Plan Review Details - Permit 14110621
Plan Review Stops For Permit 14110621
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-03-26 Cont ID  
Sent By jwitmer Date 2015-03-16 Time 11:27 Rev Time 0.00
Received By jwitmer Date 2015-03-16 Time 10:08 Sent To  
Notes
2015-03-16 11:27:34BUILDING PLAN REVIEW
 REVISION: 14110621
 PERMIT:14050621
 ADD: 600 OKEECHOBEE BLVD.
 CONT: COASTAL
 TEL: (
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: MARCH 12/ 2015
 ACTION: APPROVED
 ADOLFO REYNA HAD SENT A E-MAIL 3/20/2015 WITH
 ATTACHMENT SHEET A2.00 WITH FIRE RESISTANCE TABLE AND
 FOOTNOTES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-01-10 Cont ID  
Sent By jwitmer Date 2015-01-10 Time 10:00 Rev Time 0.00
Received By jwitmer Date 2014-12-05 Time 13:05 Sent To  
Notes
2015-01-10 09:01:48BUILDING PLAN REVIEW
 REVISION: 14110621
 PERMIT:14050621
 ADD: 600 OKEECHOBEE BLVD.
 CONT: COASTAL
 TEL: (
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JAN. 10/ 2015
 ACTION: PROVISO
  
 BUILDING REVISION APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEETS A4.01, A4.02 & A4.03 ALL INDICATE THROUGH THE
 PROVIDED NARRATIVE TO ELIMINATE CONCRETE ENCASED
 COLUMNS IN THE PREFUNCTION PERIMETER REV # 8.
 THE 2010 FBC-B TABLE 601 REQUIRES THE STRUCTURAL
 COLUMNS TO HAVE A 2 HOUR FIRE-RESISTANCE RATING, WITH
 THE ELIMINATION OF BEING ENCASED IN CONCRETE HOW DO YOU
 ENTEND ON MEETING THIS CODE REQUIREMENT? ALSO SEE 704.2
 COLUMN PROTECTION.
  
 2) SHEETS A4.01 & A4.02 BOTH INDICATE THE ELIMINATION
 OF MINERAL BOARD FIRE FIRE PROOFING IN LEU OF FIRE
 PROOFING SPRAY, THIS CAN NOT BE ASSUMED WHERE THE
 MINERAL BOARD IS ELIMINATED AND FIRE PROOFING SPRAY IS
 TO BE APPLIED AT WHAT THICKNESS AND FOR HOW MANY HOURS
 OF FIRE RATING. NO WHERE ELSE IN THE NARRATIVE DOES IT
 GIVE US WHERE WE WILL FIND THIS INFORMATION. 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) SHEET A4.11 STAIRWELLS 1, 2 & 3 ALL SHOW 3 NEW
 ELLIMENTS TO EACH OF THE STAIRWELL LANDINGS (2)
 CIRCULAR AND (1) AS A RECTANGLE THE NARRATIVE DOES NOT
 INDICATE THE USAGE, PLEASE IDENTIFY. PLEASE REVIEW
 SECTION:
  
 2010 FBC-B 1022.4 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED
 EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK
 NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT
 ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 713. THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 4) FIRE HAS COMMENT ON THIS ITEM SHEET P1.06 NOTES 3 &
 4 INDICATE A ROOF DRAIN GOING TO WASTE IN STAIRWELL #
 3, THE PIPE RUNS ABOVE IN THE CEILING SPACE, PLEASE
 PROVIDE IF THIS IS A RATED CEILING, IF SO IS IT A 2 HR
 FIRE RATED CEILING? PROVIDE CODE COMPLIANCE WITH :
  
 2010 FBC-B 1022.4 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED
 EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK
 NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT
 ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 713. THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 5) SHEET A14.01 THE NARRATIVE REV. # 8 INDICATES THE
 EXTERIOR DOORS TO THE FPL VAULT ARE NOT TO BE 3 HR.
 FIRE RATING. THIS IS NOT A CODE REQUIREMENT ENFORCEABLE
 BY THE FLORIDA BUILDING CODE OR THE NEC BUT PLEASE
 REVIEW THE FPL VAULT REQUIREMENT & AGREEMENT FOR YOUR
 PROJECT.
  
