Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-05 Cont ID  
Sent By shill Date 2014-12-05 Time 06:43 Rev Time 0.00
Received By jwitmer Date 2014-12-04 Time 16:44 Sent To  
Notes
2014-12-05 06:08:12BUILDING PLAN REVIEW
 PERMIT:14110435/ 11090826/ RE-ISSUE
 ADD: 14110435
 CONT: EVANS PETRLEUM SERVICES
 TEL: (305) 796-9695
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. DEC. 04/ 2014
 ACTION: DENIED
  
 1A) THE CANOPY STRUCTURAL CALCULATIONS SUBMITTED BY
 UNIVERSAL STRUCTURES JOB NUMBER: 11-4173 DATE SEPT
 19/2011 AND REVISION DATED JAN. 23/2012
 BOTH HAVE THE WRONG ADDRESS ON THEM, THE ADDRESS OF
 1258 PALM BEACH LAKES BLVD. IS A PROPERTY TO THE EAST
 WITH ACTIVE PERMITS AND OCCUPANCY. PLEASE CORRECT THE
 ADDRESS TO THE CORRECT PROPERTY WHERE THE PERMIT AND
 WORK IS OCCURRING.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. L. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED.
 2010 FBC-B [F] 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS.
  
 1B) THE SUBMITTED PLANS DOES NOT INCLUDE THE CANOPY
 FOUNDATION PLANS, CANOPY FRAMING AND ELEVATION PLANS
 NOR THE SECTION AND DETAIL PLANS. THIS WAS A REVISION
 SUBMITTED LATER ON. PLEASE SUBMIT THE PLANS SUBMITTED
 UNDER REVISION NUMBER: 12010568, NOTE THE CANOPY PLANS
 ALSO HAVE THE WRONG ADDRESS OF 1258 PALM BEACH LAKES
 BLVD. PLEASE SUBMIT THESE PLANS WITH THE CORRECTED
 ADDRESS OF 1270 PALM BEACH LAKES BLVD. SO THE PERMIT
 PACKAGE WOULD BE COMPLETE.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. L. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED.
 2010 FBC-B [F] 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS.
  
  
 12/11/14 UPDATE, IN REVIEWING FILE NET FOR IMPACT FEE
 PAYMENT UNDER THE EXPIRED PERMIT11090826 THERE ARE
 REVISIONS STATING THE REMOVAL OF THE GAS PUMP CANOPY
 FROM THE SCOPE OF WORK UNDER THIS PERMIT. THIS
 STATEMENT DOES NOT EXIST UNDER THE NEW RE-ISSUE SET OF
 PLANS!!!!!!!
  
  
 2) THIS PERMIT PACKAGE DOES NOT SHOW ANY UNDERGROUND
 INVESTIGATING SOILS REPORTS. UNDER THE ORIGINAL PERMIT
 THE REVIEWER ASKED FOR THIS REPORT REPEATEDLY.
 CONTRACTOR IS CONTINUING WORK AT THEIR OWN RISK!!!!!!!!
 2010 FBC-B 1803.5.2 QUESTIONABLE SOILS.
  
 3) UNDER THE ORIGINAL PERMIT PACKAGE THERE WERE SOIL
 DENSITIES TAKEN THAT ARE ALSO MISSING FROM THIS PERMIT
 PACKAGE SINCE THERE WAS FILL BROUGHT IN, THEY WERE
 NEVER REVIEWED ON THE JOBSITE BY THE INSPECTOR, THEY
 PROVISOD AT OWN RISK. PLEASE SUBMIT THESE DOCUMENTS SO
 THEY CAN ALSO BE PART OF THIS PERMIT PACKAGE.
 2010 FBC-B 1803.5.8 COMPACTED FILL MATERIAL. WHERE
 SHALLOW FOUNDATIONS WILL BEAR ON COMPACTED FILL
 MATERIAL MORE THAN 12 INCHES (305 MM) IN DEPTH, A
 GEOTECHNICAL INVESTIGATION SHALL BE CONDUCTED AND SHALL
 INCLUDE ALL OF THE FOLLOWING: (5.) FIELD TEST METHOD
 FOR DETERMINING THE IN-PLACE DRY DENSITY OF THE
 COMPACTED FILL.
  
 4) THIS PERMIT PACKAGE IS ALSO MISSING THE ROOFING
 PRODUCT APPROVALS:
 2010 FBC-B 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
 NOTE: THE ROOFING PRODUCT APPROVALS WERE SUBMITTED
 UNDER 12030576 PLEASE SUBMIT ROOFING PRODUCT APPROVALS,
 IF ENGINEERED FASTENING IS REQUIRED IN ROOF ZONES 2 & 3
 ALSO SUBMIT ENGINEERED CALCULATIONS TO RAS 117.
  
 5) PLEASE PROVIDE DOCUMENTATION THAT UNDER PERMIT #
 11090320 THAT PALM BEACH COUNTY IMPACT FEE OFFICE HAS
 REVIEWED AND STAMPED THE PLANS, THERE IS NO SUCH STAMP
 ON THESE PLANS. IF A BUILDING WAS DEMOLISHED ON THE
 SAME SITE SEE IF THERE IS EXISTING USE CREDITS THAT CAN
 BE TAKEN, THE PLANS WILL STILL REQUIRE P B C IMPACT FEE
 ASSESSMENT.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-01-06 Cont ID  
Sent By dhayes Date 2015-01-06 Time 09:10 Rev Time 0.00
Received By dhayes Date 2015-01-06 Time 08:41 Sent To  
Notes
2015-01-06 09:08:5101/06/2015
 PROJECT: VALERO STATION
 PERMIT#: 14110435
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW RE-ISSUE OF 11090826
 ACTION: APPROVED WITH EXCEPTION
  
 ADDRESS THE FOLLOWING PRIOR TO FINAL INSPECTIONS.
  
 1) REVISE THE SIZE OF THE FUSE SIZE MAIN AND CORRECT
 THE AIC RATING INDICATED IN THE SERVICE SUMMARY ON
 SHHET E-5. THE LOAD CALCULATION AND RISER DIAGRAM ARE
 CONFLICTING. THE TOTAL CALCULATED LOAD IS INDICATED AS
 439AMPS WITH A 600AMP 65K AIC RATED MAIN BREAKER SHOWN
 ON THE RISER DIAGRAM. REVISE THE NOTE THAT CALLS FOR A
 200AMP MAIN FUSE AND 10K AIC RATING. NEC 230.79.
  
 2)FL SS 526.143(2)
 A.) INDICATE METHOD OF COMPLIANCE WITH FL SS THAT
 REQUIRE EACH NEWLY CONSTRUCTED OR SUBSTANTIALLY
 RENOVATED MOTOR FUEL RETAIL OUTLET BE PREWIRED WITH AN
 APPROPRIATE TRANSFER SWITCH, AND CAPABLE OF OPERATING
 ALL FUEL PUMPS, DISPENSING EQUIPMENT, LIFESAFETY
 SYSTEMS, AND PAYMENT-ACCEPTANCE EQUIPMENT USING AN
 ALTERNATE GENERATED POWER SOURCE. INDICATE THE LOCATION
 AND TYPE OF ALTERNATE GENERATED POWER SOURCE PROPOSED.
 B.) NEC 702. PROVIDE SIGNAGE AND INDICATE LOCATION ON
 THE PLANS FOR SIGNAGE AS REQUIRED BY NEC 702.8
  
 3) FBC-E 505.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND
 505.2.4. REVISE PLANS TO COMPLY WITH THE FBC -ENERGY,
 SECTIONS NOTED FOR CONTROL OF INTERIOR AND EXTERIOR
 LIGHTING.
  
 4) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATORS. FUEL,
 CANOPY, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY,
 CCTV, NETWORK, DATA, AND, COMMUNICATION.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-15 Cont ID  
Sent By dhayes Date 2014-12-15 Time 09:08 Rev Time 0.00
Received By dhayes Date 2014-12-15 Time 08:46 Sent To  
Notes
2014-12-15 10:21:5412/15/2014
 PROJECT: VALERO STATION
 PERMIT#: 14110435
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW RE-ISSUE OF 11090826
 ACTION: APPROVED WITH EXCEPTION
  
 ADDRESS THE FOLLOWING PRIOR
 1) REVISE THE SIZE OF THE FUSE SIZE MAIN AND CORRECT
 THE AIC RATING INDICATED IN THE SERVICE SUMMARY ON
 SHHET E-5. THE LOAD CALCULATION AND RISER DIAGRAM ARE
 CONFLICTING. THE TOTAL CALCULATED LOAD IS INDICATED AS
 439AMPS WITH A 600AMP 65K AIC RATED MAIN BREAKER SHOWN
 ON THE RISER DIAGRAM. REVISE THE NOTE THAT CALLS FOR A
 200AMP MAIN FUSE AND 10K AIC RATING. NEC 230.79.
  
 2) FL SS 526.143(2)
 A.) INDICATE MEATHOD OF COMPLIANCE WITH FL SS THAT
 REQUIRE EACH NEWLY CONSTRUCTED OR SUBSTANTIALLY
 RENOVATED MOTOR FUEL RETAIL OUTLET BE PREWIRED WITH AN
 APPROPRIATE TRANSFER SWITCH, AND CAPABLE OF OPERATING
 ALL FUEL PUMPS, DISPENSING EQUIPMENT, LIFESAFETY
 SYSTEMS, AND PAYMENT-ACCEPTANCE EQUIPMENT USING AN
 ALTERNATE GENERATED POWER SOURCE. INDICATE THE LOCATION
 AND TYPE OF ALTERNATE GENERATED POWER SOURCE PROPOSED.
 B.) NEC 702. PROVIDE SIGNAGE AND INDICATE LOCATION ON
 THE PLANS FOR SIGNAGE AS REQUIRED BY NEC 702.8
  
 3) FBC-E 505.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND
 505.2.4. REVISE PLANS TO COMPLY WITH THE FBC -ENERGY,
 SECTIONS NOTED FOR CONTROL OF INTERIOR AND EXTERIOR
 LIGHTING. FBC-E 505.2
  
 4) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATORS. FUEL,
 CANOPY, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY,
 CCTV, NETWORK, DATA, AND, COMMUNICATION.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2014-12-31 Cont ID  
Sent By cranford Date 2014-12-31 Time 14:28 Rev Time 0.00
Received By cranford Date 2014-12-31 Time 11:55 Sent To E
Notes
2014-12-31 14:27:22ALSO REVIEWED UNDER E11110018

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2014-11-26 Cont ID  
Sent By cranford Date 2014-11-26 Time 13:33 Rev Time 0.00
Received By cranford Date 2014-11-26 Time 13:30 Sent To E
Notes
2014-11-26 13:33:18ENGINEERING DIVISION / PUBLIC WORKS DEPT.
  
 1. SUBMIT FOR A MODIFICATION OF THE ENGINEERING
 DIVISION APPROVAL. INCLUDE DARING CALCULATIONS AND
 WATER/SEWER FLOW ESTIMATES.
  
