Plan Review Details - Permit 14110508
Plan Review Stops For Permit 14110508
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-11-26 Cont ID  
Sent By jwitmer Date 2014-11-26 Time 16:32 Rev Time 0.00
Received By jwitmer Date 2014-11-26 Time 16:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-12-19 Cont ID  
Sent By dhayes Date 2014-12-19 Time 10:57 Rev Time 0.00
Received By dhayes Date 2014-12-19 Time 10:57 Sent To  
Notes
2014-12-18 13:23:41NEW DRAWING SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-11-14 Cont ID  
Sent By dhayes Date 2014-11-14 Time 10:34 Rev Time 0.00
Received By dhayes Date 2014-11-14 Time 10:34 Sent To  
Notes
2014-11-14 10:55:4611/14/2014
 PROJECT: NAIL SALON
 PERMIT#: 14110508
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) VERIFY THE INSTALLATION OF NEW OUTLET IN EXISTING
 FIREWALLS ARE INSTALLED SUCH THAT THE REQUIRED
 FIRE-RESISTANCE WILL NOT BE REDUCED. FBC 713.3.1
  
 2) VERIFY BRANCH CIRCUIT FEEDING EMERGENCY AND EXIT
 LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS THAT SERVING
 THE NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF
 ANY LOCAL SWITCHES. NEC 700.12(F)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-11-17 Cont ID  
Sent By pleduc Date 2014-11-17 Time   Rev Time 0.00
Received By pleduc Date 2014-11-17 Time 13:49 Sent To  
Notes
2014-11-17 14:00:59THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 ADD 2 ADDITIONAL EMERGENCY LIGHTS, 1 IN THE FRONT AND 1
 IN THE BACK, ALONG THE EXIT TRAVEL PATH.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-02-09 Cont ID  
Sent By hmoser Date 2015-02-09 Time 14:36 Rev Time 0.00
Received By hmoser Date 2015-01-28 Time 15:58 Sent To  
Notes
2015-01-28 16:09:06B26
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-28 Cont ID  
Sent By skennedy Date 2014-12-28 Time 11:26 Rev Time 0.00
Received By skennedy Date 2014-12-18 Time 13:23 Sent To  
Notes
2014-12-18 13:24:14RE-SUBMITTAL SENT TO B9 BIN FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-02 Cont ID  
Sent By skennedy Date 2014-12-02 Time 17:26 Rev Time 0.00
Received By skennedy Date 2014-11-13 Time 10:34 Sent To  
Notes
2014-11-14 11:00:02B26

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-02-09 Cont ID  
Sent By hmoser Date 2015-02-09 Time 14:36 Rev Time 0.00
Received By hmoser Date 2015-02-09 Time 12:54 Sent To  
Notes
2015-02-09 14:36:02PASS PROVISO
 1) REFER TO SECTION 501.2.1 LOCATION OF EXHAUST OUTLETS
 2010 FBC (M)
 2) REFER TO SECTION 503.2.4.40SHUTOFF DAMPER CONTROLS.
 2010 FLORIDA ENERGY CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-12-28 Cont ID  
Sent By skennedy Date 2014-12-28 Time 11:25 Rev Time 0.00
Received By skennedy Date 2014-12-28 Time 11:25 Sent To  
Notes
2014-12-28 11:26:23SECOND REVIEW FBC 2010
  
 THE COMMENTS FROM THE FIRST REVIEW WERE APPARENTLY NOT
 ADDRESSED. SEE BELOW.
  
 PLEASE PROVIDE A SYSTEM THAT CAPTURES THE CONTAMINANTS
 (PRODUCTS) AND ODORS AT THEIR SOURCE, MANICURE TABLES
 AS PER THE FLORIDA MECHANICAL CODE BELOW
  