 6) LIFE SAFETY SHEETS TO SHOW AREA OF RESCUE ASSISTANCE
 2010 FBC-ACCESSIBILITY CODE 207.1. SEE SECTION 1007 OF
 THE 2003 IBC 107.6 AREA OF REFUGE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-27 Cont ID  
Sent By dhayes Date 2015-03-27 Time 15:55 Rev Time 0.00
Received By dhayes Date 2015-03-25 Time 09:51 Sent To  
Notes
2015-03-27 15:58:103/27/2015
 PROJECT: WPC CONVENTION CENTER HILTON HOTEL REVISION
 TRACKING #14110621
 PERMIT#: 14050111
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 4TH ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SWIMMING POOLS, SITE LIGHTING,
 GENERATORS. HOOD EXHAUST, FIRE ALARM, ACCESS CONTROL
 SYSTEM, SECURITY, CCTV, NETWORK, DATA, AND,
 COMMUNICATION.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-01-22 Cont ID  
Sent By dhayes Date 2015-01-22 Time 11:44 Rev Time 0.00
Received By dhayes Date 2015-01-22 Time 11:43 Sent To  
Notes
2015-01-22 11:45:261/22/2015
 PROJECT: WPC CONVENTION CENTER HILTON HOTEL REVISION
 TRACKING #14110621
 PERMIT#: 14050111
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) E1.03
 PROVIDE MANUFACTURER PRODUCT APPROVALS ON WHEEL CHAIR
 LIFT. NEC 110.3(B)
  
 2) E1.03
 VERIFY ANY LIGHT FIXTURE DISTANCE FROM SWIMMING POOL
 WATER?S EDGE. 680.22(C)(1)
  
 3) E1.11
 VERIFY REQUIRED CLEARANCES ABOUT ELECTRICAL EQUIPMENT
 VFD?S DISC?S ETC.. . NEC 110.26
  
 4) E2.00, E2.01, E2.02
 A. KEY NOTES 1 THROUGH 5 ARE BLACKED OUT IN THE KEY
 NOTE SCHEDULE YET STILL CALLED OUT ON THE FLOOR PLAN.
 B. OUTLETS PLACED BEHIND THE BED SHALL BE EQUIPPED WITH
 PROTECTION. NEC 210.60(B)
  
 5) E2.02
 APPLY KEY NOTE 9 TO THE ENTRANCE TO PRESIDENTIAL SUITE
 #1238
  
 6) E3.06, E3.07, E3.08
 VENDING MACHINES TO BE GFI PROTECTED. NEC 422.51
 OUTLETS WITHIN 6? OF A SINK TO BE GFI PROTECTED. NEC
 210.8(B)(5)
 SEPARATE PERMIT APPLICATION(S) WITH SHOP DRAWINGS,
 PRODUCT APPROVALS AND WRITTEN SEQUENCE OF OPERATION ARE
 REQUIRED FOR ALL EXHAUST HOODS.
  
 7) E4.01
 ADD DRAWING KEYNOTE 5 TO EMERGENCY GENERATOR FEEDER
 F-11 FEEDING THE FIRE PUMP CONTROLLER.
 ADD FEEDER SCHEDULE SYMBOL TO ALL FEEDERS ON RISER
 DIAGRAM TO INDICATE PROPER CONDUCTOR SIZING PER NEC
 310.16 AND WPB AMENDMENTS TO FBC 107.3.2
 ADD NOTE AND INDICATE APPLICATION METHOD FOR BUILDING
 SIGNAGE FOR COMPLIANCE WITH FBC-ENERGY 505.2.4
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD
 EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY,
 CCTV, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-03-04 Cont ID  
Sent By cranford Date 2015-03-04 Time 09:43 Rev Time 0.00
Received By cranford Date 2015-03-04 Time 09:43 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2014-12-19 Cont ID  
Sent By cranford Date 2014-12-19 Time 11:52 Rev Time 0.00
Received By cranford Date 2014-12-19 Time 09:46 Sent To  
Notes
2014-12-19 10:47:04ON SHEETS C5.02 AND C5.03, THE SANITARY IS SHOWN
 CONNECTING WITH A 10X6" WYE WITHIN THE FLORIDA AVENUE
 RIGHT-OF-WAY RATHER THAN VIA A SANITARY DOGHOUSE
 MANHOLE AS SHOWN IN THE ENGINEERING DEPARTMENT
 APPROVAL. PLEASE REVISE THE PLANS TO COMPLY WITH THE
 APPROVED CONSTRUCTION PLANS.
  
 THE PLUMBING PLANS APPEAR TO SHOW ONLY ONE DISCHARGE
 POINT FROM THE LIFT STATION, WHICH THEN APPEARS TO BE
 ROUTED THROUGH THE GREASE TRAP. RESTROOM WASTE IS NOT
 TO BE ROUTED THROUGH THE INTERCEPTOR OR SEPARATOR.
  
 PLEASE SHOW WHERE THE PROPOSED ROOF DRAINS WILL TIE
 INTO THE STORM WATER MANAGEMENT SYSTEM.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS
 (561)494-1098
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-03-04 Cont ID  
Sent By wjolin Date 2015-03-04 Time 13:34 Rev Time 0.00
Received By wjolin Date 2015-03-04 Time 13:24 Sent To  
Notes
2015-03-04 13:34:43FIRE PIT (SKY TERRACE) HAS NOT BEEN ACCEPTED OR
 REJECTED AT THIS TIME. PRODUCT DATA AND SHOP DRAWINGS
 TO BE SUBMITTED BY CONTRACTOR. OPEN FLAMES WILL NEED TO
 BE GUARDED AGAINST ACCIDENTAL OR INTENTIONAL CONTACT BY
 OCCUPANTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-12-17 Cont ID  
Sent By wjolin Date 2014-12-17 Time 15:35 Rev Time 0.00
Received By wjolin Date 2014-11-21 Time 16:58 Sent To  
Notes
2014-12-17 14:29:29600 OKEECHOBEE BOULEVARD - HIGH RISE HOTEL
 PERMIT #14050111
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: ALL FIRE REVIEW COMMENTS REFERENCE NFPA 101 REFER
 TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION WITH
 FLORIDA AMENDMENTS).
  
 SHEET P0.01: ELEVATOR SUMP PIPING ROUTED THROUGH FIRE
 PUMP ROOM. PER NFPA 20 SECTION 5.12.1.1.4, ROOMS
 CONTAINING FIRE PUMPS SHALL BE FREE FROM STORAGE AND
 PENETRATIONS NOT ESSENTIAL TO THE OPERATION OF THE PUMP
 AND RELATED COMPONENTS.
  
 SHEET P1.02 & P1.06: ROOF DRAIN PIPING ROUTED IN EXIT
 STAIR ENCLOSURE ABOVE CEILING. PER SECTION 7.1.3.2.1,
 PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT
 ENCLOSURE ASSEMBLY SHALL BE LIMITED TO DOOR ASSEMBLIES
 FROM NORMALLY OCCUPIED SPACES AND CORRIDORS, REQUIRED
 EXIT DOOR OPENINGS, ELECTRICAL CONDUIT SERVING THE EXIT
 ENCLOSURE, DUCTWORK AND EQUIPMENT NECESSARY FOR
 INDEPENDENT STAIR PRESSURIZATION, WATER OR STEAM PIPING
 NECESSARY FOR THE HEATING OR COOLING OF THE EXIT
 ENCLOSURE, SPRINKLER PIPING, STANDPIPES, AND
 PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE
 CIRCUITS ARE INSTALLED IN METAL CONDUIT AND THE
 PENETRATIONS ARE PROTECTED.
  
 FIRE PIT (SKY TERRACE) HAS NOT BEEN ACCEPTED OR
 REJECTED AT THIS TIME. PRODUCT DATA AND SHOP DRAWINGS
 TO BE SUBMITTED BY CONTRACTOR. OPEN FLAMES WILL NEED TO
 BE GUARDED AGAINST ACCIDENTAL OR INTENTIONAL CONTACT BY
 OCCUPANTS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-03-17 Cont ID  
Sent By tklarge Date 2015-03-17 Time 06:54 Rev Time 0.00
Received By tklarge Date 2015-03-17 Time 04:50 Sent To  
Notes
2015-03-17 06:56:19THE SPECIFICATIONS FOR THE GAS EQUIPMENT SHALL BE
 SUBMITTED AT THE TIME OF THE GAS APPLICATION SUBMITTAL.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-01-07 Cont ID  
Sent By tklarge Date 2014-12-15 Time 15:26 Rev Time 0.00
Received By tklarge Date 2014-12-01 Time 15:26 Sent To  
Notes
2015-01-13 11:48:351) THE SPECIFICATIONS FOR THE GAS EQUIPMENT SHALL BE
 SUBMITTED AT THE TIME OF THE GAS APPLICATION SUBMITTAL.
 2) SHT. P3.02 - THE GAS LOAD IS LISTED AS 8,361,000 AND
 I CALCULATE THE BTU LOAD AS 8,175,000 AND THE LOAD AT
 THE METER SHOWS 7,853,000. CLARIFY.
 3).) THE LINE TO THE POOL & SPA HEATER IS UNDERSIZED AT
 1 1/2'. THE MAX. BTU LOAD AT 16' ( THE 20' COLUMN MUST
 BE USED) IS 1430,000. THIS LINE SHALL BE SIZED TO 2"
 PER TABLE 402.4 (2) OF THE 2010 FGC.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-27 Cont ID  
Sent By lmarchan Date 2015-03-27 Time 16:31 Rev Time 0.00
Received By lmarchan Date 2015-02-25 Time 15:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-29 Cont ID  
Sent By cpuell Date 2015-01-29 Time 16:25 Rev Time 0.00
Received By cpuell Date 2014-11-19 Time 11:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-01-06 Cont ID  
Sent By hmoser Date 2015-01-06 Time 14:25 Rev Time 0.00
Received By hmoser Date 2014-12-27 Time 07:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-03-17 Cont ID  
Sent By tklarge Date 2015-03-17 Time 06:54 Rev Time 0.00
Received By tklarge Date 2015-03-16 Time 11:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-12-15 Cont ID  
Sent By tklarge Date 2014-12-15 Time 12:12 Rev Time 0.00
Received By tklarge Date 2014-12-01 Time 13:11 Sent To  
Notes
2014-12-15 12:12:231) ON THE ISOMETRIC DRAWING SHEETS, CLEARLY IDENTIFY
 THE SPECIFIC AREAS OF THE FLOOR THAT APPLY TO THE
 SPECIFIC ISOMETRIC; E.G.- AREA Q1, Q3, ETC.AND PROVIDE
 A PLAN VIEW SHEET NUMBER OR ROOM NUMBERS. THIS WILL
 HELP EXPRDITE THE REVIEW.
 2) THE SPECIFICATIONS FOR THE GAS EQUIPMENT SHALL BE
 SUBMITTED AT THE TIME OF THE GAS APPLICATION SUBMITTAL.
 3) SHT. P1.02 - COOLING TOWER WATER SHALL NOT DISCHARGE
 TO THE SANITARY SYSTEM PER SEC. 90-126 OF THE CITY OF
 WPB CODE OF ORDINANCES SEC. 90-126 (5). SEE GRID LINES
 G-H AND 1.
 4) SHT.P2.04 - GRID LINES B.1& 17 - SHOWS A FLOOR SINK
 TO THE SANITARY AND A FLOOR DRAIN IN THE SAME AREA
 DISCHARGING TO THE GREASE WASTE LINE.CLARIFY.
 5) SHT.P2.04 - LOCATION OF FLOOR SINK & FLOOR DRAIN AT
 FIXTURES B8 & B11 DO NOT CORRELATE WITH THE KITCHEN AND
 BAR ISOMETRIC ON P3.00. SEE GRID LINES A-B & 17 (TO THE
 RIGHT OF THE STAIRWELL.)
 6) SHT. P3.00 - IDENTIFY THE GREASY WASTE ISOMETRICS AS
