| 2014-11-18 07:48:43 | BUILDING PLAN REVIEW |
| | PERMIT: 14110431 |
| | ADD: 1000 N DIXIE HWY |
| | CONT: TBD/ CHURCH OF GOD LIGHT HOUSE OF HOPE |
| | TEL: (561)460-8779 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. NOV. 18/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SUBMITTED PLANS ARE COPIES OF ARCHITECTURAL PLANS, |
| | FOR THE APPLICANTS USE AS REFERANCE ONLY. ARCHITECTURAL |
| | SHEETS ARE COPRIGHTED!!! |
| | |
| | 2) FOR A CHANGE OF OCCUPANCY THE EXISTING BUILDING CODE |
| | CHAPTER 9 SEE SECTION 901.3.1 FOR A PARTIAL CHANGE OF |
| | OCCUPANCY OF A BUILDING. |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE |
| | DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE |
| | FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN; |
| | SITE PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR |
| | TRUSS LAYOUT; ALL FENESTRATION PENETRATIONS; FLASHING; |
| | AND ROUGH OPENING DIMENSIONS; AND ALL EXTERIOR |
| | ELEVATIONS: |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE 503). |
| | 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | PRE-ENGINEERED SYSTEMS |
| | 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL |
| | INCLUDE THE FOLLOWING |
| | REQUIREMENTS: |
| | OCCUPANT LOAD AND EGRESS CAPACITIES |
| | 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | FLOOR SYSTEMS |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA |
| | TUS.ASPX FOR PERMIT STATUS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |