Plan Review Details - Permit 14110576
Plan Review Stops For Permit 14110576
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-05-04 Cont ID  
Sent By JWITMER Date 2015-05-04 Time 09:50 Rev Time 0.00
Received By jwitmer Date 2015-05-04 Time   Sent To  
Notes
2015-05-04 09:49:46BUILDING PLAN REVIEW
 PERMIT: 14110576
 ADD: 6230 S DIXIE HWY, UNIT 6230A & 6230 B
 CONT: CARLOS GONZALEX
 TEL: (561)386-8217
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. MAY 04/ 2015
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 4) 2ND REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 5) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-02 Cont ID  
Sent By jwitmer Date 2014-12-02 Time 14:20 Rev Time 0.00
Received By jwitmer Date 2014-12-02 Time 13:57 Sent To  
Notes
2014-12-02 14:20:14BUILDING PLAN REVIEW
 PERMIT: 14110576
 ADD: 6230 S DIXIE HWY, UNIT 6230A & 6230 B
 CONT: CARLOS GONZALEX
 TEL: (561)386-8217
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 02/ 2014
 ACTION: DENIED
  
 1) SHEET 2 OF 3 INDICATES THE SPLITTING THE TENANTCY
 INTO 2 SMALLER TENANT SPACES. THE TENANT WALL IS SHOWN
 AS DETAIL A THIS SHEET. THE DETAIL INDICATES A 1 HOUR
 FIRE RATED WALL WITH 3 5/8 IN. METAL STUDS CENTER TO
 CENTER NOT GIVEN AND 5/8 IN DRYWALL. PLEASE PROVIDE THE
 ASSEMBLY FROM UL OR THE GYPSUM ASSOCIATION WHERE 5/8
 INCH DRYWALL PROVIDES A ONE HOUR RATING. EVEN THE 2010
 FBC-B TABLE 720.1(2) (16) INDICATES THE USE OF 5/8 INCH
 TYPE X DRYWALL FOR FIRE RATED WALLS.
  
 2) THR NEW PROPOSED TENANT SEPARATION WALL DETAIL IS
 NOT CLEAR WHERE THE TOP OFTHE WALL IS GOING TO STOP,
 SHOW COMPLIANCE WITH SECTION 709.4 CONTINUITY. FIRE
 PARTITIONS SHALL EXTEND FROM THE TOP OF THE FOUNDATION
 OR FLOOR/CEILING ASSEMBLY BELOW TO THE UNDERSIDE OF THE
 FLOOR OR ROOF SHEATHING, SLAB OR DECK ABOVE OR TO THE
 FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING
 ASSEMBLY ABOVE, AND SHALL BE SECURELY ATTACHED THERETO.
 IF THE PARTITIONS ARE NOT CONTINUOUS TO THE SHEATHING,
 DECK OR SLAB, AND WHERE CONSTRUCTED OF COMBUSTIBLE
 CONSTRUCTION, THE SPACE BETWEEN THE CEILING AND THE
 SHEATHING, DECK OR SLAB ABOVE SHALL BE FIREBLOCKED OR
 DRAFTSTOPPED IN ACCORDANCE WITH SECTIONS 717.2 AND
 717.3 AT THE PARTITION LINE. THE SUPPORTING
 CONSTRUCTION SHALL BE PROTECTED TO AFFORD THE REQUIRED
 FIRE-RESISTANCE RATING OF THE WALL SUPPORTED, EXCEPT
 FOR WALLS SEPARATING TENANT SPACES IN COVERED MALL
 BUILDINGS, WALLS SEPARATING DWELLING UNITS, WALLS
 SEPARATING SLEEPING UNITS AND CORRIDOR WALLS, IN
 BUILDINGS OF TYPE IIB, IIIB AND VB CONSTRUCTION
  
 3) THE EXISTING FRONT STOREFRONT PANEL IS BEING REMOVED
 AND A ALCOVE IS BEING CREATED. THIS CONSTRUCTION IS TO
 BE WEATHER TIGHT THERE IS NO WALL IDENTIFYING TAGS IN
 THIS WALL SECTION, NOR IS THERE A SECTION THROUGH THE
 CEILING AS TO THE MATERIALS TO CREATE THE ALCOVE
 CEILING NOR THE FRAMING ABOVE.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,107.2.1.3.ADDITIONAL
 INFORMATION REQUIRED. NOTE THIS IS A EXTERIOR WALL AND
 WILL HAVE TO MEET THE PRESSURES FOR 170 VULT WIND
 LOADING, PARTOF THE MWFRS, MAIN WIND FORCE RESISTING
 SYSTEM.
  
 4) .2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-05-18 Cont ID  
Sent By D.HAYES Date 2015-05-18 Time 15:50 Rev Time 0.00
Received By dhayes Date 2015-05-18 Time 15:50 Sent To  
Notes
2015-05-18 15:51:045/18/2015
 PROJECT: INTERIOR
 PERMIT#: 14110576
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE RISER DIAGRAM INDICATES PANEL A AND B FED
 DIRECTLY FROM THE SAME METER WITHOUT ANY OVER CURRENT
 PROTECTION AND LANDING DIRECTLY INTO MAIN LUG ONLY
 PANELS. INDICATE THE REQUIRED DISCONNECTS FOR THE
 SERVICE EQUIPMENT. NEC 230.70
  
 2) THE LINE DIAGRAM IS NOT CLEAR AS TO HOW PANEL "A AND
 PANEL B ARE TO BE FED. THE RISER DIGRAM INDICATES BOTH
 PANELS FED FROM THE SAME METER. PROVIDE A SITE PLAN
 INDICATING THE LOCATION OF THE ELECTRICAL SERVICE FOR
 THE BUILDING. WPB AMENDMENTS TO THE FBC 107
  
 3) WHERE WALLS OR PARTITIONS ARE REQUIRED TO HAVE A
 FIRE-RESISTANCE RATING THE NEW RECEPTACLE OUTLETS SHALL
 BE PROTECTED IN COMPLIANCE WITH FBC 713.3.2.
  
 4) PROVIDE ADDITIONAL EMERGENCY ILLUMINATION AT THR
 EXIT DOORS AS REQUIRED FOR THE MEANS OF EGRESS. NEC
 700.16
  
 5) THE BRANCH CIRCUIT FEEDING THE EXIT AND EMERGENCY
 LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS THAT SERVING
 THE NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF
 ANY LOCAL SWITCHES. NEC 700.12
  
 6) INDICATE THE REQUIRED TIME CLOCKS FOR THE STORE
 FRONT SIGNS. FBC-E 505.2
  
 7) ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GROUND FAULT CIRCUIT INTERRUPTER PROTECTION. NEC 422.52
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-18 Cont ID  
Sent By dhayes Date 2014-12-18 Time 15:48 Rev Time 0.00
Received By dhayes Date 2014-12-18 Time 15:48 Sent To  
Notes
2014-12-18 16:41:2512/18/2014
 PROJECT: INTERIOR
 PERMIT#: 14110576
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE ADDITIONA INFORMATION TO CLARIFY NEW PANEL
 "B" ON THE "EXISTING FLOOR PLAN THERE IS NO PANEL "B"
 IN THE PROPOSED FLOOR PLAN THERE IS A PANEL "B" ON THE
 NEW RESTROOM PARTITION. THERE IS A RISER DIAGRAM SHOWN
 ON THE SAME PAGE BUT IT IS SHOWN AS EXISTING. PLEASE
 REVISE PLANS FOR CLARIFICATION.
  
 2) CLARIFY THE PURPOSE OF THE RECEPTACLE SYMBOL ABOOVE
 THE DOORS BY THE EXIT LIGHTS.
  
 3) MEMBRANE PENETRATIONS SHALL COMPLY WITH SECTION
 713.3.1. WHERE WALLS OR PARTITIONS ARE REQUIRED TO HAVE
 A FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE
 INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE WILL
 NOT BE REDUCED. FBC 713.3.2 MEMBRANE PENETRATIONS.
 REVISE THE PLANS FOR COMPLIANCE.
  
 4) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED
 MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND
 ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE
 REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL
 BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY
 INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF
 A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT
 REQUIRES EMERGENCY ILLUMINATION. NEC 700.16
  
 5) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT
 SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
 NEC 700.12
  
 6) REVISE THE FLOOR PLAN TO INDICATE ALL CIRCUIT
 NUMBERS AS THEY COINCIDE TO THE CIRCUIT DIRECTORY(S).
  
 7) ALL NEW RECEPTACLE OUTLETS SHALL BE TAMPER
 SESISTANT. NEC 406.11
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-11-17 Cont ID  
Sent By pleduc Date 2014-11-17 Time   Rev Time 0.00
Received By pleduc Date 2014-11-17 Time 13:47 Sent To  
Notes
2014-11-17 14:36:21THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS PERMITTED
 TO BE EQUIPPED WITH A KEYED LOCK WITH LOCK/UNLOCK
 INDICATOR WINDOW AND SIGNAGE STATING THE DOOR IS TO
 REMAIN UNLOCKED DURING BUSINESS HOURS. NO OTHER LOCKING
 OR LATCHING MECHANISMS ARE PERMITTED.
  
