Plan Review Details - Permit 14110621
| Plan Review Stops For Permit 14110621 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2015-03-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-03-16 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-03-16 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2015-03-16 11:27:34 | BUILDING PLAN REVIEW | | | REVISION: 14110621 | | | PERMIT:14050621 | | | ADD: 600 OKEECHOBEE BLVD. | | | CONT: COASTAL | | | TEL: ( | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2ND REVIEW | | | DATE: MARCH 12/ 2015 | | | ACTION: APPROVED | | | ADOLFO REYNA HAD SENT A E-MAIL 3/20/2015 WITH | | | ATTACHMENT SHEET A2.00 WITH FIRE RESISTANCE TABLE AND | | | FOOTNOTES. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | DEVELOPMENT SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2015-01-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-01-10 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-12-05 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2015-01-10 09:01:48 | BUILDING PLAN REVIEW | | | REVISION: 14110621 | | | PERMIT:14050621 | | | ADD: 600 OKEECHOBEE BLVD. | | | CONT: COASTAL | | | TEL: ( | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: JAN. 10/ 2015 | | | ACTION: PROVISO | | | | | | BUILDING REVISION APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | 1) SHEETS A4.01, A4.02 & A4.03 ALL INDICATE THROUGH THE | | | PROVIDED NARRATIVE TO ELIMINATE CONCRETE ENCASED | | | COLUMNS IN THE PREFUNCTION PERIMETER REV # 8. | | | THE 2010 FBC-B TABLE 601 REQUIRES THE STRUCTURAL | | | COLUMNS TO HAVE A 2 HOUR FIRE-RESISTANCE RATING, WITH | | | THE ELIMINATION OF BEING ENCASED IN CONCRETE HOW DO YOU | | | ENTEND ON MEETING THIS CODE REQUIREMENT? ALSO SEE 704.2 | | | COLUMN PROTECTION. | | | | | | 2) SHEETS A4.01 & A4.02 BOTH INDICATE THE ELIMINATION | | | OF MINERAL BOARD FIRE FIRE PROOFING IN LEU OF FIRE | | | PROOFING SPRAY, THIS CAN NOT BE ASSUMED WHERE THE | | | MINERAL BOARD IS ELIMINATED AND FIRE PROOFING SPRAY IS | | | TO BE APPLIED AT WHAT THICKNESS AND FOR HOW MANY HOURS | | | OF FIRE RATING. NO WHERE ELSE IN THE NARRATIVE DOES IT | | | GIVE US WHERE WE WILL FIND THIS INFORMATION. 2010 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1, ADMINISTRATION 107.2.1.3 ADDITIONAL | | | INFORMATION IS REQUIRED. | | | | | | 3) SHEET A4.11 STAIRWELLS 1, 2 & 3 ALL SHOW 3 NEW | | | ELLIMENTS TO EACH OF THE STAIRWELL LANDINGS (2) | | | CIRCULAR AND (1) AS A RECTANGLE THE NARRATIVE DOES NOT | | | INDICATE THE USAGE, PLEASE IDENTIFY. PLEASE REVIEW | | | SECTION: | | | | | | 2010 FBC-B 1022.4 PENETRATIONS. PENETRATIONS INTO AND | | | OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED | | | EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK | | | NECESSARY FOR INDEPENDENT VENTILATION OR | | | PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, | | | ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION | | | SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT | | | ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING | | | 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE | | | PROTECTED IN ACCORDANCE WITH SECTION 713. THERE SHALL | | | BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER | | | PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES. | | | | | | 4) FIRE HAS