Plan Review Details - Permit 14110665
Plan Review Stops For Permit 14110665
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-04-22 Cont ID  
Sent By skennedy Date 2015-04-22 Time 15:18 Rev Time 0.00
Received By skennedy Date 2015-04-22 Time 15:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-08 Cont ID  
Sent By skennedy Date 2015-04-08 Time 15:22 Rev Time 0.00
Received By skennedy Date 2015-04-08 Time 15:22 Sent To Z
Notes
2015-04-08 16:11:421ST REVIEW: FBC 2010
  
 PROVIDE ENGINEER REVIEWED SHOP DRAWING FROM SIGN
 MANUFACTURER.
  
 VALUATION APPEARS LOW, FBC 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-29 Cont ID  
Sent By skennedy Date 2014-11-29 Time 15:08 Rev Time 0.00
Received By skennedy Date 2014-11-29 Time 15:08 Sent To Z
Notes
2014-11-29 15:11:591ST REVIEW: FBC 2010
  
 PROVIDE CONNECTION INFORMATION PER FBC 2204, FOR THE
 SIGN MEMBERS, (SQUARE TUBES, METAL FASTENERS,
 FRABRICATED FACE )TO INDICATE HOW IT IS HELD TOGETHER.
 IS IT WELDED, BOLTED?
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-23 Cont ID  
Sent By skennedy Date 2015-03-23 Time 11:21 Rev Time 0.00
Received By dhayes Date 2015-03-23 Time 11:21 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-11-26 Cont ID  
Sent By dhayes Date 2014-11-26 Time 16:26 Rev Time 0.00
Received By dhayes Date 2014-11-26 Time 11:21 Sent To  
Notes
2014-11-26 16:27:4011/26/2014
 PROJECT: AUDI SIGNAGE
 PERMIT#: 14110665
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE PLANS IN ACCORDANCE WITH THE FOLLOWING COMMENTS:
  
 1) NEC 600.5
 EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY
 A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES NO OTHER LOAD.
  
 2) NEC 600.3 AND 110.3 LISTING.
 ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING ?
 FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND
 INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS
 OTHERWISE APPROVED BY SPECIAL PERMISSION.
  
 3) NEC 600.6(A)(1) LOCATION.
 DISCONNECTS. EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR
 FEEDER CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR
 OUT-LINE LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN
 EXTERNALLY OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL
 OPEN ALL UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN
 OR OUTLINE LIGHTING SYSTEM THAT IT CONTROLS.
  
 4) FBC-E 505.2.4
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS.
  
 5) NEC 600.4 MARKINGS.
 (A) SIGNS AND OUTLINE LIGHTING SYSTEMS. SIGNS AND
 OUTLINE LIGHTING SYSTEMS SHALL BE MARKED WITH THE
 MANUFACTURER?S NAME, TRADEMARK, OR OTHER MEANS OF
 IDENTIFICATION; AND INPUT VOLTAGE AND CURRENT RATING.
 (B) SIGNS WITH LAMPHOLDERS FOR INCANDESCENT LAMPS.
 SIGNS AND OUTLINE LIGHTING SYSTEMS WITH LAMPHOLDERS FOR
 INCANDESCENT LAMPS SHALL BE MARKED TO INDICATE THE
 MAXIMUM ALLOWABLE LAMP WATTAGE PER LAMPHOLDER. THE
 MARKINGS SHALL BE PERMANENTLY INSTALLED, IN LETTERS AT
 LEAST 6 MM (1?4 IN.) HIGH, AND SHALL BE LOCATED WHERE
 VISIBLE DURING RELAMPING.
 (C) SECTION SIGNS. SECTION SIGNS SHALL BE MARKED TO
 INDICATE THAT FIELD-WIRING AND INSTALLATION
 INSTRUCTIONS ARE REQUIRED. THE ELECTRICAL CONNECTIONS
 TO SAME ARE UNDER A DIFFERENT PERMIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-04-22 Cont ID  
Sent By skennedy Date 2015-04-22 Time 15:18 Rev Time 0.00
Received By skennedy Date 2015-04-17 Time   Sent To  
Notes
2015-04-17 18:24:52SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-10 Cont ID  
Sent By eschneid Date 2015-04-10 Time 17:30 Rev Time 0.00
Received By eschneid Date 2015-03-20 Time 18:25 Sent To  
Notes
2015-03-20 18:26:18RE-SUBMITTAL SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-02 Cont ID  
Sent By eschneid Date 2014-12-02 Time 16:26 Rev Time 0.00
Received By eschneid Date 2014-11-19 Time 07:01 Sent To  
Notes
2014-11-19 07:01:51INCOMING SENT TO ZONING. JW

Review Stop Z ZONING
Rev No 2 Status P Date 2015-04-10 Cont ID  
Sent By eschneid Date 2015-04-10 Time 17:25 Rev Time 0.75
Received By eschneid Date 2015-04-10 Time 17:25 Sent To  
Notes
2015-04-10 17:28:12PASSED
  
 1) SIGN 5 - HIGH FREESTANDING SIGN
  
 ALLOWED: 477.63 SQ. FT.
 PROPOSED: 395.8 SQ. FT.
  
