| 2014-12-09 17:44:00 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| | TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY |
| | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE |
| | UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION TO |
| | INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND |
| | PROFIT AND PROFESSIONAL DESIGN FEES. VALUATION WAS |
| | UPDATED TO $26,058. THE PERMIT FEE BALANCE IS $637.02. |
| | |
| | 3- CLEARLY SPECIFY ON PLANS THE NAME OF THE ALTERED |
| | ROOM ADJACENT TO THE NEW BEDROOM ADDITION AS REQUIRED |
| | BY SEC. 401.3 OF 2010 FBC-EXISTING BUILDING. ROOM IS |
| | NOT DEFINED AND NEED TO VERIFY EGRESS REQUIREMENTS. |
| | |
| | 4- WALL SECTION PROVIDED: |
| | A) LETTERING IS TOO SMALL AND IS MISSING INFORMATION. |
| | DRAWING WAS COPIED AND PASTED AND IS MISSING ALL THE |
| | INFORMATION ON THE LEFT HAND SIDE. REVISE AS REQUIRED. |
| | SEC. 107.2.1.4 CITY AMENDMENTS TO FBC. |
| | |
| | B) FOOTING INFORMATION IS NOT CLEAR. THERE IS |
| | INFORMATION REGARDING A STEM WALL, BUT THERE IS NOT |
| | STEM WALL SHOWN. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | C) CLEARLY SHOW THE FOOTING DIMENSION BELOW GRADE AND |
| | ABOVE GRADE. DIMENSION SHOWN IS OFFSET. COORDINATE WITH |
| | SIZE OF FOOTING SPECIFIED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 5- SPECIFY CARBON MONOXIDE ALARMS AS REQUIRED BY SEC. |
| | R315 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 6- GABLE END BRACING DETAIL: PROVIDE COMPLETE |
| | SPECIFICATIONS FOR THE RAKE BEAM. THERE IS NOT BEAM |
| | SCHEDULE PROVIDED. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) POLYGLASS ROOFING UNDERLAYMENT. NOA 11-1229.01 |
| | SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE |
| | CURRENT NOA. |
| | |
| | B) FIXED WINDOWS: NEED PRODUCT APPROVAL THAT MEETS THE |
| | DESIGN PRESSURES CALCULATED BY THE ARCHITECT. NOA |
| | 11-1114.14 SUBMITTED DOESN'T MEET CALCULATED DESIGN |
| | PRESSURES. |
| | |
| | 8- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 9- DESIGN PRESSURES CALCULATED BY THE ARCHITECT FOR THE |
| | NEW 72" X 60" STOREFRONT FIXED WINDOWS ARE TOO LOW. |
| | REVISE AS REQUIRED. SEC. R301 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 10- ENERGY CALCULATIONS: |
| | A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC. |
| | 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | B) REVISE ITEM #12B: NEED 13 SEER MIN.. SEE GENERAL |
| | INSTRUCTION NOTE #2 OF ENERGY CALCULATIONS SUBMITTED. |
| | |
| | (NOTE: HOUSE IS A HISTORIC CONTRIBUTING HOUSE. ENERGY |
| | CALCULATIONS ARE NOT REQUIRED). |
| | |
| | 11- ARCHITECT TO PROVIDE DETAIL AND SPECIFICATIONS |
| | SHOWING COMPLIANCE WITH THE R7.8 INSULATION ON MASONRY |
| | WALLS AS REQUIRED BY THE ENERGY CALCULATIONS SUBMITTED. |
| | |
| | 12- PROVIDE WINDOWS AND DOORS MANUFACTURER'S SPECS |
| | SHOWING COMPLIANCE WITH THE U-FACTOR AND SHGC FACTOR |
| | SPECIFIED ON ITEM #6 OF ENERGY CALCULATIONS SUBMITTED. |
| | SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 13- SOIL TEST REPORT NEEDS ENGINEER'S ORIGINAL SEAL AND |
| | SIGNATURE AS REQUIRED BY CHAPTER 471 FL. ST. |
| | |
| | 13- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE |
| | INSTALLATION OF STORM SHUTTERS. YOU CAN USE THE CITY |
| | SAMPLE FOR STORM SHUTTERS INSTALLATION SCHEDULE OR USE |
| | ANY OTHER FORMAT THAT PROVIDES ALL THE REQUIRED |
| | INFORMATION. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS.. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |