Plan Review Details - Permit 14110349
Plan Review Stops For Permit 14110349
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-01-14 Cont ID  
Sent By jwitmer Date 2015-01-14 Time 07:00 Rev Time 0.00
Received By jwitmer Date 2015-01-14 Time 06:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-12-17 Cont ID  
Sent By jwitmer Date 2014-12-17 Time 14:09 Rev Time 0.00
Received By jwitmer Date 2014-12-17 Time 11:59 Sent To  
Notes
2014-12-17 14:09:07BUILDING PLAN REVIEW
 PERMIT: 14110349
 ADD: 410 EVERNIA ST. # 110
 CONT: MASON DEV. & CONST.L
 TEL: (561)623-8801
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. DEC. 17/ 2014
 ACTION: DENIED
 FIRST FLOOR LEVEL 792 SQ. FT.
 MEZZANINE LEVEL 276 SQ. FT. 2010 FBC-B 505.2 AREA
 LIMITATION. EXCEPTION # 2 ALLOWABLE AREA 1/2 OF THE 354
 FLOOR UNENCLOSED AREA 354 SQ FT.
 MEZZANINE SQ. FT. AREA CODE COMPLIANT!
 -------------------------------------------------------
 -------------------
 TOTAL AREA 1068 SQ FT /2= 534 SQ. FT.
  
  
 1) PLEASE NOTE THE PLANS INDICATE IN THE TITLE BLOCK A
 LOFTS BUT THE SHEET S-1 UNDER THE HEADING SCOPE OF WORK
 INDICATES A BEAUTY SALON A BUSINESS OCCUPANCY AS A
 LEVEL II ALTERATION UNDER THE 2010 EXST .BLDG. CODE.
 THE WHITNEY WAS PERMITED UNDER PERMIT # 04031591, THE
 FIRST FLOOR AND MEZZANINE LEVEL WERE PERMITED AS A
 RESIDENTIAL OCCUPANCY. THERE HAS BEEN NO PERMIT TO THIS
 SUITE # 110 TO CHANGE THE OCCUPANCY TO ANY OTHER
 OCCUPANCY. THIS UNIT WILL REQUIRE A CHANGE IN OCCUPANCY
 PERMIT, NOT A LEVEL II ALTERATION TO BECOME A BEAUTY
 SALON.
  
 2) PLEASE NOTE THE KITCHEN ON THE FIST FLOOR SHOWS A
 COOK TOP UNIT IN THE FLOOR PLAN, TO BE CONSIDERED PART
 OF A BUSINESS OCCUPANCY, THEN OVER THE STOVE A GREASE
 HOOD WOULD BE REQUIRED. SEE 2010 FBC-M. 506.1.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-15 Cont ID  
Sent By jwitmer Date 2014-11-15 Time 12:05 Rev Time 0.00
Received By jwitmer Date 2014-11-15 Time 10:01 Sent To  
Notes
2014-11-15 11:28:49BUILDING PLAN REVIEW
 PERMIT: 14110349
 ADD: 410 EVERNIA ST. # 110
 CONT: MASON DEV. & CONST.L
 TEL: (561)623-8801
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. NOV.15/ 2014
 ACTION: DENIED
 FIRST FLOOR LEVEL 792 SQ. FT.
 MEZZANINE LEVEL 276 SQ. FT. 2010 FBC-B 505.2 AREA
 LIMITATION. EXCEPTION # 2 ALLOWABLE AREA 1/2 OF THE 354
 FLOOR UNENCLOSED AREA 354 SQ FT.
 MEZZANINE SQ. FT. AREA CODE COMPLIANT!
 -------------------------------------------------------
 -------------------
 TOTAL AREA 1068 SQ FT /2= 534 SQ. FT.
  
 1) PLEASE NOTE THE PLANS INDICATE IN THE TITLE BLOCK A
 LOFTS BUT THE SHEET SHEET A-1 UNDER THE HEADING OF
 OCCUPANCY INDICATES A MIXED USE. A LIVE / WORK BARBER/
 BEAUTY SALON. PLEASE IDENTIFY WHICH THIS PLANS WAS
 DESIGNED UNDER. SINCE BOTH LIVE/ WORK LOFTS (FBC-B 438)
 & MIXED OCCUPANCY (FBC-B 508) ARE IDENTIFIED AS
 OCCUPANCY TYPES. FOR THE PURPOSE OF THIS REVIEW, IT
 WILL BE DEFINED AS A WORK/ LIVE LOFT COVERED UNDER THE
 2010 FBC SECTION 438.
 PLEASE REVIEW THE ALLOWABLE AREA FOR THE BUSINESS
 OCCUPANCY FOUND IN 2010 FBC-B 438.1.1 LIMITATIONS 2.
 THE NONRESIDENTIAL AREA IS PERMITTED TO BE A MAXIMUM 50
 PERCENT OF THE AREA OF EACH LIVE/WORK UNIT.
 THE MEZZANINE FLOOR AREA DOES NOT MEET THE 1/2 OF THE
 TOTAL FLOOR AREA OF THE LIVE/ WORK UNIT.
  