 SUCH AND NOT AS SANITARY.WPB AMEND. TO 2010 FBC
 107.2.1.
 7) SHT.P3.00 - THE KITCHEN AND BAR ISOMETRIC SHOWS A 4"
 FLOOR DRAIN BY GRID LINES B.1 & 17 BUT IT IS NOT SHOWN
 ON SHT. P2.04.
 8) SHT. P3.00 - A HAND SINK (B33) IS SHOWN ON THE
 KITCHEN AND BAR ISOMETRIC BUT IS NOT SHOWN ON
 SHT.P2.04. SEE GRID LINE 17 BETWEEN A-B.
 9) SHT.P3.01E - IDENTIFY THE 750 GAL. GREASE
 INTERCEPTOR ON THE RISER.WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 10) SHT.P3.01E -KEYNOTE #6- CALLS OUT A 1250 GAL.
 GREASE INTERCEPTOR BUT IT IS ALSO IDENTIFYING THE
 OIL/SAND INTERCEPTOR AS SUCH.CLARIFY.
 11) SHT. P3.00 - RISER #2 - SHOW THE
 CONNECTION/CONTINUATION POINT OF THE 4" SANITARY TO THE
 LIFT STATION. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 12) SHT. P3.01 - SHT. P3.01 HAS A NOTE ON WATER RISERE
 #6 THAT REFERS TO A 4" GREASE WASTE PIPE /CONNECT TO
 GREASE TRAP. CLARIFY.
 13) SHT. P3.01G - THE SANITARY ISOMETRIC DOES NOT
 CORRELATE WITH THE FLOOR PLAN ON SHT.P103.FLOOR DRAINS
 ARE SHOWN ON THE FLOOR PLAN AND NOT ON THE RISER AND
 VICE-VERSA, NUMBER OF WATER CLOSETS AND LAVATORIES ON
 THE FLOOR PLAN DO NOT MATCH ISOMETRIC, ISOMETRIC FOR
 TOILET ROOMS 116, 117,114B AND 114C DO NOT MATCH FLOOR
 PLAN.
 14) SHT. P3.01E- SHOWS A WATER CLOSET DRAINING INTO A
 2" LINE. SIZE THE WASTE AND VENT FOR THIS FIXTURE.
 15) SHT. P3.01E - ELEVATOR SUMP RISER NOTE STATES
 "ELEVATOR SUMP/TYP. OF 5 BUT ONLY 4 SUMPS ARE SHOWN ON
 THE RISER. CLARIFY.
 16) SHT.P3.01E - THE NARRATIVE STATES "REMOVE SUMP FROM
 ELEVATOR PIT". BUT THIS IS NOT REFERENCED ON THE
 ELEVATOR PIT RISER. CLARIFY. IDENTIFY THE ELEVATOR
 NUMBER WHERE THE SUMP WAS REMOVED.
 17) SHT. P3.01F- RISER #4 SHOWS THE CIRCLED NUMBER 1 AS
 SHOCK ARRESTORS & THE KEYNOTE STATES IT AS A '2 1/2 "
 COLD WATER LINE ABOVE THE CEILING.CLARIFY.
 18) SHT. P3.01G - RISER #2 - SHOW THE CONNECTION POINT
 OF THE 4" SOIL STACK.
 19) SHT. 3.00 - RISER #2 - SHOW THE CONNECTION POINT OF
 THE 4" SANITARY LINE TO THE LIFT STATION.
 20) SHT. P3.02 - THE GAS LOAD IS LISTED AS 8,361,000
 AND I CALCULATE THE BTU LOAD AS 8,175,000 AND THE LOAD
 AT THE METER SHOWS 7,853,000. CLARIFY.
 21) THE LINE TO THE POOL & SPA HEATER IS UNDERSIZED AT
 1 1/2'. THE MAX. BTU LOAD AT 16' ( THE 20' COLUMN MUST
 BE USED) IS 1430,000. THIS LINE SHALL BE SIZED TO 2"
 PER TABLE 402.4 (2) OF THE 2010 FGC.
 22) SHT. P3.05 - WHAT IS THE 3" FIRE RISER CONNECTING
 TO? IDENTIFY THE SHT. NUMBER WHERE THE CONTINUATION CAN
 BE FOUND? IDENTIFY THE CONTINUATION POINT FOR THIS
 LINE.
 23) SHT. P4.04 - SUBMIT A KEYNOTE LEGEND FOR THE
 CIRCLED NUMBER 1 ON THE SANITARY RISERS.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-04-09 Cont ID  
Sent By tklarge Date 2014-12-01 Time 10:02 Rev Time 0.00
Received By skennedy Date 2015-04-09 Time 16:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-03-06 Cont ID  
Sent By eschneid Date 2015-03-06 Time 12:16 Rev Time 2.00
Received By eschneid Date 2015-03-06 Time 12:16 Sent To  
Notes
2015-03-06 12:17:09PASSED W/PROVISO
  