 KELLY CRANFORD, PE
 561-494-1098
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-12-04 Cont ID  
Sent By scaldero Date 2014-12-04 Time 11:29 Rev Time 0.00
Received By scaldero Date 2014-12-04 Time 11:29 Sent To  
Notes
2014-12-04 11:32:41PERMIT # 14110435
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PENDING PROVISO:
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION
 OF THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE
 UNDERGROUND FIRE LINE AND FIRE HYDRANTS. FIRE HYDRANT
 APPEARS TO HAVE BEEN INSTALLED WITHOUT A PERMIT AND/OR
 REQUIRED INSPECTIONS.
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-01-14 Cont ID  
Sent By hmoser Date 2015-01-14 Time 13:39 Rev Time 0.00
Received By hmoser Date 2015-01-14 Time 08:31 Sent To  
Notes
2015-01-14 08:31:48TO HMOSER DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-06 Cont ID  
Sent By dhayes Date 2015-01-06 Time 09:12 Rev Time 0.00
Received By dhayes Date 2014-12-29 Time 10:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-18 Cont ID  
Sent By hmoser Date 2014-12-18 Time 10:06 Rev Time 0.00
Received By hmoser Date 2014-11-10 Time 09:38 Sent To  
Notes
2014-11-24 08:26:23SENT TO C18 ON 11/24/14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-12-11 Cont ID  
Sent By jwitmer Date 2014-12-05 Time 06:43 Rev Time 0.00
Received By jwitmer Date 2014-12-05 Time 06:43 Sent To  
Notes
2014-12-05 06:44:26PERMIT 11090826 IMPACT FEES PAID, SEE ATTACHED DOCUMENT
 FROM WILLIE SWOOPE PALM BEACH CTY. IMPACT FEE OFFICE NO
 FEES DUE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-01-14 Cont ID  
Sent By hmoser Date 2015-01-14 Time 13:39 Rev Time 0.00
Received By hmoser Date 2015-01-14 Time 12:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-01-02 Cont ID  
Sent By hmoser Date 2015-01-02 Time 14:27 Rev Time 0.00
Received By hmoser Date 2015-01-02 Time 13:50 Sent To  
Notes
2015-01-02 14:27:53PLAN DENIED
 PROVIDE ENERGY CALCULATIONS WITH PLAN
 PER SECTION 503.2.1 CALCULATION OF HEATING AND COOLING
 2010 FLORIDA ENERGY CODE
 PROVIDE EQUIPMENT SCHEDULE ON THE PLAN.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-18 Cont ID  
Sent By hmoser Date 2014-12-18 Time 10:01 Rev Time 0.00
Received By hmoser Date 2014-12-19 Time 15:56 Sent To  
Notes
2014-12-18 10:06:11RE-STAMP DENIED
 THERE WAS NEVER A MECHANICAL AIR CONDITIONING PERMIT
 ON THIS JOB APPLICATION, PLAN, ENERGY CALCULATIONS
 REQUIRED
 FOR PERMIT.
 PROVIDE EQUIPMENT SCHEDULE ON PLAN PER 107 FBC 2010
 AND ENERGY CALCULATIONS WITH PLAN PER FLORIDA ENERGY
 CODE
 503.2.10 CALCULATION OF HEATING AND COOLING 2010
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-11-24 Cont ID  
Sent By tklarge Date 2014-11-24 Time 11:12 Rev Time 0.00
Received By tklarge Date 2014-11-24 Time 09:00 Sent To  
Notes
2014-11-24 11:14:31RE-ISSUE OF 11090826.

Review Stop Z ZONING
Rev No 2 Status P Date 2014-12-29 Cont ID  
Sent By ajones Date 2014-12-29 Time 15:48 Rev Time 0.00
Received By ajones Date 2014-12-29 Time 15:48 Sent To  
Notes
2014-12-29 15:49:43APPROVAL IS FOR BUILDING ONLY NO EXTERIOR SITE WORK

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-10 Cont ID  
Sent By avann Date 2014-12-10 Time 10:14 Rev Time 0.00
Received By ajones Date 2014-12-10 Time 10:14 Sent To  
Notes
2014-12-10 10:20:1012/10/14- FAILED. 1.A PALM BEACH COUNTY RIGHT-OF-WAY
 PERMIT FOR THE CHANGES REQUESTED TO THE CURB CUT ALONG
 AUSTRALIAN AVENUE MUST BE OBTAINED.
 2. THE SITE PLAN SUBMITTED DOES NOT REFLECT TO CHANGES
 TO THE SITE PLAN REQUESTED BY PAM BEACH COUNTY AS PART
 OF THE ROW PERMIT REQUESTED FOR THE CHANGES TO THE
 AUSTRALIAN AVENUE CURB CUT.
  
  
 ANGELLA VANN, PLANNING AND ZONING ADMINISTRATOR
 561-822-1441
 [email protected]
  