Plan Review Details - Permit 14110682
Plan Review Stops For Permit 14110682
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-11-30 Cont ID  
Sent By jgomez Date 2015-11-30 Time 17:22 Rev Time 0.00
Received By jgomez Date 2015-11-30 Time 17:05 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-11-12 Cont ID  
Sent By jgomez Date 2015-11-12 Time 15:31 Rev Time 0.00
Received By jgomez Date 2015-11-12 Time 15:31 Sent To E
Notes
2015-11-12 15:31:24BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- SIZE OF FOOTING SPECIFIED ON REVISED SHEET A1
 DOESN'T MATCH SIZE SHOWN ON FOOTING SCHEDULE ON SHEET
 A4. REVISE AS REQUIRED.
  
 2- SHUTTERS INSTALLATION SCHEDULE: REVISE THE ANCHOR
 SPACING FOR THE CALK-IN ANCHOR SPECIFIED. NEED TO USE
 THE MASONRY COLUMN NOT THE CONCRETE COLUMN. SEE TABLES
 ON SHEET 5 AND 6 OF 8 OF THE SHUTTERS PRODUCT APPROVAL
 SUBMITTED AND REVISE AS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-08-17 Cont ID  
Sent By jgomez Date 2015-08-17 Time 14:03 Rev Time 0.00
Received By jgomez Date 2015-08-17 Time 14:03 Sent To E
Notes
2015-08-17 14:04:34NOTE: BUILDING REVIEW MAY BE APPROVED WITH PROVISO.
 COMMENTS BELOW MAY BE ADDRESSED AFTER PERMIT IS ISSUED.
 FEES MAY APPLY. CONTRACTOR'S RESPONSE IS REQUIRED:
 REQUESTING PROVISO OR RE-SUBMITTING INFORMATION BELOW.
  
 1- SIZE OF FOOTING SPECIFIED ON PLANS AND SIZE
 RECOMMENDED ON THE GEOTECHNICAL REPORT DON'T MATCH.
 REVISE AS REQUIRED TO MATCH OR ARCHITECT TO PROVIDE
 LETTER ACKNOWLEDGING THAT HE READ THE GEOTHECHNICAL
 REPORT RECOMMENDATION AND THE FOOTING SIZE HE SPECIFIED
 IS ADEQUATE. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- TYPICAL WALL SECTION ON SHEET A3: COORDINATE SIZE OF
 FOOTING TO COMPLY WITH THE CLEARANCE FOR TERMITE
 INSPECTION REQUIRED BY SEC. R704 AND MINIMUM FOOTING
 DEPTH REQUIRED BY SEC. R403.1.4. A 16" DEEP FOOTING
 DOESN'T PROVIDE 6" CLEARANCE AND 12" DEPTH BELOW GRADE.
 REVISE TYPICAL WALL SECTION, FOUNDATION PLAN AND
 FOOTING SCHEDULE AS REQUIRED AND COORDINATE WITH ITEM
 #2 ABOVE.
  
 3- SPECIFY THE SIZE OF THE GARAGE DOOR STRUCTURAL BUCK.
 SEC. R301.1.
  
 4- REVISE THE SHUTTERS INSTALLATION SCHEDULE: SHUTTER
 MOUNTING CONNECTION TYPE IS INCORRECT. SUBSTRATE IS
 CONCRETE BLOCK NOT POURED CONCRETE. CLARIFY SHUTTER
 MOUNTING CONNECTION AND SPECIFIC ANCHOR TYPE.
  
 5- NEW SHEET A4: THE LEFT HAND SIDE OF THE STRUCTURAL
 NOTES GOT CUT OFF. PROVIDE COMPLETE DRAWING.
  
 6- REVISE THE ENERGY CALCULATIONS: CALCULATIONS NEED TO
 BE DONE ON THE ACTUAL ORIENTATION OF THE BUILDING.
 BUILDING IS FACING A TRUE NORTH. THERE ARE NOT NORTH
 EAST ORIENTATION, ETC. SEC. 103.2.1.1.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-12 Cont ID  
Sent By jgomez Date 2014-12-12 Time 14:54 Rev Time 0.00
Received By jgomez Date 2014-12-12 Time 14:39 Sent To  
Notes
2014-12-12 14:54:37NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG. RD.) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE SOIL TEST REPORT (2 COPIES WITH ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE). SEC. R401.4 OF 2010
 FBC-RESIDENTIAL.
  