COMMENT ON THIS ITEM SHEET P1.06 NOTES 3 & | | | 4 INDICATE A ROOF DRAIN GOING TO WASTE IN STAIRWELL # | | | 3, THE PIPE RUNS ABOVE IN THE CEILING SPACE, PLEASE | | | PROVIDE IF THIS IS A RATED CEILING, IF SO IS IT A 2 HR | | | FIRE RATED CEILING? PROVIDE CODE COMPLIANCE WITH : | | | | | | 2010 FBC-B 1022.4 PENETRATIONS. PENETRATIONS INTO AND | | | OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED | | | EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK | | | NECESSARY FOR INDEPENDENT VENTILATION OR | | | PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, | | | ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION | | | SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT | | | ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING | | | 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE | | | PROTECTED IN ACCORDANCE WITH SECTION 713. THERE SHALL | | | BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER | | | PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES. | | | | | | 5) SHEET A14.01 THE NARRATIVE REV. # 8 INDICATES THE | | | EXTERIOR DOORS TO THE FPL VAULT ARE NOT TO BE 3 HR. | | | FIRE RATING. THIS IS NOT A CODE REQUIREMENT ENFORCEABLE | | | BY THE FLORIDA BUILDING CODE OR THE NEC BUT PLEASE | | | REVIEW THE FPL VAULT REQUIREMENT & AGREEMENT FOR YOUR | | | PROJECT. | | | | | | 6) LIFE SAFETY SHEETS TO SHOW AREA OF RESCUE ASSISTANCE | | | 2010 FBC-ACCESSIBILITY CODE 207.1. SEE SECTION 1007 OF | | | THE 2003 IBC 107.6 AREA OF REFUGE. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | DEVELOPMENT SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2015-03-27 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-03-27 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-03-25 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2015-03-27 15:58:10 | 3/27/2015 | | | PROJECT: WPC CONVENTION CENTER HILTON HOTEL REVISION | | | TRACKING #14110621 | | | PERMIT#: 14050111 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 4TH ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY | | | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS | | | ARE REQUIRED FOR SWIMMING POOLS, SITE LIGHTING, | | | GENERATORS. HOOD EXHAUST, FIRE ALARM, ACCESS CONTROL | | | SYSTEM, SECURITY, CCTV, NETWORK, DATA, AND, | | | COMMUNICATION. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-01-22 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-01-22 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-01-22 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2015-01-22 11:45:26 | 1/22/2015 | | | PROJECT: WPC CONVENTION CENTER HILTON HOTEL REVISION | | | TRACKING #14110621 | | | PERMIT#: 14050111 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 3RD ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) E1.03 | | | PROVIDE MANUFACTURER PRODUCT APPROVALS ON WHEEL CHAIR | | | LIFT. NEC 110.3(B) | | | | | | 2) E1.03 | | | VERIFY ANY LIGHT FIXTURE DISTANCE FROM SWIMMING POOL | | | WATER?S EDGE. 680.22(C)(1) | | | | | | 3) E1.11 | | | VERIFY REQUIRED CLEARANCES ABOUT ELECTRICAL EQUIPMENT | | | VFD?S DISC?S ETC.. . NEC 110.26 | | | | | | 4) E2.00, E2.01, E2.02 | | | A. KEY NOTES 1 THROUGH 5 ARE BLACKED OUT IN THE KEY | | | NOTE SCHEDULE YET STILL CALLED OUT ON THE FLOOR PLAN. | | | B. OUTLETS PLACED BEHIND THE BED SHALL BE EQUIPPED