 403.3 OUTDOOR AIRFLOW RATE.
 TABLE 403.3?CONTINUED
 MINIMUM VENTILATION RATES
  
  
 H. FOR NAIL SALONS, THE REQUIRED EXHAUST SHALL INCLUDE
 VENTILATION TABLES OR OTHER SYSTEMS THAT CAPTURE THE
 CONTAMINANTS AND ODORS AT THEIR SOURCE AND ARE CAPABLE
 OF EXHAUSTING A MINIMUM OF 50 CFM PER STATION.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-02 Cont ID  
Sent By rbergsma Date 2014-12-02 Time   Rev Time 1.00
Received By rbergsma Date 2014-12-02 Time   Sent To  
Notes
2014-12-02 10:30:37PLEASE PROVIDE A SYSTEM THAT CAPTURES THE CONTAMINANTS
 (PRODUCTS) AND ODORS AT THEIR SOURCE, MANICURE TABLES
 AS PER THE FLORIDA MECHANICAL CODE BELOW
  
 403.3 OUTDOOR AIRFLOW RATE.
 TABLE 403.3?CONTINUED
 MINIMUM VENTILATION RATES
  
  
 H. FOR NAIL SALONS, THE REQUIRED EXHAUST SHALL INCLUDE
 VENTILATION TABLES OR OTHER SYSTEMS THAT CAPTURE THE
 CONTAMINANTS AND ODORS AT THEIR SOURCE AND ARE CAPABLE
 OF EXHAUSTING A MINIMUM OF 50 CFM PER STATION.
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-01-30 Cont ID  
Sent By tklarge Date 2015-01-30 Time 13:03 Rev Time 0.00
Received By tklarge Date 2015-01-30 Time 12:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-12-22 Cont ID  
Sent By tklarge Date 2014-12-22 Time 06:31 Rev Time 0.00
Received By tklarge Date 2014-12-22 Time 06:06 Sent To  
Notes
2014-12-22 06:06:181) THE DRINKING FOUNTAIN SHALL HAVE A 30' WIDE BY 48'
 CLEAR FLOOR SPACE CENTERED ON THE UNIT TO ALLOW FOR A
 FORWARD APPROACH PER THE 2010 FL. ACCESS. CODE
 SEC.602.2. A TURNING DIAMETER DOES NOT COMPLY.
 2) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS/
 INSTALLATION MANUALS FOR THE PEDICURE CHAIRS. 2ND
 REQUEST. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 3) PROVISIONS FOR THERMAL EXPANSION SHALL BE INSTALLED
 ON THE HOT WATER SYSTEM PER THE 2010 FL. PLBG. CODE
 SEC.607.3.
 4) WHERE ARE SHEETS A-1 & A-2? SUBMIT 2 COMPLETE SETS
 OF PLANS WITH ALL THE SHEETS.WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 5) SHT. P-1 - THE REFERENCE TO SEPARATE FACILITIES NOT
 BEING REQUIRED FOR ESTABLISHMENTS THAT SEAT 10 PERSONS
 OR LESS APPLIES TO FOOD SERVICE ESTABLISHMENTS, NOT
 BUSINESS OCCUPANCIES. THE CORRECT EXCEPTION IS SEC.
 403.2 (3) OF THE 2010 FL. PLUMBING CODE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-25 Cont ID  
Sent By tklarge Date 2014-11-25 Time 09:23 Rev Time 0.00
Received By jwitmer Date 2014-11-26 Time 16:26 Sent To  
Notes
2014-11-25 09:23:20WPB ADMIN. AMEND. TO 201 FBC SEC. 107.2.1.
 1) SUBMIT MANUFACTURER'S SPEC SHEETS / INSTALLATION
 INSTRUCTIONS FOR THE PEDICURE CHAIRS.
 2) A NOTE ON THE PLANS STATES THAT THIS IS A CHANGE IN
 USE. INDICATE THE PREVIOUS USE ON THE PLAN. IF THIS IS
 A CHANGE IN OCCUPANCY THE WORK SHALL COMPLY WITH
 CHAPTER 9 OF THE FL. EXISTING BUILDING CODE.
 3) A DRINKING FOUNTAIN IS REQUIRED. NO FEWER THAN TWO
 DRINKING FOUNTAINS SHALL BE PROVIDED PER THE 2010 FAC
 SEC. 211.2.
 4) THE NEW DRINKING FOUNTAINS SHALL BE SHOWN ON THE
 SANITARY AND WATER RISERS.
 5) THE DRINKING FOUNTAINS SHALL BE PROVIDED WITH CLEAR
 FLOOR SPACE COMPLYING WITH THE 2010 FL. ACCESSIBILITY
 CODE SECS.306 & 602.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  