 2) SIGN 6 -HIGH FREESTANDING SIGN
  
 TOTAL HS ALLOWED: 477.63 SQ. FT.
 SIGN 5: 395.8 SQ. FT.
 PROPOSED: 36.6 SQ. FT.
 TOTAL HS SIGNAGE: 432.4 SQ. FT.
  
 3) SIGN 7 - PARKING AREA IDENTIFICATION SIGN
  
 ALLOWED: 4 SQ. FT. PER FACE
 PROPOSED: 4 SQ. FT. PER FACE
  
 4) SIGNS 8 AND 11 - PARKING AREA INSTRUCTIONAL SIGN
  
 PROPOSED: 4 SQ. FT. PER FACE
  
 5) SIGN 9 - LOW FREESTANDING SIGN
  
 ALLOWED: 529.69 SQ. FT.
 PROPOSED: 22 SQ. FT.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-02 Cont ID  
Sent By eschneid Date 2014-12-02 Time 16:21 Rev Time 0.75
Received By eschneid Date 2014-12-02 Time 16:21 Sent To  
Notes
2014-12-02 16:26:31FAILED
  
 1) THE SUBMITTED PLAN IS NOT THE APPROVED SITE PLAN.
  
 2) THE VISIBILITY TRIANGLE SHALL BE SHOWN ON THE SITE
 PLAN.
  
 3) THE SETBACK DIMENSIONS FROM THE RIGHT-OF-WAY LINE TO
 THE PROPERTY LINE SHALL BE SHOWN ON THE SITE PLAN.
  
 4) SIGN 5 - HIGH FREESTANDING SIGN
  
 ALLOWED: 477.63 SQ. FT.
 PROPOSED: 600 SQ. FT.
  
 A. THE SIGN EXCEEDS THE PERMISSIBLE SQUARE FOOTAGE FOR
 A HIGH FREESTANDING SIGN ON THE OKEECHOBEE BOULEVARD
 FRONTAGE.
  
 B. THIS SIGN IS NOT SHOWN IN THE APPROVED SITE PLAN
 SIGN LOCATION ON. THE LOCATION SHOWN ON THE PERMIT SITE
 PLAN CONFLICTS WITH REQUIRED, APPROVED LANDSCAPE.
  
 5) SIGN 6 -HIGH FREESTANDING SIGN
  
 ALLOWED: SIGN 5 EXCEEDS THE PERMISSIBLE SQUARE FOOTAGE
 FOR THE OKEECHOBEE BOULEVARD FRONTAGE SO NO SQUARE
 FOOTAGE AVAILABLE.
 PROPOSED: 36.6 SQ. FT.
  
 A. THE SIGN EXCEEDS THE PERMISSIBLE SQUARE FOOTAGE FOR
 A HIGH FREESTANDING SIGN THE OKEECHOBEE BOULEVARD
 FRONTAGE.
  
 B. THIS SIGN IS NOT SHOWN IN THE APPROVED SIGN
 LOCATION. THE LOCATION SHOWN ON THE PERMIT SITE PLAN
 CONFLICTS WITH REQUIRED, APPROVED LANDSCAPE.
  
 6) SIGN 7 - PARKING AREA IDENTIFICATION SIGN
  
 ALLOWED: 4 SQ. FT. PER FACE
 PROPOSED: 11 SQ. FT. PER FACE
  
 A. THE SIGN EXCEEDS THE PERMISSIBLE SQUARE FOOTAGE FOR
 A PARKING AREA IDENTIFICATION SIGN.
  
 B. THIS SIGN IS SHOWN IN A SIGN LOCATION ON SITE PLAN;
 HOWEVER, IT MAY BE ADVISABLE TO INCORPORATE IT ONTO
 SIGN 5.
  
 7) SIGN 8 - PARKING AREA INSTRUCTIONAL SIGN
  
 PROPOSED: 4 SQ. FT. PER FACE
  
 A. SIGN COMPLIES WITH ZONING CODE
  
 8) SIGN 9 - LOW FREESTANDING SIGN
  
 ALLOWED: 529.69 SQ. FT.
 PROPOSED: 22 SQ. FT.
  
 A. THIS SIGN IS SHOWN IN A SIGN LOCATION ON SITE PLAN.
  
 B. SIGN COMPLIES WITH ZONING CODE (PROVIDED IT MEETS
 SETBACK FROM RIGHT-OF-WAY).
  
 9) SIGN 11 - PARKING AREA INSTRUCTIONAL SIGN
  
 PROPOSED: 11 SQ. FT. PER FACE
  
 A. THE "AUDI" MAY NOT BE ON THE SIGN AS THIS THEN
 BECOMES A LOW FREESTANDING SIGN IN EXCESS OF THE NUMBER
 PERMITTED ON THE SITE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
  