Plan Review Details - Permit 14110382
Plan Review Stops For Permit 14110382
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-05-26 Cont ID  
Sent By skennedy Date 2015-05-26 Time 15:47 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-03-11 Cont ID  
Sent By jgomez Date 2015-03-11 Time 10:24 Rev Time 0.00
Received By jgomez Date 2015-03-11 Time 10:23 Sent To  
Notes
2015-03-11 10:25:30RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- NEW SHEET #2: SHED ROOF SECTION:
 A) ORIGINAL COMMENT: ENGINEER OF RECORD TO PROVIDE
 DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE WITH THE
 ROOF CROSS VENTILATION AS REQUIRED BY SEC. R806 OF 2010
 FBC-RESIDENTIAL.
  
 ***RESPONSE TO REVISED WALL SECTION: 3" X 16" SCREEN
 VENTS @ 6'-0" O.C. DON'T PROVIDE CROSS VENTILATION. 2 X
 12 ROOF RAFTERS DON'T ALLOW CROOS VENTILATION. THERE IS
 NOT SPACE FOR CROSS VENTILATION. SPECIFIED SCREEN VENTS
 ONLY PROVIDE VENTILATION TO THE RAFTERS THAT ARE
 LOCATED BETWEEN THE SCREEN VENTS. THE REST OF THE ROOF
 IS UNVENTED. REVISE AS REQUIRED.
  
 B) PRINTING QUALITY ON NEW PAGE 2 IS NOT ACCEPTABLE FOR
 RECORDS RETENTION AS REQUIRED BY SECTION SEC. 107.2.1.4
 OF CITY AMENDMENTS TO FBC. THE INFORMATION IS NOT
 READABLE. LETTERING IS NOT CLEAR AND THE LETTERING
 GUIDE LINES DON'T ALLOW TO READ THE LETTERING.
  
 2- ENERGY CALCULATIONS: (REPEAT COMMENT. NOT ADDRESSED
 AT ALL).
  
 ****NOTE: INFORAMTION SHOWN ON PLANS BY THE ENGINEER OF
 RECORD AND INFORMATION SHOWN ON THE ENERGY CALCULATIONS
 NEED TO MATCH.
  
 A) ENGINEER WHO PREPARED THE CALCULATIONS TO PROVIDE
 NAME, LICENSE NUMBER AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE.
  
 B) FORM NEEDS TO BE SIGNED AND DATED BY THE
 OWNER/AGENT. SEC. 103.2.3 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 C) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. THE CONTRACTOR IS NOT THE OWNER. REVISE AS
 REQUIRED. AND, COMPLETE THE PERMIT OFFICE AND
 JURISDICTION NUMBER. SEC. 103.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 D) REVISE THE ROOF MATERIAL SHOWN ON PAGE 2 OF 5. THERE
 ARE NOT SHINGLES ON THIS HOUSE. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 E) REVISE THE DOOR INFORMATION SHOWN ON PAGE 3 OF 5.
 THERE ARE NOT WOOD DOORS. THERE ARE NOT 3 EXTERIOR
 DOORS EITHER. REVISE THE DOOR ORIENTATION. SEE PLANS
 AND PRODUCT APPROVALS AND REVISE AS REQUIRED. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 F) REVISE THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 5.
 REVISE THE ORIENTATION TO MATCH PLANS. REVISE THE
 OVERHANG DEPTH AND SEPARATION TO MATCH PLANS. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 3- PROVIDE MANUFACTURER SPECS FOR WINDOWS AND DOORS
 SHOWING THE U-FACTOR AND SHGC FACTORS SHOWN ON ITEM # 7
 OF THE ENERGY CALCULATIONS SUBMITTED. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION. (REPEAT COMMENT. NOT
 ADDRESSED).
 ***NOTE: THIS ITEM IS NOT REQUIRED TO BE SUBMITTED NOW.
 THIS ITEM WAS REQUESTED TO AVOID ANY CONFLICT WITH THE
 ENERGY CALCULATIONS SUBMITTED. IF THE INSTALLED
 WINDOWS/DOORS DON'T HAVE THESE ENERGY EFFICIENCY
 FACTORS, THEN IT WILL FAIL INSPECTIONS.
  
 4- ENGINEER OF RECORD TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR MASONRY WALLS SHOWING COMPLIANCE
 WITH THE R VALUE SPECIFIED ON ITEM #9. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION. (REPEAT COMMENT. NOT
 ADDRESSED)
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMITT OLD/VOID DRAWINGS FOR REFERENCE AND TO EXPEDITE
 THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-11 Cont ID  
Sent By jgomez Date 2014-12-11 Time 12:31 Rev Time 0.00
Received By jgomez Date 2014-12-11 Time 12:25 Sent To  
Notes
2014-12-11 12:34:46RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- DRAWINGS NEED THE ORIGINAL SEAL AND SIGNATURE OF THE
 ENGINEER RESPONSIBLE FOR THE DESIGN AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE.
  
 2- SPECIFY THE SIZE OF THE NEW BEDROOM EGRESS WINDOW.
 PLANS SUBMITTED DON'T SPECIFY THE SIZE. SEC. R310
 FBC-RESIDENTIAL.
  
 3- PROVIDE COMPLETE SPECIFICATIONS FOR THE NEW MASONRY
 OPENING TO RECEIVE NEW EGRESS WINDOW. PROVIDE COMPLETE
 SPECIFICATIONS FOR THE COLUMNS AND REINFORCING.
 DRAWINGS SUBMITTED SHOW COLUMNS ON BOTH SIDES OF
 OPENING, BUT THERE ARE NO SPECIFICATIONS. SEC. R301 OF
 2010 FBC-RESIDENTIAL.
  
 4- REVISE CONNECTOR SCHEDULE. CLEARLY IDENTIFY WHICH
 SPECIFIC H10 SIMPSON STRUCTURAL CONNECTORS IS GOING TO
 BE USED. THERE ARE MANY TYPES OF H10 CONNECTORS ON THE
 SIMPSON CATALOG. AND, REVISE THE NAIL SIZE AND NUMBER
 OF NAILS FOR ALL CONNECTORS TO MATCH PRODUCT APPROVAL
 SPECS. SEC. R301 OF 2010 FBC-RESIDENTIAL. OTHERWISE,
 ENGINEERING ANALYSIS WILL BE REQUIRED FOR NAILING OTHER
 THAN THE SPECIFIED ON THE PRODUCT APPROVAL.
  
 5- WALL SECTION SUBMITTED:
 A) ENGINEER OF RECORD TO PROVIDE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE ROOF CROSS
 VENTILATION AS REQUIRED BY SEC. R806 OF 2010
 FBC-RESIDENTIAL.
  
 B) ENGINEER OF RECORD TO PROVIDE COMPLETE
 SPECIFICATIONS FOR THE ROOF OUTLOOKERS. SPECIFY SIZE
 AND FASTENERS. SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 C) REVISE STUCCO THICKNESS TO COMPLY WITH TABLE
 R702.1(1) OF 2010 FBC-RESIDENTIAL. NEED 7/8" MIN.
  
 D) NEED TO SHOW NOT LESS THAN 6" CLEARANCE FROM GRADE
 TO STUCCO AS REQUIRED BY SEC. R704 OF 2010
 FBC-RESIDENTIAL. REVISE DRAWING AS REQUIRED.
  
 6- ENERGY CALCULATIONS:
 A) ENGINEER WHO PREPARED THE CALCULATIONS TO PROVIDE
 NAME, LICENSE NUMBER AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE.
  
 B) FORM NEEDS TO BE SIGNED AND DATED BY THE
 OWNER/AGENT. SEC. 103.2.3 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 C) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. THE CONTRACTOR IS NOT THE OWNER. REVISE AS
 REQUIRED. AND, COMPLETE THE PERMIT OFFICE AND
 JURISDICTION NUMBER. SEC. 103.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 D) REVISE THE ROOF MATERIAL SHOWN ON PAGE 2 OF 5. THERE
 ARE NOT SHINGLES ON THIS HOUSE. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 E) REVISE THE DOOR INFORMATION SHOWN ON PAGE 3 OF 5.
 THERE ARE NOT WOOD DOORS. THERE ARE NOT 3 EXTERIOR
 DOORS EITHER. REVISE THE DOOR ORIENTATION. SEE PLANS
 AND PRODUCT APPROVALS AND REVISE AS REQUIRED. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 F) REVISE THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 5.
 REVISE THE ORIENTATION TO MATCH PLANS. REVISE THE
 OVERHANG DEPTH AND SEPARATION TO MATCH PLANS. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 7- PROVIDE MANUFACTURER SPECS FOR WINDOWS AND DOORS
 SHOWING THE U-FACTOR AND SHGC FACTORS SHOWN ON ITEM # 7
 OF THE ENERGY CALCULATIONS SUBMITTED. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 8- ENGINEER OF RECORD TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR MASONRY WALLS SHOWING COMPLIANCE
 WITH THE R VALUE SPECIFIED ON ITEM #9. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED BY THE
 ENGINEER ON THE CONNECTOR SCHEDULE. NOTE: ENGINEER MAY
 LIST FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE
 SPECIFIED CONNECTOR OR PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-05-26 Cont ID  
Sent By skennedy Date 2015-05-26 Time 15:47 Rev Time 0.00
Received By skennedy Date 2015-05-15 Time 11:45 Sent To  
Notes
2015-05-05 11:58:28NEW DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-10 Cont ID  
Sent By skennedy Date 2015-03-10 Time 10:07 Rev Time 0.00
Received By skennedy Date 2015-03-10 Time 10:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-17 Cont ID  
Sent By skennedy Date 2014-12-17 Time 08:00 Rev Time 0.00
Received By skennedy Date 2014-12-17 Time 08:00 Sent To  
Notes
2014-12-17 08:13:031ST REVIEW: FBC 2010 NEC 2008
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE.
  