 3- SHEET A1:
 A) PROVIDE INFORMATION FOR THE DROPPED FOOTING SIZE AND
 REINFORCEMENT BETWEEN GARAGE AND THE REST OF THE HOUSE.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 B) WINDOW ON BEDROOMS #2 AND #3 DON'T COMPLY WITH
 EGRESS REQUIREMENTS. SEC. R310.1.2 OF 2010
 FBC-RESIDENTIAL. PROVIDE MANUFACTURER'S SPECIFICATIONS
 SHOWING COMPLIANCE WITH THE REQUIRED CLEAR HEIGHT
 OPENING OR REVISE SIZE OF WINDOW TO COMPLY.
  
 C) CLARIFY THE WIDTH SIZE SPECIFIED ON THE WINDOW
 SCHEDULE FOR ALL SH 25 WINDOWS. WIDTH DIMENSION OF
 2'-2" DOESN'T SEEM TO BE CORRECT. REVISE/CLARIFY AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 D) SPECIFY ATTIC ACCESS. SEC. R807 OF 2010
 FBC-RESIDENTIAL.
  
 4- PROVIDE CARBON MONOXIDE ALARMS AS REQUIRED BY SEC.
 R315 OF 2010 FBC-RESIDENTIAL.
  
 5-TYPICAL WALL SECTION ON SHEET A3:
 A) SHOW COMPLIANCE WITH THE CLEARANCE REQUIRED FOR
 TERMITE INSPECTION AS REQUIRED BY SEC. R704 OF 2010
 FBC-RESIDENTIAL.
  
 B) SPECIFY THE FOOTING MIN. DEPTH AS REQUIRED BY SEC.
 R403.1.4 OF 2010 FBC-RESIDENTIAL.
  
 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION WAS UPGRADED TO $150,000. THE PERMIT FEE
 BALANCE IS $3142.50. VALUATION TO INCLUDE ALL LABOR,
 MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND ALL
 DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS TO FBC.
  
 7- PROVIDE GARAGE STRUCTURAL BUCK DETAIL AND
 SPECIFICATIONS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 8- PROVIDE WINDOW AND DOOR MANUFACTURER'S SPECS SHOWING
 THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS ON ITEM #7. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) PRECAST LINTELS SPECIFIED ON PLANS.
  
 B) ENTRY WOOD DOOR AS SPECIFIED ON PLANS AND ENERGY
 CALCULATIONS (OTHERWISE REVISE PLANS AND ENERGY
 CALCULATIONS).
  
 C) OVERHEAD GARAGE DOOR SIZE AS SPECIFIED ON PLANS.
 DRAWINGS SUBMITTED ARE FOR 9'-0" MAX. DOOR WIDTH. NEED
 DRAWINGS FOR 10'-0" WIDE DOORS.
  
 D) INSULATED FIBERGLASS DOOR. NEED COMPLETE DRAWINGS.
 DRAWINGS SUBMITTED ARE CUT IN HALF. PRINT DRAWINGS IN
 FORMAT THAT WILL PRINT ENTIRE PAGE.
  
 10- DESIGN PROFESSIONAL OF RECORD TO REVIEW AND APPROVE
 ABOVE PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS
 TO FBC.
  
 11- PROVIDE STORM SHUTTERS COMPLETE INSTALLATION
 SCHEDULE. USE CITY SAMPLE OR PROVIDE COMPLETE REQUIRED
 INFORMATION UNDER A DIFFERENT FORMAT. SEC. R301.1 OF
 2010 FBC-RESIDENTIAL.
  
 ****PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE AND REPLACE ANY REVISED DRAWING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-11-15 Cont ID  
Sent By skennedy Date 2015-11-15 Time 11:11 Rev Time 0.00
Received By skennedy Date 2015-11-15 Time 11:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-18 Cont ID  
Sent By skennedy Date 2015-08-18 Time 15:59 Rev Time 0.00
Received By skennedy Date 2015-08-18 Time 15:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-16 Cont ID  
Sent By skennedy Date 2014-12-16 Time 10:14 Rev Time 0.00
Received By skennedy Date 2014-12-16 Time 10:14 Sent To  
Notes
2014-12-16 10:35:571ST REVIEW: FBC 2010
  
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
  
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
  
 NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET. SEE
 FRONT DOOR ALONG THE WALL TO THE LEFT IN LIVING ROOM.
  
