Plan Review Details - Permit 14110440
Plan Review Stops For Permit 14110440
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-01-16 Cont ID  
Sent By jwitmer Date 2015-01-16 Time 11:27 Rev Time 0.00
Received By jwitmer Date 2015-01-15 Time 11:19 Sent To  
Notes
2015-01-16 11:27:05BUILDING PLAN REVIEW
 PERMIT: 14110440
 ADD: 4115 GEORGIA AVE
 CONT: T D GONE BUILDING
 TEL: (561)436-4047
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JAN. 16/ 2015
 ACTION: BUILDING PROVISO
  
 1) THE DESIGNER OF RECORD PREFERS TO SUBMIT THE PRODUCT
 APPROVALS FOR WINDOWS AND DOOR AS A DEFERRED SUBMITTAL.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE
 BEEN APPROVED BY THE BUILDING OFFICIAL.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, SWING DOORS & OVERHEAD DOORS.
 (B) WINDOWS & MULLIONS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-02 Cont ID  
Sent By jwitmer Date 2014-12-02 Time 15:00 Rev Time 0.00
Received By jwitmer Date 2014-12-02 Time 14:26 Sent To  
Notes
2014-12-02 15:00:06BUILDING PLAN REVIEW
 PERMIT: 14110440
 ADD: 4115 GEORGIA AVE
 CONT: T D GONE BUILDING
 TEL: (561)436-4047
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 02/ 2014
 ACTION: DENIED
  
 1) SHEET A1 OF 3 SHOWS DOOR # 5 AS A 1 HOUR FIRE RATED
 DOOR SEE DOOR SCHEDULE A2. THE WALL SEPARATING THE
 MERCANTILE FROM THE STORAGE OCCUPANCY DOES NOT INDICATE
 IF A S1 OR S2, DEPENDING ON THE OCCUPANCY THE WALL
 BETWEEN THE 2 OCCUPANCIES MAY OR MAY NOT REQUIRE FIRE
 RATING, SEE FBC-B TABLE 508.4.
  
 2) SHEET A1 OF 3 INDICATES THE INSTALATION OF NEW
 EXTERIOR WINDOWS AND DOORS, PLEASE SHOW COMPLIANCE WITH
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 2.THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-102010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING
  
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 2.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 3) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-01-31 Cont ID  
Sent By dhayes Date 2015-01-31 Time 14:35 Rev Time 0.00
Received By dhayes Date 2015-01-31 Time 14:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-31 Cont ID  
Sent By dhayes Date 2014-12-31 Time 11:28 Rev Time 0.00
Received By dhayes Date 2014-12-31 Time 08:38 Sent To  
Notes
2014-12-31 11:59:3212/31/2014
 PROJECT: GLUE PRODUCTS
 PERMIT#: 14110440
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE THE CIRCUITRY ON THE FLOOR PLAN TO COINCIDE
 WITH THE REQUIRED PANEL SCHEDULE AS WELL AS A RISER
 DIAGRAM AND LOAD CALCULATION. WPB AMENDMENTS ? FBC
 107.3.5.1.2 ELECTRICAL
  
 2) PROVIDE COMPLETE CIRCUIT DIRECTORIES FOR ELECTRICAL
 PANELS. EVERY CIRCUIT SHALL BE LEGIBLY IDENTIFIED AS TO
 ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC
 408.4
  
 3) DRINKING FOUNTAIN REQUIRES A GFI PROTECTED
 RECEPTACLE OUTLET. NEC 422.52
  
 4) INDICATE THE REQUIRED LIGHTING CONTROLS FOR INTERIOR
 AND EXTERIOR ILLUMINATION. LIGHTING SYSTEMS SHALL BE
 PROVIDED WITH CONTROLS AS REQUIRED IN SECTIONS 505.2.1,
 505.2.2, 505.2.3 AND 505.2.4. FBC 505.2 LIGHTING
 CONTROLS (MANDATORY).
  
 5) INDICATE THE REQUIRED LIGHTING ABOUT ELECTRICAL
 EQUIPMENT. ILLUMINATION SHALL BE PROVIDED FOR ALL
 WORKING SPACES ABOUT ELECTRICAL PANELS AND EQUIPMENT.
 NEC 110.34 (D)
  
 6) INDICATE THE REQUIRED WORKING CLEARANCE ABOUT
 ELECTRICAL EQUIPMENT. SUFFICIENT ACCESS AND WORKING
 SPACE SHALL BE PROVIDED AND MAINTAINED ABOUT ALL
 ELECTRICAL EQUIPMENT TO PERMIT READY AND SAFE OPERATION
 AND MAINTENANCE OF SUCH EQUIPMENT. NEC 110.26
  