WITH | | | PROTECTION. NEC 210.60(B) | | | | | | 5) E2.02 | | | APPLY KEY NOTE 9 TO THE ENTRANCE TO PRESIDENTIAL SUITE | | | #1238 | | | | | | 6) E3.06, E3.07, E3.08 | | | VENDING MACHINES TO BE GFI PROTECTED. NEC 422.51 | | | OUTLETS WITHIN 6? OF A SINK TO BE GFI PROTECTED. NEC | | | 210.8(B)(5) | | | SEPARATE PERMIT APPLICATION(S) WITH SHOP DRAWINGS, | | | PRODUCT APPROVALS AND WRITTEN SEQUENCE OF OPERATION ARE | | | REQUIRED FOR ALL EXHAUST HOODS. | | | | | | 7) E4.01 | | | ADD DRAWING KEYNOTE 5 TO EMERGENCY GENERATOR FEEDER | | | F-11 FEEDING THE FIRE PUMP CONTROLLER. | | | ADD FEEDER SCHEDULE SYMBOL TO ALL FEEDERS ON RISER | | | DIAGRAM TO INDICATE PROPER CONDUCTOR SIZING PER NEC | | | 310.16 AND WPB AMENDMENTS TO FBC 107.3.2 | | | ADD NOTE AND INDICATE APPLICATION METHOD FOR BUILDING | | | SIGNAGE FOR COMPLIANCE WITH FBC-ENERGY 505.2.4 | | | | | | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY | | | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS | | | ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD | | | EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY, | | | CCTV, NETWORK, DATA, AND, COMMUNICATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | | REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2015-03-04 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
2015-03-04 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
2015-03-04 |
Time |
09:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2014-12-19 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
2014-12-19 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
2014-12-19 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2014-12-19 10:47:04 | ON SHEETS C5.02 AND C5.03, THE SANITARY IS SHOWN | | | CONNECTING WITH A 10X6" WYE WITHIN THE FLORIDA AVENUE | | | RIGHT-OF-WAY RATHER THAN VIA A SANITARY DOGHOUSE | | | MANHOLE AS SHOWN IN THE ENGINEERING DEPARTMENT | | | APPROVAL. PLEASE REVISE THE PLANS TO COMPLY WITH THE | | | APPROVED CONSTRUCTION PLANS. | | | | | | THE PLUMBING PLANS APPEAR TO SHOW ONLY ONE DISCHARGE | | | POINT FROM THE LIFT STATION, WHICH THEN APPEARS TO BE | | | ROUTED THROUGH THE GREASE TRAP. RESTROOM WASTE IS NOT | | | TO BE ROUTED THROUGH THE INTERCEPTOR OR SEPARATOR. | | | | | | PLEASE SHOW WHERE THE PROPOSED ROOF DRAINS WILL TIE | | | INTO THE STORM WATER MANAGEMENT SYSTEM. | | | | | | KELLY CRANFORD, P.E. | | | LAND DEVELOPMENT ENGINEER | | | PUBLIC WORKS | | | (561)494-1098 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2015-03-04 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2015-03-04 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2015-03-04 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2015-03-04 13:34:43 | FIRE PIT (SKY TERRACE) HAS NOT BEEN ACCEPTED OR | | | REJECTED AT THIS TIME. PRODUCT DATA AND SHOP DRAWINGS | | | TO BE SUBMITTED BY CONTRACTOR. OPEN FLAMES WILL NEED TO | | | BE GUARDED AGAINST ACCIDENTAL OR INTENTIONAL CONTACT BY | | | OCCUPANTS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2014-12-17 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-12-17 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-11-21 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2014-12-17 14:29:29 | 600 OKEECHOBEE BOULEVARD - HIGH RISE HOTEL | | | PERMIT #14050111 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | NOTE: ALL FIRE REVIEW COMMENTS REFERENCE NFPA 101 REFER | | | TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION WITH | | | FLORIDA AMENDMENTS). | | | | | | SHEET P0.01: ELEVATOR SUMP PIPING ROUTED THROUGH FIRE | | | PUMP ROOM. PER NFPA 20 SECTION 5.12.1.1.4, ROOMS | | | CONTAINING FIRE PUMPS SHALL BE FREE FROM STORAGE AND | | | PENETRATIONS NOT ESSENTIAL TO THE OPERATION OF THE PUMP | | | AND RELATED COMPONENTS. | | | | | | SHEET P1.02 & P1.06: ROOF DRAIN PIPING ROUTED IN EXIT | | | STAIR ENCLOSURE ABOVE CEILING. PER SECTION 7.1.3.2.1, | | | PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT | | | ENCLOSURE ASSEMBLY SHALL BE LIMITED TO DOOR ASSEMBLIES | | | FROM NORMALLY OCCUPIED SPACES AND CORRIDORS, REQUIRED | | | EXIT DOOR OPENINGS, ELECTRICAL CONDUIT SERVING THE EXIT | | | ENCLOSURE, DUCTWORK AND EQUIPMENT NECESSARY FOR | | | INDEPENDENT STAIR PRESSURIZATION, WATER OR STEAM PIPING | | | NECESSARY FOR THE HEATING OR COOLING OF THE EXIT | | | ENCLOSURE, SPRINKLER PIPING, STANDPIPES, AND | | | PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE | | | CIRCUITS ARE INSTALLED IN METAL CONDUIT AND THE | | | PENETRATIONS ARE PROTECTED. | | | | | | FIRE PIT (SKY TERRACE) HAS NOT BEEN ACCEPTED OR | | | REJECTED AT THIS TIME. PRODUCT DATA AND SHOP DRAWINGS | | | TO BE SUBMITTED BY CONTRACTOR. OPEN FLAMES WILL NEED TO | | | BE GUARDED AGAINST ACCIDENTAL OR INTENTIONAL CONTACT BY | | | OCCUPANTS. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2015-03-17 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-03-17 |
Time |
06:54 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-03-17 |
Time |
04:50 |
Sent To |
|
|
| Notes |
| 2015-03-17 06:56:19 | THE SPECIFICATIONS FOR THE GAS EQUIPMENT SHALL BE | | | SUBMITTED AT THE TIME OF THE GAS APPLICATION SUBMITTAL. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2015-01-07 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-12-15 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-12-01 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2015-01-13 11:48:35 | 1) THE SPECIFICATIONS FOR THE GAS EQUIPMENT SHALL BE | | | SUBMITTED AT THE TIME OF THE GAS APPLICATION SUBMITTAL. | | | 2) SHT. P3.02 - THE GAS LOAD IS LISTED AS 8,361,000 AND | | | I CALCULATE THE BTU LOAD AS 8,175,000 AND THE LOAD AT | | | THE METER SHOWS 7,853,000. CLARIFY. | | | 3).) THE LINE TO THE POOL & SPA HEATER IS UNDERSIZED AT | | | 1 1/2'. THE MAX. BTU LOAD AT 16' ( THE 20' COLUMN MUST | | | BE USED) IS 1430,000. THIS LINE SHALL BE SIZED TO 2" | | | PER TABLE 402.4 (2) OF THE 2010 FGC. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-03-27 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2015-03-27 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2015-02-25 |
Time |
15:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-01-29 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2015-01-29 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2014-11-19 |
Time |
11:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2015-01-06 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2015-01-06 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-12-27 |
Time |
07:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2015-03-17 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-03-17 |
Time |