 NEC 210.52(C)(3)-(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP SPACE WITH A LONG DIMENSION OF
 600 MM (24 IN.) OR GREATER
 AND A SHORT DIMENSION OF 300 MM (12 IN.) OR GREATER. A
 PENINSULAR COUNTERTOP IS MEASURED FROM THE CONNECTING
 EDGE.
  
 NEC 210.52(G) BASEMENTS AND GARAGES. FOR A ONE-FAMILY
 DWELLING THE FOLLOWING PROVISIONS SHALL APPLY: (1) AT
 LEAST ONE RECEPTACLE OUTLET, IN ADDITION TO THOSE FOR
 SPECIFIC EQUIPMENT, SHALL BE INSTALLED IN EACH
 BASEMENT, IN EACH ATTACHED GARAGE, AND IN EACH DETACHED
 GARAGE WITH ELECTRIC POWER.
  
 NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTED
 REQUIRED FOR GARAGE RECEPTACLE.
  
 NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-11-30 Cont ID  
Sent By jgomez Date 2015-11-30 Time 17:05 Rev Time 0.00
Received By jgomez Date 2015-11-20 Time 11:07 Sent To  
Notes
2015-11-23 11:07:40RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-11-15 Cont ID  
Sent By skennedy Date 2015-11-15 Time 11:11 Rev Time 0.00
Received By skennedy Date 2015-11-03 Time 16:33 Sent To  
Notes
2015-11-03 16:33:59R20

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-18 Cont ID  
Sent By skennedy Date 2015-08-18 Time 16:00 Rev Time 0.00
Received By skennedy Date 2015-07-27 Time 19:19 Sent To  
Notes
2015-08-12 08:03:55R20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-16 Cont ID  
Sent By skennedy Date 2014-12-16 Time 10:36 Rev Time 0.00
Received By skennedy Date 2014-11-18 Time 07:23 Sent To  
Notes
2014-11-19 07:23:41INCOMING SENT TO R-08. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-08-17 Cont ID  
Sent By jgomez Date 2015-08-17 Time 14:32 Rev Time 0.00
Received By jgomez Date 2015-08-17 Time 14:32 Sent To  
Notes
2015-08-17 14:33:18NO FEES. MU-2015-16564. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-12-12 Cont ID  
Sent By jgomez Date 2014-12-12 Time 15:02 Rev Time 0.00
Received By jgomez Date 2014-12-12 Time 15:02 Sent To  
Notes
2014-12-12 15:07:201- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG. RD.)
 TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-11-12 Cont ID  
Sent By jgomez Date 2015-11-12 Time 16:58 Rev Time 0.00
Received By jgomez Date 2015-11-12 Time 16:57 Sent To  
Notes
2015-11-12 17:05:50 
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-08-18 Cont ID  
Sent By jgomez Date 2015-08-17 Time 18:28 Rev Time 0.00
Received By jgomez Date 2015-08-17 Time 18:28 Sent To  
Notes
2015-08-17 18:39:23NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED DON'T
 IDENTIFY THE PROGRAM THAT WAS ISSUED TO PERFORM THE
 CALCULATIONS. NEED TO USE APPROVED SOFTWARE. SEE SEC.
 403.6 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- EQUIPMENT SIZING CALCULATIONS NEED TO BE DONE BASED
 ON THE BUILDING LOADS FOR THE ACTUAL DIRECTIONAL
 ORIENTATION O THE BUILDING. CALCULATIONS SUBMITTED
 DON'T MATCH ACTUAL BUILDING ORIENTATION. SEE SEC. 403.6
 OF 2010 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-15 Cont ID  
Sent By jgomez Date 2014-12-15 Time 07:20 Rev Time 0.00
Received By jgomez Date 2014-12-15 Time 07:20 Sent To  
Notes
2014-12-15 07:20:34NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- A/C PLANS TO HAVE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS. ONLY
 THE EQUIPMENT SUMMARY WAS PROVIDED. SEC. 403.6 OF 2010
 FBC-ENERGY CONSERVATION.
 ***NOTE: MAKE SURE CALCUALTIONS ARE DONE BASED ON THE
 HOUSE ACTUAL BUILDING ORIENTATION AS REQUIRED BY SEC.
 406.6.
  