 7) VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 8) INDICATE ALL REQUIRED EMERGENCY ILLUMINATION.
 EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED MEANS
 OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND ALL
 OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE REQUIRED
 ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL BE
 DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY
 INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF
 A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT
 REQUIRES EMERGENCY ILLUMINATION. NEC 700.16
  
 9) PROVIDE THE LOCATION OF ALL MECHANICAL EQUIPMENT
 WITH ASSOCIATED REQUIRED DISCONNECTS AND GFI OUTLETS.
 NEC 210.63, 210.8(A)(3), NEC 440.14
  
 10) INDICATE PROVISIONS FOR THE REQUIRED SIGN CIRCUIT
 AND SHOW WINDOW LIGHTING. NEC 210.62, 600.5(A)
  
 11) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD
 EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY,
 CCTV, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-02-26 Cont ID  
Sent By cranford Date 2015-02-26 Time 11:23 Rev Time 0.00
Received By cranford Date 2015-02-26 Time 11:03 Sent To  
Notes
2015-02-26 11:22:54ALSO APPROVED UNDER ENGINEERING DEVELOPMENT APPLICATION
 E14120034

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-02-13 Cont ID  
Sent By cranford Date 2015-02-13 Time 07:23 Rev Time 0.00
Received By cranford Date 2015-02-12 Time 15:25 Sent To  
Notes
2015-02-13 07:14:35ALSO BEING REVIEWED UNDER ENGINEERING APPLICATION
 E14120034

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-01-13 Cont ID  
Sent By pleduc Date 2015-01-13 Time   Rev Time 0.00
Received By pleduc Date 2015-01-12 Time 16:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-11-18 Cont ID  
Sent By pleduc Date 2014-11-18 Time   Rev Time 0.00
Received By pleduc Date 2014-11-14 Time 12:11 Sent To  
Notes
2014-11-18 09:18:15THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PLAN SHEETS PACKETS WERE INCONSISTENT.
  
 PLEASE PROVIDE THE OCCUPANY CLASSIFICATION. IT APPEARS
 THAT IT IS OF MISED USE.
  
 THE FIRE LINE MAY NEED TO BE APPLIED FOR UNDER A
 SEPARATE PERMIT, PLEASE CONFIRM WITH CONSTRUCTION
 SERVICES.
  
 A LIFE SAFETY PLAN WAS NOT SUBMITTED THAT INCLUDES ALL
 OCCUPANCY LOADS, EXIT PATHS, COOMON PATHS OF TRAVEL,
 EMERGECNY LIGHTS, EXIT SIGNS AND EXITS. ALL EXITS MUST
 LEAD TO A PUBLIC WAY. EXITING INTO A LOCKED SECURED
 PARKING LOT IS NOT A PUBLIC WAY.
  
 A FIRE SPRINKLER PLAN WAS NOT PROVIDED, AN ENGINEERED
 CONCEPTUAL PLAN SHALL BE PROVIDED THAT INCLUDES ALL
 COMMODITIES, STORGAE AND RACK PROTECTION.
  
 A FIRE ALARM WAS NOT PROVIDED, AND ENGINEERED
 CONCEPTUAL PLAN SHALL BE PROVIDED. THE FIRE ALARM
 SYSTEM SHALL BE MONITORED.
  