06:54 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-03-16 |
Time |
11:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2014-12-15 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-12-15 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-12-01 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2014-12-15 12:12:23 | 1) ON THE ISOMETRIC DRAWING SHEETS, CLEARLY IDENTIFY | | | THE SPECIFIC AREAS OF THE FLOOR THAT APPLY TO THE | | | SPECIFIC ISOMETRIC; E.G.- AREA Q1, Q3, ETC.AND PROVIDE | | | A PLAN VIEW SHEET NUMBER OR ROOM NUMBERS. THIS WILL | | | HELP EXPRDITE THE REVIEW. | | | 2) THE SPECIFICATIONS FOR THE GAS EQUIPMENT SHALL BE | | | SUBMITTED AT THE TIME OF THE GAS APPLICATION SUBMITTAL. | | | 3) SHT. P1.02 - COOLING TOWER WATER SHALL NOT DISCHARGE | | | TO THE SANITARY SYSTEM PER SEC. 90-126 OF THE CITY OF | | | WPB CODE OF ORDINANCES SEC. 90-126 (5). SEE GRID LINES | | | G-H AND 1. | | | 4) SHT.P2.04 - GRID LINES B.1& 17 - SHOWS A FLOOR SINK | | | TO THE SANITARY AND A FLOOR DRAIN IN THE SAME AREA | | | DISCHARGING TO THE GREASE WASTE LINE.CLARIFY. | | | 5) SHT.P2.04 - LOCATION OF FLOOR SINK & FLOOR DRAIN AT | | | FIXTURES B8 & B11 DO NOT CORRELATE WITH THE KITCHEN AND | | | BAR ISOMETRIC ON P3.00. SEE GRID LINES A-B & 17 (TO THE | | | RIGHT OF THE STAIRWELL.) | | | 6) SHT. P3.00 - IDENTIFY THE GREASY WASTE ISOMETRICS AS | | | SUCH AND NOT AS SANITARY.WPB AMEND. TO 2010 FBC | | | 107.2.1. | | | 7) SHT.P3.00 - THE KITCHEN AND BAR ISOMETRIC SHOWS A 4" | | | FLOOR DRAIN BY GRID LINES B.1 & 17 BUT IT IS NOT SHOWN | | | ON SHT. P2.04. | | | 8) SHT. P3.00 - A HAND SINK (B33) IS SHOWN ON THE | | | KITCHEN AND BAR ISOMETRIC BUT IS NOT SHOWN ON | | | SHT.P2.04. SEE GRID LINE 17 BETWEEN A-B. | | | 9) SHT.P3.01E - IDENTIFY THE 750 GAL. GREASE | | | INTERCEPTOR ON THE RISER.WPB AMEND. TO 2010 FBC | | | SEC.107.2.1. | | | 10) SHT.P3.01E -KEYNOTE #6- CALLS OUT A 1250 GAL. | | | GREASE INTERCEPTOR BUT IT IS ALSO IDENTIFYING THE | | | OIL/SAND INTERCEPTOR AS SUCH.CLARIFY. | | | 11) SHT. P3.00 - RISER #2 - SHOW THE | | | CONNECTION/CONTINUATION POINT OF THE 4" SANITARY TO THE | | | LIFT STATION. WPB AMEND. TO 2010 FBC SEC.107.2.1. | | | 12) SHT. P3.01 - SHT. P3.01 HAS A NOTE ON WATER RISERE | | | #6 THAT REFERS TO A 4" GREASE WASTE PIPE /CONNECT TO | | | GREASE TRAP. CLARIFY. | | | 13) SHT. P3.01G - THE SANITARY ISOMETRIC DOES NOT | | | CORRELATE WITH THE FLOOR PLAN ON SHT.P103.FLOOR DRAINS | | | ARE SHOWN ON THE FLOOR PLAN AND NOT ON THE RISER AND | | | VICE-VERSA, NUMBER OF WATER CLOSETS AND LAVATORIES ON | | | THE FLOOR PLAN DO NOT MATCH ISOMETRIC, ISOMETRIC FOR | | | TOILET ROOMS 116, 117,114B AND 114C DO NOT MATCH FLOOR | | | PLAN. | | | 14) SHT. P3.01E- SHOWS A WATER CLOSET DRAINING INTO A | | | 2" LINE. SIZE THE WASTE AND VENT FOR THIS FIXTURE. | | | 15) SHT. P3.01E - ELEVATOR SUMP RISER NOTE STATES | | | "ELEVATOR SUMP/TYP. OF 5 BUT ONLY 4 SUMPS ARE SHOWN ON | | | THE RISER. CLARIFY. | | | 16) SHT.P3.01E - THE NARRATIVE STATES "REMOVE SUMP FROM | | | ELEVATOR PIT". BUT THIS IS NOT REFERENCED ON THE | | | ELEVATOR PIT RISER. CLARIFY. IDENTIFY THE ELEVATOR | | | NUMBER WHERE THE SUMP WAS REMOVED. | | | 17) SHT. P3.01F- RISER #4 SHOWS THE CIRCLED NUMBER 1 AS | | | SHOCK ARRESTORS & THE KEYNOTE STATES IT AS A '2 1/2 " | | | COLD WATER LINE ABOVE THE