 FBC-107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS - THE CONSTRUCTION DOCUMENTS
 SHALL BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL
 WHERE REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES& 61G1 FLORIDA ADMINISTRATIVE CODE, THEN HE OR
 SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL TO SAID
 DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 I SUGGEST YOU PROVIDE A PANEL SCHEDULE OR AT LEAST
 NOTES TO INDICATE WIRE SIZE AND OCP AT A MINIMUM IN
 ADDITION TO THE PLAN YOU HAVE SUBMITTED.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-26 Cont ID  
Sent By skennedy Date 2015-05-26 Time 15:47 Rev Time 0.00
Received By skennedy Date 2015-05-05 Time 12:45 Sent To  
Notes
2015-05-05 12:45:46RE-SUBMITTAL SENT TO R5 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-11 Cont ID  
Sent By jgomez Date 2015-03-11 Time 10:24 Rev Time 0.00
Received By jgomez Date 2015-02-23 Time 16:26 Sent To  
Notes
2015-02-25 16:26:50RE-SUBMITTAL SENT TO R18 BIN FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-17 Cont ID  
Sent By skennedy Date 2014-12-17 Time 08:00 Rev Time 0.00
Received By skennedy Date 2014-11-10 Time 07:00 Sent To  
Notes
2014-11-12 06:59:59INCOMING SENT TO R-06 BOX. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2014-12-11 Cont ID  
Sent By jgomez Date 2014-12-11 Time 12:14 Rev Time 0.00
Received By jgomez Date 2014-12-11 Time 12:14 Sent To  
Notes
2014-12-11 12:25:15NO IMPACT FEES REQUIRED. MU-2014-23005.

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-05-15 Cont ID  
Sent By skennedy Date 2015-05-15 Time 11:44 Rev Time 0.00
Received By skennedy Date 2015-05-15 Time 11:44 Sent To  
Notes
2015-05-05 12:39:45NEW DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-03-07 Cont ID  
Sent By tklarge Date 2015-03-07 Time 05:25 Rev Time 0.00
Received By tklarge Date 2015-03-07 Time 05:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-24 Cont ID  
Sent By tklarge Date 2014-11-24 Time 06:28 Rev Time 0.00
Received By tklarge Date 2014-11-24 Time 06:19 Sent To  
Notes
2014-11-24 06:37:061) PLANS ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 DESIGN PROFESSIONAL OF RECORD PER THE FL. ADMIN. CODE
 RULE 61G15-23.002.
 2) SUBMIT A SANITARY RISER THAT IS CLEAR AND REFLECTS
 THE SCOPE OF WORK. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2014-12-11 Cont ID  
Sent By jgomez Date 2014-12-11 Time 15:34 Rev Time 0.00
Received By jgomez Date 2014-12-11 Time 15:34 Sent To  
Notes
2014-12-11 15:34:56FLAT ROOF FL2533-R11.

Review Stop Z ZONING
Rev No 3 Status P Date 2015-06-02 Cont ID  
Sent By sgraham Date 2015-06-02 Time 12:46 Rev Time 0.00
Received By sgraham Date 2015-06-02 Time 12:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2015-05-08 Cont ID  
Sent By sgraham Date 2015-05-08 Time 15:10 Rev Time 0.00
Received By sgraham Date 2015-05-08 Time 15:10 Sent To  
Notes
2015-05-08 15:10:565/8/15 ZONING FAILED
  
 1. PROVIDE TWO UP TO DATE SURVEYS
2015-05-05 12:39:09NEW DRAWINGS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-11-17 Cont ID  
Sent By sgraham Date 2014-11-17 Time 15:51 Rev Time 0.00
Received By sgraham Date 2014-11-17 Time 15:51 Sent To  
Notes
2015-05-08 15:10:0011/14/2014 ZONING FAILED
  
 1. PROVIDES TWO UP TO DATE SURVEYS
2014-11-14 12:30:0811/14/14