 A KNOX LOCK KEY SYSTEM, INCLUDING A KNOX BOX AND KNOX
 GATE ACCESS, SHALL BE PROVIDED FOR 24 HOUR EMERGENCY
 ACCESS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-02-26 Cont ID  
Sent By cranford Date 2015-02-26 Time 11:26 Rev Time 0.00
Received By cranford Date 2015-02-13 Time   Sent To  
Notes
2015-02-18 08:36:14TO ZONING BOX.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-13 Cont ID  
Sent By cranford Date 2015-02-13 Time 07:25 Rev Time 0.00
Received By cranford Date 2015-01-09 Time 09:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-31 Cont ID  
Sent By dhayes Date 2014-12-31 Time 12:02 Rev Time 0.00
Received By dhayes Date 2014-11-12 Time 10:51 Sent To  
Notes
2014-11-13 10:52:17SENT TO C14 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-12-02 Cont ID  
Sent By jwitmer Date 2014-12-02 Time 14:30 Rev Time 0.00
Received By jwitmer Date 2014-12-02 Time 14:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-01-17 Cont ID  
Sent By tklarge Date 2015-01-17 Time 08:53 Rev Time 0.00
Received By tklarge Date 2015-01-17 Time 08:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-24 Cont ID  
Sent By tklarge Date 2014-11-24 Time 14:07 Rev Time 0.00
Received By tklarge Date 2014-11-24 Time 11:58 Sent To  
Notes
2014-11-24 13:22:171) SHT. A-1 - THE TOILET PAPER DISPENSER SHALL BE
 LOCATED 7" MIN. AND 9 IN. MAXIMUM IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER.
 SHOW ON THE PLANS.2010 FL. ACCESS. CODE SEC. 604.7.
 2) SHT. A-1 - THE SEAT HEIGHT OF A WATER CLOSET ABOVE
 THE FINISH FLOOR SHALL BE 17"-19" MAX. SHOW ON THE
 PLANS.FAC SEC.604.4
 3) GRAB BAR BEHIND WATER CLOSET SHALL BE MOUNTED AT
 33"- 36" ABOVE THE FINISH FLOOR PER FAC SEC.609.4. SHOW
 ON PLANS.
 4) SHOW THE CLEAR FLOOR SPACE FOR THE DRINKING
 FOUNTAINS ON THE PLANS.THE CLEAR FLOOR SPACE SHALL BE
 CENTERED ON THE INDIVIDUAL FIXTURE AND NOT BOTH
 FIXTURES. THE CLEAR FLOOR SPACE SHALL BE POSITIONED FOR
 A FORWARD APPROACH.FAC SEC.602.2.
 5) THE DRINKING FOUNTAINS REQUIRE VENTS PER FPC
 SEC,901.201.
 6) FLOOR DRAINS REQUIRE TRAP PRIMERS PER THE 2010 FPC.
 1002.4.
 7) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS.
 PER THE 2010 FPC SEC. 708.3.4.
 8)THE WASTE STACKS FOR THE LAVS ARE SHOWN AS 1 1/2 INCH
 UNDERGROUND AND 2" THROUGH THE ROOF, CLARIFY.
 9) A CLEANOUT IS REQUIRED WHERE THE BUILDING DRAIN
 MEETS THE BUILDING SEWER PER THE 708.3.5.
 10) SHT.A-3 - AS DRAWN, THE DRINKING FOUNTAINS ARE
 DISCHARGING INTO A HORIZONTAL WET VENT WHICH IS NOT
 PERMITTED PER SEC.909.1 OF THE FPC.
 11) SHT. A-3 - A 1 1/2 WET VENT CAN ONLY CARRY ONE
 DRAINAGE FIXTURE UNIT.AS DRAWN THERE ARE TWO FIXTURE
 UNITS ON THE 1 1/2" WET VENT AT THE WOMEN'S RESTROOM.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-02-18 Cont ID  
Sent By dkittred Date 2015-02-18 Time 16:25 Rev Time 0.00
Received By dkittred Date 2015-02-18 Time 10:34 Sent To ENG
Notes
2015-02-18 16:25:032/18/15 - ADDITIONAL NOTATIONS ADDED TO PLAN REGARDING
 LANDSCAPE PLANTINGS. DK

Review Stop Z ZONING
Rev No 2 Status F Date 2015-01-20 Cont ID  
Sent By dkittred Date 2015-01-20 Time 10:22 Rev Time 0.00
Received By dkittred Date 2015-01-20 Time 08:25 Sent To  
Notes
2015-01-20 10:22:15PLANNING AND ZONING COMMENTS: ***FAILED***
  
 1/20/15
  
 1. PLANNING COMMENTS WERE ADDRESSED ON THE COMMENT
 SHEET PROVIDED WITH RESUBMITAL, HOWEVER, THERE WERE NO
 REVISIONS TO THE PLANS INCLUDED. (REF. ORIGINAL
 COMMENTS FROM 11/19/2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-11-19 Cont ID  
Sent By dkittrid Date 2014-11-19 Time 09:39 Rev Time 0.00
Received By dkittred Date 2014-11-18 Time 15:33 Sent To  
Notes
2014-11-19 09:39:48PLANNING AND ZONING COMMENTS: ***FAILED***
  
 11/19/14
  
 1. IT APPEARS THAT ALL VEGETATION IN THE 4 FOOT
 LANDSCAPE AREA ON THE EAST SIDE OF THE BUILDING IS
 GOING TO NEED TO BE REMOVED FOR INSTALLATION OF WATER
 SERVICE CONNECTION AND ASSOCIATED ASSEMBLIES. PLAN WILL
 NEED TO INDICATE SCREENING THE BACKFLOW PREVENTER AND
 OTHER VERTICAL COMPONENTS. IT IS RECOMMENDED TO EXPAND
 THE LANDSCAPE AREA TO THE SOUTH TO BE ABLE TO INSTALL A
 VEGETATIVE BUFFER FOR SCREENING OF THE EQUIPMENT.
 PLEASE INDICATE ON THE SITE PLAN IF LANDSCAPING WILL
 NEED TO BE REMOVED AND HOW THE EQUIPMENT WILL BE
 SCREENED.
  
 2. A WHEEL STOP WILL NEED TO BE PROVIDED ON THE SECOND
 TO LAST PARKING SPACE ON THE WEST SIDE OF THE PROPERTY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2014-11-14 12:14:3811/14/14