CEILING.CLARIFY. | | | 18) SHT. P3.01G - RISER #2 - SHOW THE CONNECTION POINT | | | OF THE 4" SOIL STACK. | | | 19) SHT. 3.00 - RISER #2 - SHOW THE CONNECTION POINT OF | | | THE 4" SANITARY LINE TO THE LIFT STATION. | | | 20) SHT. P3.02 - THE GAS LOAD IS LISTED AS 8,361,000 | | | AND I CALCULATE THE BTU LOAD AS 8,175,000 AND THE LOAD | | | AT THE METER SHOWS 7,853,000. CLARIFY. | | | 21) THE LINE TO THE POOL & SPA HEATER IS UNDERSIZED AT | | | 1 1/2'. THE MAX. BTU LOAD AT 16' ( THE 20' COLUMN MUST | | | BE USED) IS 1430,000. THIS LINE SHALL BE SIZED TO 2" | | | PER TABLE 402.4 (2) OF THE 2010 FGC. | | | 22) SHT. P3.05 - WHAT IS THE 3" FIRE RISER CONNECTING | | | TO? IDENTIFY THE SHT. NUMBER WHERE THE CONTINUATION CAN | | | BE FOUND? IDENTIFY THE CONTINUATION POINT FOR THIS | | | LINE. | | | 23) SHT. P4.04 - SUBMIT A KEYNOTE LEGEND FOR THE | | | CIRCLED NUMBER 1 ON THE SANITARY RISERS. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2015-04-09 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-12-01 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-04-09 |
Time |
16:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2015-03-06 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2015-03-06 |
Time |
12:16 |
Rev Time |
2.00 |
| Received By |
eschneid |
Date |
2015-03-06 |
Time |
12:16 |
Sent To |
|
|
| Notes |
| 2015-03-06 12:17:09 | PASSED W/PROVISO | | | | | | 1) THE SIGHT LINE DRAWING SHOWS THAT THE TOP OF THE | | | LAUNDRY CHUTE MAY BE VISIBLE. IF IT IS VISIBLE (NOT | | | SCREENED) WHEN THE CHUTE HAS BEEN PLACED ON THE ROOF | | | AND THE ARCHITECTURAL FEATURES HAVE BEEN INSTALLED, | | | THEN THE EXPOSED PORTION OF THE CHUTE SHALL BE | | | SCREENED. PAINTING THE CHUTE TO MATCH THE ARCHITECTURAL | | | FEATURE OR THE SKY MAY SUFFICE IF THE CHUTE IS NO | | | LONGER DETECTABLE. | | | | | | 2) ALL RIGHT-OF-WAY TIMING AND SEPARATE PERMIT | | | CONDITIONS REMAIN IN PLACE. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2015-01-29 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2015-01-29 |
Time |
10:10 |
Rev Time |
6.00 |
| Received By |
eschneid |
Date |
2015-01-29 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2015-01-29 16:07:56 | FAILED | | | | | | 1) THE REVISED PLANS DO NOT CORRESPOND TO THE LATEST | | | SUBMITTED MINOR AMENDMENT. AN EXAMPLE IS THE CHANGED | | | DOOR PLACEMENT BY THE EVENT LAWNS. PLEASE ENSURE THAT | | | THE PERMIT PLANS AND THE MINOR AMENDMENT PLANS MATCH - | | | THIS INCLUDES THE DATA TABLES. | | | | | | 2) SHEET A7.15 NO LONGER SHOWS THE LINEN SHOOT ROOF TOP | | | AREA BEING SCREENED. PROVIDE HOW THIS ROOFTOP EQUIPMENT | | | WILL BE SCREENED. SHEET A9.03 SEEMS TO CONFLICT AS | | | SCREENING IS SHOWN. PLEASE EXPLAIN. | | | | | | 3) THE FOLLOWING PROVISO WAS NOT ADDRESSED FROM THE | | | PREVIOUS PERMIT SUBMITTAL: | | | | | | AS PART OF A PERMIT REVISION PRIOR TO THEIR | | | INSTALLATION, PROVIDE SHEET E6.02, THE FIXTURE SHEET | | | WHICH SHOWS THE SPECIFIC LIGHTING WHICH WILL BE | | | PROVIDED FOR THE ART NICHES. THIS SHEET IS REFERENCED | | | AS INCLUDED, BUT IS NOT ON THE ELECTRONIC UPLOAD. ALSO, | | | PLEASE INCLUDE THE SPEC SHEET. | | | | | | 4) ALL RIGHT-OF-WAY TIMING AND SEPARATE PERMIT | | | CONDITIONS REMAIN IN PLACE. | | | | | | CONTACT ERIC SCHNEIDER (561) 822-1446. | | | | | | | | 2014-12-01 11:43:54 | 12/1/14 |
|
|
|