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-05-23 Cont ID  
Sent By vperez Date 2016-05-23 Time 08:45 Rev Time 0.00
Received By vperez Date 2016-05-23 Time 08:45 Sent To  
Notes
2016-05-23 09:03:49INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVISO: PLEASE HAVE DESIGNER OF RECORD SIGN AND
 SEAL ELECTRICAL SHEET, ONLY MAIN SHEET WAS SIGNED.
 2. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-02 Cont ID  
Sent By skennedy Date 2015-03-02 Time 13:59 Rev Time 0.00
Received By skennedy Date 2015-03-02 Time 13:59 Sent To  
Notes
2015-02-26 09:29:15NEW DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-16 Cont ID  
Sent By skennedy Date 2014-12-16 Time 11:23 Rev Time 0.00
Received By skennedy Date 2014-12-16 Time 11:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-05-23 Cont ID  
Sent By vperez Date 2016-05-23 Time 08:45 Rev Time 0.00
Received By vperez Date 2016-05-23 Time 08:45 Sent To  
Notes
2015-11-18 14:07:04RESUB ROUTED TO JGOMEZ - COULD NOT LOCATE ORIGINAL
 SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-08-11 Cont ID  
Sent By jgomez Date 2015-08-11 Time 08:03 Rev Time 0.00
Received By jgomez Date 2015-07-27 Time 14:25 Sent To  
Notes
2015-07-27 14:25:41JGOMEZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-02 Cont ID  
Sent By jgomez Date 2015-03-02 Time 14:21 Rev Time 0.00
Received By skennedy Date 2015-01-28 Time 16:01 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-16 Cont ID  
Sent By skennedy Date 2014-12-16 Time 11:23 Rev Time 0.00
Received By skennedy Date 2014-11-18 Time 07:05 Sent To  
Notes
2014-11-19 07:17:45INCOMING SENT TO R-07.JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-02-26 Cont ID  
Sent By jgomez Date 2015-02-26 Time 11:08 Rev Time 0.00
Received By jgomez Date 2015-02-26 Time 11:08 Sent To  
Notes
2015-02-26 11:11:08MU-2015-001973. $236.59 PAID. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-12-15 Cont ID  
Sent By jgomez Date 2014-12-15 Time 12:52 Rev Time 0.00
Received By jgomez Date 2014-12-15 Time 12:47 Sent To  
Notes
2014-12-15 12:54:261- BRING PLANS TO PALM BEACH COUNTY BUILDING (2300 N.
 JOG RD.) TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK
 COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES
 ARE DUE. REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2015-12-07 Cont ID  
Sent By jgomez Date 2015-12-07 Time 16:45 Rev Time 0.00
Received By jgomez Date 2015-12-07 Time 16:45 Sent To  
Notes
2015-12-07 16:46:15 
  
 NOTE:
 THERE ARE TWO OPTIONS TO EXPEDITE THE PERMIT ISSUANCE:
 (1) PERMIT MAY BE ISSUED WITH A PROVISO. OWNER/BUILDER
 WILL ADDRESS COMMENTS AFTER THE PERMIT IS ISSUED. FEES
 WILL APPLY OR (2)OWNER/BUILDER TO ADDRESS COMMENTS
 BEFORE ISSUING THE PERMIT. OWNER/BUILDER TO NOTIFY THIS
 OFFICE WITH PREFERRED OPTION.
  
  
 RESIDENTIAL (R3) ADDITION FOURTH MECHANICAL REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE A/C PLAN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS TO FBC. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 2- A/C PLAN TO LIST THE EQUIPMENT SPECIFIED ON THE
 EQUIPMENT SIZING CALCULATIONS AND ENERGY CALCULATIONS
 SUBMITTED. SEC. 107.3.5.3(10) CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER TO EXPEDITE THE
 REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-08-11 Cont ID  
Sent By jgomez Date 2015-08-11 Time 07:46 Rev Time 0.00
Received By jgomez Date 2015-08-11 Time 07:40 Sent To  
Notes
2015-08-11 07:47:16RESIDENTIAL (R3) ADDITION THIRD MECHANICAL REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE A/C PLAN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- EQUIPMENT SIZING CALCULATIONS: ENGINEER LISTED ON
 TOP OF ENTIRE HOUSE CALCULATIONS TO PROVIDE SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 3- INFORMATION SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS DON'T MATCH INFORMATION SHOWN ON THE
 ENERGY CALCULATIONS AND ON A/C PLAN. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-02-26 Cont ID  
Sent By jgomez Date 2015-02-26 Time 17:48 Rev Time 0.00
Received By jgomez Date 2015-02-26 Time 17:47 Sent To  
Notes
2015-02-26 17:57:50RESIDENTIAL (R3) ADDITION SECOND MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE A/C PLAN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS TO FBC. (REPEAT COMMENT).
  
 2- EQUIPMENT SIZING CALCULATIONS: ENGINEER LISTED ON
 TOP OF ENTIRE HOUSE CALCULATIONS TO PROVIDE SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 3- INFORMATION SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS DON'T MATCH INFORMATION SHOWN ON THE
 ENERGY CALCULATIONS AND ON A/C PLAN. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-15 Cont ID  
Sent By jgomez Date 2014-12-15 Time 18:05 Rev Time 0.00
Received By jgomez Date 2014-12-15 Time 18:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-02-26 Cont ID  
Sent By jgomez Date 2015-02-26 Time 18:12 Rev Time 0.00
Received By jgomez Date 2015-02-26 Time 18:12 Sent To  
Notes
2015-02-26 09:29:44NEW DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-11-26 Cont ID  
Sent By tklarge Date 2014-11-26 Time 11:26 Rev Time 0.00
Received By tklarge Date 2014-11-26 Time 11:11 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2015-08-10 Cont ID  
Sent By jgomez Date 2015-08-10 Time 19:29 Rev Time 0.00
Received By jgomez Date 2015-08-10 Time 19:29 Sent To  
Notes
2015-08-10 19:30:50SHINGLES FLORIDA PRODUCT APPROVAL FL1956-R9.

Review Stop Z ZONING
Rev No 2 Status P Date 2014-12-15 Cont ID  
Sent By sgraham Date 2014-12-15 Time   Rev Time 0.00
Received By sgraham Date 2014-12-15 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-11 Cont ID  
Sent By sgraham Date 2014-12-11 Time 15:14 Rev Time 0.00
Received By sgraham Date 2014-12-11 Time 15:14 Sent To  
Notes
2014-12-11 15:15:0912/11/14 ZONING FAILED
  
 1. NEW ADDITION MUST BE 3' FEET FROM THE PROPERTY LINE
2014-12-01 13:57:5812/1/14