 3- CALCULATIONS TO PROVIDE THE MANUFACTURER AND MODEL
 NUMBER SHOWING THE SENSIBLE AND TOTAL COOLING CAPACITY
 AS REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 4- HEATING INFORMATION SHOWN ON THE EQUIPMENT SIZING
 SIZING CALCULATIONS DOESN'T MATCH INFORMATION SHOWN ON
 THE ENERGY CALCULATIONS. REVISE AS REQUIRED TO MATCH.
 SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-12-02 Cont ID  
Sent By gjohnson Date 2015-12-02 Time 13:00 Rev Time 0.00
Received By gjohnson Date 2015-12-02 Time 13:00 Sent To  
Notes
2015-11-30 17:43:48NEW DRAWING SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-11-09 Cont ID  
Sent By gjohnson Date 2015-11-09 Time 17:31 Rev Time 0.00
Received By gjohnson Date 2015-11-09 Time 17:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-08-03 Cont ID  
Sent By tklarge Date 2015-08-03 Time 06:11 Rev Time 0.00
Received By tklarge Date 2015-08-03 Time 05:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-12-04 Cont ID  
Sent By dkittred Date 2014-12-04 Time 09:54 Rev Time 0.00
Received By tklarge Date 2014-11-26 Time 10:36 Sent To  
Notes
2014-12-01 13:56:1412/1/14
2014-11-26 10:50:28***PROVISO***
 SUBMIT REVISED SANITARY RISER FOR REVIEW PRIOR TO ROUGH
 PLUMBING INSPECTION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2015-08-17 Cont ID  
Sent By jgomez Date 2015-08-17 Time 17:49 Rev Time 0.00
Received By jgomez Date 2015-08-17 Time 17:49 Sent To  
Notes
2015-08-17 17:49:46SHINGLES FLORIDA PRODUCT APPROVAL FL1956-R9.

Review Stop Z ZONING
Rev No 3 Status P Date 2015-11-05 Cont ID  
Sent By dkittred Date 2015-11-05 Time 10:16 Rev Time 0.00
Received By dkittred Date 2015-11-05 Time 08:52 Sent To  
Notes
2015-11-05 10:16:3611/5/15 - RESTAMPED REVISED SHEETS. DK

Review Stop Z ZONING
Rev No 2 Status P Date 2015-07-29 Cont ID  
Sent By dkittred Date 2015-07-29 Time 12:46 Rev Time 0.00
Received By dkittred Date 2015-07-29 Time 11:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-01 Cont ID  
Sent By dkittred Date 2014-12-01 Time 15:08 Rev Time 0.00
Received By dkittred Date 2014-12-01 Time 14:21 Sent To  
Notes
2014-12-01 15:07:16PLANNING AND ZONING COMMENTS: ***FAILED***
  
 12/1/14
  
 ITEMS TO BE ADDRESSED FOR PERMIT:
  
 1. A SEPARATE LANDSCAPE PERMIT IN CONFORMANCE WITH
 ARTICLE XIV SHALL BE SUBMITTED. (NOTE: ZLDR SEC.
 94-442(B)(2)A. - FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHADE, FLOWERING, OR FRUIT TREE SHALL BE
 PLANTED FOR EACH 1,200 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE
 FEET OF OPEN SPACE OR PORTION THEREOF.)
  
  
 GENERAL COMMENTS:
  
 1. NOTATION ADDED TO SITE PLAN THAT A/C MUST BE A
 MINIMUM OF 2.67' FROM THE PROPERTY LINE BASED ON A
 MAXIMUM 4' ENCROACHMENT OF MECHANICAL INTO A REQUIRED
 SETBACK.
  
 2. A SEPARATE PERMIT IS REQUIRED FOR THE DRIVEWAY.
 PLEASE KEEP IN MIND THAT WITHIN THE FRONTYARD SETBACK,
 A MINIMUM 1,000 SQ. FT. OR 75%, WHICHEVER IS LESS, OF
 GREEN SPACES [(ZLDR SEC. 94-482(A)] IS REQUIRED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  