 1) THE SIGHT LINE DRAWING SHOWS THAT THE TOP OF THE
 LAUNDRY CHUTE MAY BE VISIBLE. IF IT IS VISIBLE (NOT
 SCREENED) WHEN THE CHUTE HAS BEEN PLACED ON THE ROOF
 AND THE ARCHITECTURAL FEATURES HAVE BEEN INSTALLED,
 THEN THE EXPOSED PORTION OF THE CHUTE SHALL BE
 SCREENED. PAINTING THE CHUTE TO MATCH THE ARCHITECTURAL
 FEATURE OR THE SKY MAY SUFFICE IF THE CHUTE IS NO
 LONGER DETECTABLE.
  
 2) ALL RIGHT-OF-WAY TIMING AND SEPARATE PERMIT
 CONDITIONS REMAIN IN PLACE.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-01-29 Cont ID  
Sent By eschneid Date 2015-01-29 Time 10:10 Rev Time 6.00
Received By eschneid Date 2015-01-29 Time 10:10 Sent To  
Notes
2015-01-29 16:07:56FAILED
  
 1) THE REVISED PLANS DO NOT CORRESPOND TO THE LATEST
 SUBMITTED MINOR AMENDMENT. AN EXAMPLE IS THE CHANGED
 DOOR PLACEMENT BY THE EVENT LAWNS. PLEASE ENSURE THAT
 THE PERMIT PLANS AND THE MINOR AMENDMENT PLANS MATCH -
 THIS INCLUDES THE DATA TABLES.
  
 2) SHEET A7.15 NO LONGER SHOWS THE LINEN SHOOT ROOF TOP
 AREA BEING SCREENED. PROVIDE HOW THIS ROOFTOP EQUIPMENT
 WILL BE SCREENED. SHEET A9.03 SEEMS TO CONFLICT AS
 SCREENING IS SHOWN. PLEASE EXPLAIN.
  
 3) THE FOLLOWING PROVISO WAS NOT ADDRESSED FROM THE
 PREVIOUS PERMIT SUBMITTAL:
  
 AS PART OF A PERMIT REVISION PRIOR TO THEIR
 INSTALLATION, PROVIDE SHEET E6.02, THE FIXTURE SHEET
 WHICH SHOWS THE SPECIFIC LIGHTING WHICH WILL BE
 PROVIDED FOR THE ART NICHES. THIS SHEET IS REFERENCED
 AS INCLUDED, BUT IS NOT ON THE ELECTRONIC UPLOAD. ALSO,
 PLEASE INCLUDE THE SPEC SHEET.
  
 4) ALL RIGHT-OF-WAY TIMING AND SEPARATE PERMIT
 CONDITIONS REMAIN IN PLACE.
  
 CONTACT ERIC SCHNEIDER (561) 822-1446.
  
  