Plan Review Details - Permit 14110377
Plan Review Stops For Permit 14110377
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-11-26 Cont ID  
Sent By jwitmer Date 2014-11-26 Time 16:54 Rev Time 0.00
Received By jwitmer Date 2014-11-26 Time 16:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-11-21 Cont ID  
Sent By wjolin Date 2014-11-21 Time 11:19 Rev Time 0.00
Received By wjolin Date 2014-11-21 Time 10:27 Sent To  
Notes
2014-11-21 11:17:346651 NORTH JOG ROAD - LIVING WALLS
 PERMIT #14110377
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 A FIRE HYDRANT IS LOCATED TO THE NORTHWEST OF THE FIRE
 PUMP ROOM. VERIFY LIVING WALLS DO NOT ENCROACH WORKING
 CLEARANCES REQUIRED FOR FIRE HYDRANTS. PER SECTION
 18.3.4.1 (NFPA 1), FIRE HYDRANTS SHALL BE PROVIDED WITH
 CLEARANCES OF 7?-6? TO THE FRONT AND SIDES AND 4?-0? TO
 THE BACKSIDE OF THE STEAMER CAP.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-06 Cont ID  
Sent By cpuell Date 2015-02-06 Time 15:52 Rev Time 0.00
Received By cpuell Date 2015-01-20 Time 07:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-18 Cont ID  
Sent By cpuell Date 2014-12-18 Time 15:19 Rev Time 0.00
Received By cpuell Date 2014-11-12 Time 10:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-02-12 Cont ID  
Sent By skennedy Date 2015-02-12 Time 08:52 Rev Time 0.00
Received By skennedy Date 2015-02-11 Time 16:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-02-06 Cont ID  
Sent By eschneid Date 2015-02-06 Time 15:02 Rev Time 0.25
Received By eschneid Date 2015-02-06 Time 15:02 Sent To  
Notes
2015-02-06 15:03:53PASSED W/PROVISO
  
 1) THE NEW CONSTRUCTION VALUE OF THIS PERMIT EXCEEDS
 $500,000 AND THUS IS REQUIRED TO MEET THE PROVISIONS OF
 THE ART IN PUBLIC PLACES REGULATIONS IN THE CITY CODE.
  
 2) THE PROPOSED LIVING WALLS ARE NOT SHOWN ON THE
 CURRENTLY APPROVED SITE PLAN. PRIOR TO THE COMPLETION
 OF THE PROJECT, THE SWA SHALL SUBMIT THE FINAL AS BUILT
 SITE AND LANDSCAPE PLANS TO THE PLANNING DIVISION FOR
 APPROVAL.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-18 Cont ID  
Sent By eschneid Date 2014-12-18 Time 14:46 Rev Time 0.00
Received By eschneid Date 2014-12-04 Time 10:56 Sent To  
Notes
2014-12-18 14:53:45FAILED
  
 1) THE NEW CONSTRUCTION VALUE OF THIS PERMIT EXCEEDS
 $500,000 AND THUS IS REQUIRED TO MEET THE PROVISIONS OF
 THE ART IN PUBLIC PLACES REGULATIONS IN THE CITY CODE.
 PLEASE ADDRESS HOW THE ART IN PUBLIC PLACES REQUIREMENT
 WILL BE FULFILLED.
  
 2) THE PROPOSED LIVING WALLS ARE NOT SHOWN ON THE
 CURRENTLY APPROVED SITE PLAN. PRIOR TO THE COMPLETION
 OF THE PROJECT, THE SWA SHALL SUBMIT THE FINAL AS BUILT
 SITE AND LANDSCAPE PLANS TO THE PLANNING DIVISION FOR
 APPROVAL.
  
 3) PLEASE EXPLAIN WHY THERE ARE TWO 17 FOOT X 11 FOOT
 OPENINGS IN THE LIVING WALL BY THE POWER BLOCK
 BUILDING. THESE DO NOT SEEM TO RESULT IN SCREENING THE
 AREA BEHIND THE WALL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
  
2014-11-14 12:30:4111/14/14