| 2014-11-14 13:33:26 | 1801 PALM BEACH LAKES BOULEVARD |
| | PERMIT #14110536 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | OPEN-AIR MERCANTILE OPERATIONS: PER NFPA 101 SECTION |
| | 36.4.3.3, MERCANTILE OPERATIONS THAT ARE CONDUCTED IN |
| | ROOFED-OVER AREAS SHALL BE TREATED AS MERCANTILE |
| | BUILDINGS, PROVIDED THAT CANOPIES OVER INDIVIDUAL SMALL |
| | STANDS TO PROTECT MERCHANDISE FROM THE WEATHER ARE NOT |
| | CONSTRUED AS CONSTITUTING BUILDINGS FOR THE PURPOSE OF |
| | THIS CODE. THE INTENT OF 36/37.4.3.3 IS TO EXEMPT SMALL |
| | MERCHANDISE STANDS WITH CANOPIES FROM CLASSIFICATION AS |
| | MERCANTILE BUILDINGS. ALL OTHER ROOFED-OVER AREAS |
| | SHOULD BE TREATED AS BUILDINGS CLASSIFIED BY AREA AND |
| | HEIGHT AS CLASS A, CLASS B, OR CLASS C MERCANTILE |
| | OCCUPANCIES AND ARE SUBJECT TO THE APPROPRIATE |
| | PROVISIONS OF CHAPTERS 36 AND 37 OF THE LIFE SAFETY |
| | CODE. |
| | |
| | CLASS B MERCANTILE (+3,000 SQ.FT.) SHALL BE PROVIDED |
| | WITH ILLUMINATED EXIT AISLES, EMERGENCY LIGHTING (SUCH |
| | AS BATTERY BACK-UP OR GENERATOR) AND ILLUMINATED EXIT |
| | SIGNS. |
| | |
| | AISLES OF 36-INCHES IN CLEAR, UNOBSTRUCTED WIDTH SHALL |
| | BE ESTABLISHED AND MAINTAINED AT ALL TIMES. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | POST WEATHERPROOF "NO SMOKING" SIGNS IN CONSPICUOUS |
| | LOCATIONS. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |