Plan Review Details - Permit 14110537
Plan Review Stops For Permit 14110537
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-04-21 Cont ID  
Sent By skennedy Date 2015-04-21 Time 07:17 Rev Time 0.00
Received By skennedy Date 2015-04-21 Time 07:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-23 Cont ID  
Sent By skennedy Date 2014-11-23 Time 14:33 Rev Time 0.00
Received By skennedy Date 2014-11-23 Time 14:33 Sent To FIRE
Notes
2014-11-23 14:50:051ST REVIEW: FBC 2010
  
 THE SUBMITTAL DOES NOT PROVIDE INFORMATION NECESSARY TO
 DETERMINE COMPLIANCE WITH APPLICABLE CODES:
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 PROVIDE ATTACHMENT DETAILS OF GATES TO POST OR SHOP
 DRAWING FORM SUPPLIER REVIEWED BY ROBERT S MONSOUR, PE.
  
 PROVIDE LOCATION OF GATE OPERATOR. INDICATE HOW IT IS
 TO BE MOUNTED OR SECURED TO ITS LOCATION. THERE IS
 FOOTING DETAIL INCLUDED, BUT IT IS UNCLEAR WHAT IT IS
 FOR. THE FOOTING DETAIL IS FROM TEM SYSTEMS, INC. AND
 IT NOT ACKNOWLEGED AS DESIGNED OR REVIEWED BY A DESIGN
 PROFESSIONAL AND DOES NOT INCLUDE THE NAME OF THE
 DESIGNER.
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 PROVIDE AN ELECTRICAL DESIGN BY A QUALIFIED ELECTRICAL
 DESIGNER TO TO SHOW SOURCE OF POWER, CIRCUITS, WIRING
 METHOD, OCP & GFCI PROTECTION AT A MINIMUM. .
  
 FBC 107.3.5.3 ? PROVIDE A SITE PLAN TO DEMONSTRATE
 LOCATION OF PROPOSED INPROVEMENTS AND ASSOCIATED ACCESS
 DRIVES.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-05-02 Cont ID  
Sent By dhayes Date 2015-05-02 Time 12:44 Rev Time 0.00
Received By dhayes Date 2015-05-02 Time 12:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-03-25 Cont ID  
Sent By skennedy Date 2015-04-21 Time 07:18 Rev Time 0.00
Received By dhayes Date 2015-03-25 Time 11:27 Sent To FIRE
Notes
2015-03-25 12:30:20WPB AMENDMENTS. FBC 107.3.2
 PROVIDE ADDITIONAL INFORMATION FOR CLARIFICATION. THE
 ELECTRICAL PLAN PROVIDED IN THIS SUBMITTAL INDICATES
 ALL SWITCHGEAR AND BRANCH WIRING IS EXSITING. THERE IS
 NO INDICATION OF NEW WORK. PROVIDE AN ELECTRICAL PLAN
 THAT INDICATES HOW THE NEW GATE IS CONNECTED TO THE
 EXISTING WIRING SYSTEM. INCLUDE CONDUIT AND WIRING
 TYPES AND SIZES.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-11-23 Cont ID  
Sent By skennedy Date 2014-11-23 Time 14:50 Rev Time 0.00
Received By skennedy Date 2014-11-23 Time 14:50 Sent To  
Notes
2014-11-23 14:50:53SEE BUILDING PLAN REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-03-26 Cont ID  
Sent By pleduc Date 2015-03-26 Time   Rev Time 0.00
Received By pleduc Date 2015-03-26 Time 14:36 Sent To Z
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-11-24 Cont ID  
Sent By pleduc Date 2014-11-24 Time   Rev Time 0.00
Received By pleduc Date 2014-11-24 Time 12:12 Sent To PC
Notes
2014-11-24 12:17:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE ADDRESS BUILDING COMMENTS.
  
 PLEASE PROVIDE A NOTE ON THE NEWLY SUBMITTED PLAN THAT
 INDICATES A KNOX KEY SWITCH SYSTEM SHALL BE INSTALLED
 TO ENSURE 24 HOUR EMERGENCY ACCESS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-02 Cont ID  
Sent By dhayes Date 2015-05-02 Time 12:44 Rev Time 0.00
Received By dhayes Date 2015-04-30 Time 15:54 Sent To  
Notes
2015-04-30 15:55:04TO DAH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-21 Cont ID  
Sent By dhayes Date 2015-04-21 Time 07:18 Rev Time 0.00
Received By skennedy Date 2015-03-25 Time 11:27 Sent To E
Notes
2015-04-06 16:25:21TO SAK DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-24 Cont ID  
Sent By pleduc Date 2014-11-24 Time   Rev Time 0.00
Received By pleduc Date 2014-11-13 Time 14:21 Sent To  
Notes
2014-11-13 14:21:18ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2015-03-27 Cont ID  
Sent By sgraham Date 2015-03-27 Time 14:02 Rev Time 0.00
Received By sgraham Date 2015-03-27 Time 14:02 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-11-18 Cont ID  
Sent By sgraham Date 2014-11-18 Time 10:07 Rev Time 0.00
Received By sgraham Date 2014-11-18 Time 10:07 Sent To  
Notes
2014-11-18 10:12:0711/18/14 ZONING FAILED
  
 1. PROVIDE A SITE PLAN SHOWING THE LOCATION ON THE NEW
 GATES AND EXISTING BARRIER GATES