 THUMB-TURN LOCK TO BE EQUIPPED WITH AN ?OPEN/LOCKED?
 INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR).
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-30 Cont ID  
Sent By   Date 2015-05-30 Time   Rev Time 0.00
Received By   Date 2015-04-27 Time   Sent To  
Notes
2015-04-28 11:09:52B-05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-18 Cont ID  
Sent By dhayes Date 2014-12-18 Time 16:41 Rev Time 0.00
Received By dhayes Date 2014-11-14 Time 09:14 Sent To  
Notes
2014-11-15 09:15:48B15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-12-02 Cont ID  
Sent By jwitmer Date 2014-12-02 Time 14:20 Rev Time 0.00
Received By jwitmer Date 2014-12-02 Time 14:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date   Cont ID  
Sent By H.MOSER Date   Time   Rev Time 0.00
Received By skennedy Date 2015-04-27 Time 08:15 Sent To  
Notes
2015-05-15 08:29:13 
 2ND REVIEW: FBC 2010 MECHANICAL
 CHRISTOPHER COLE
  
 1) THE SUBMITTED AC PLAN NEEDS TO BE BE ENLARGED FOR
 CLARITY: THE NOTES AND DETAILS ARE NOT LEGIBLE- SECTION
 106.1.1 WPB AMENDMENTS TO THE FBC-10 BUILDING CODE.
 2) 2ND REQUEST FOR NEW RESTROOM EXHAUST DETAILS:
 EQUIPMENT SCHEDULE FOR FAN, EXHAUST DUCT SPECS, DUCT
 RUN AND TERMINATION LOCATION.
 3) 2ND REQUEST FOR ENERGY CALCULATIONS FOR THE TWO NEW
 TENANT SPACES- SEE SECTION 701.3 AND 711.1 FBC-10
 EXISTING BUILDING CODE; AND TABLE 101.4.1 FBC-10 ENERGY
 CONSERVATION.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-03 Cont ID  
Sent By rbergsma Date 2014-12-03 Time   Rev Time 0.50
Received By rbergsma Date 2014-12-03 Time   Sent To  
Notes
2014-12-03 14:10:39PROVIDE COMPLETE MECHANICAL PLANS TO INDICATE HVAC,
 BATH EXHAUST, OUTSIDE AIR MINIMUMS, EXPECTED OCCUPANT
 LOADS AND ENERGY CALC'S FOR NEW SPACES CREATED.
 UNTIL THIS INFORMATION IS SUBMITTED A COMPLETE REVIEW
 IS NOT POSSIBLE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-05-30 Cont ID  
Sent By TKLARGE Date 2015-05-30 Time 11:04 Rev Time 0.00
Received By tklarge Date 2015-05-30 Time 10:51 Sent To  
Notes
2015-05-30 11:04:161)SHOW THE DRINKING FOUNTAINS ON THE SANITARY RISER
 DIAGRAM ( BOTH OF THEM). WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 2) SHOW BOTH DRINKING FOUNTAINS ON THE WATER RISER
 DIAGRAM AND SIZE THE WATER RISER IN IT'S ENTIRETY. WPB
 AMEND. TO 2010 FBC SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-25 Cont ID  
Sent By tklarge Date 2014-11-25 Time 10:37 Rev Time 0.00
Received By tklarge Date 2014-11-25 Time 10:24 Sent To  
Notes
2014-11-25 10:37:291) A DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1 OF
 THE 2010 FPC. A MINIMUM OF TWO SHALL BE PROVIDED PER
 SEC.211.2 OF THE FL. ACCESSIBILITY CODE. THE DRINKING
 FOUNTAINS SHALL BE PRVIDED WITH CLEAR FLOOR SPACE AS
 REQUIRED BY SECS. 306 & 606.2 OF THE FL. ACCESSIBILITY
 CODE.
 2) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO 2010
 FBC SEC. 107.3.1.5.3.
 3) SHT. 2 NOTES THAT THE NEW SPACE WILL BE A MERCANTILE
 OCCUPANCY BUT THE FLOOR PLAN NOTES IT AS OFFICE SPACE.
 CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-12-01 Cont ID  
Sent By ajones Date 2014-12-01 Time 13:55 Rev Time 0.00
Received By ajones Date 2014-12-01 Time 13:55 Sent To  
Notes
***NONE***