 2) SINCE THE AREA LIMITATIONS CAN NOT BE MEET FOR A
 WORK/ LIVE LOFT IT WILL NEED TO BE REVIEWED AS A MIXED
 OCCUPANCY. THE WAY THE DESIGN IS NOW FOR A DWELLING
 UNIT (R2) TTHE REQUIREMENTS OF 439.2 WILL NEED TO BE
 COMPLIED WITH. NOTE A DWELLING UNIT WILL NEED TO HAVE A
 KITCHEN, OTHER WISE THE UPSTAIRS UNIT WILL BE
 CONSIDERED A SLEEPING UNIT. SEE 709 REQUIREMENTS FOR
 FIRE PARTITIONS.
  
 3) PLEASE NOTE IF THE KITCHEN ON THE FIST FLOOR IS TO
 BE CONSIDERED PART OF THE BUSINESS OCCUPANCY, THEN OVER
 THE STOVE A GREASE HOOD WOULD BE REQUIRED. SEE 2010
 FBC-M. 506.1.
  
 4) FOR THE UPSTAIR MEZZANINE TO BE CONSIDERED A R2
 OCCUPANCCY WITH ENCLOSED WALL PLEASE PROVIDE THE
 PROPOSED UPSTAIRS LANDING, WITH THE RATED WALL AND DOOR
 TO THE SLEEPING ROOM. 1009.5 STAIRWAY LANDINGS VS DOOR
 SWINGS. 709.1 & 709.3.
  
 5) NOTE FOR THE FIELD INSPECTORS TO VERIFY IN THE
 FIELD. THIS UNIT WAS BUILT UNDER THE FAIR HOUSING
 GUIDELINES AND BOTH WATER CLOSETS SHOULD HAVE BEEN SET
 AT 15 INCHES FROM THE WALL. NOTE WITH THE CHANGE OF
 OCCUPANCY TO A BUSINESS OCCUPANCY THE 1ST FLOOR WATER
 CLOSET WILL NOW NEED TO SET BETWEEN 16- 18 INCHES FROM
 THE WALL LINE. 2010 FL ACCESSIBILITY CODE 604.2.
  
 6) THE OTHER ISSUE WITH THE SIZE OF THE FIRST FLOOR
 RESTROOM IN THE 7'-0" DIMENSION IS IF THE LAV PROVIDED
 IS OVER THE MINIMUM DIMENSION THE ROOM WILL BE TO SMALL
 AND THE REQUIRED 60 INCHES CLEAR FOR THE WATER CLOSET
 WILL NOT BE MET, SEE ACCESS. CODE 604.3.1 SIZE.
  
 7) THE LOFT PLAN IS MISSING A GAURDFAILING RIGHT OF THE
 STAIR AT THE TOP LANDING. SEE THE REQUIREMENTS FOR
 GUARDS FOUND IN THE 2010 FBC-B 1013.1-3.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-12-19 Cont ID  
Sent By dhayes Date 2014-12-19 Time 10:14 Rev Time 0.00
Received By dhayes Date 2014-12-19 Time 10:12 Sent To  
Notes
2014-12-19 10:42:5612/19/2014
 PROJECT: J & G SALON
 PERMIT#: 14110349
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 1) PROVIDE LIGHTING CONTROL. FBC-E 505.2
  
 2) VERIFY WHERE WALLS OR CEILINGS ARE REQUIRED TO HAVE
 A FIRE-RESISTANCE RATING, RECESSED OUTLETS SHALL BE
 INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE WILL
 NOT BE REDUCED. FBC 713.3.2
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-11-12 Cont ID  
Sent By tlarge Date 2014-11-12 Time 15:19 Rev Time 0.00
Received By dhayes Date 2014-11-12 Time 15:19 Sent To P
Notes
2014-11-12 15:54:5411/12/2014
 PROJECT: BEAUTY LOFT
 PERMIT#: 14110349
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE PANEL SCHEDULE AND LOAD CALCULATION TO
 INDICATE NEW AND EXISTING LOADS. WPB AMENDMENTS TO THE
 FBC 107.3.2
  
 2) REVISE FLOOR PLAN TO INDICATE CIRCUIT NUMBERS ON THE
 NEW AND EXISTING CIRCUITS. WPB AMENDMENTS TO THE FBC
 107.3.2
  
 3) REVISE LIGHTING PLAN TO INDICATE THE CIRCUITS TO
 FEED EMERGENCY AND EXIT LIGHTING. EMERGENCY EXIT
 CIRCUIT SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES. NEC 700.12(F)
  
 4) INDICATE ON THE REVISED LIGHTING PLAN TH REQUIRED
 EMERGENCY EGRESS LIGHTING AT STAIRS. NEC 700.16
  
 5) PROVIDE MANUFACTURER PRODUCT DATA SHEETS FOR CEILING
 MOUNTED BLOW DRYER SYSTEMS. NEC 110.3(B)
  
 6) INDICATE THE REQUIRED LIGHTING CONTROL ON REVISED
 LIGHTING PLAN. FBC-E 505.2
  
 7) VERIFY WHERE WALLS OR PARTITIONS ARE REQUIRED TO
 HAVE A FIRE-RESISTANCE RATING, RECESSED OUTLETS SHALL
 BE INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE
 WILL NOT BE REDUCED. FBC 713.3.2
  
 8) VERIFY THE REQUIRED SIGN CIRCUIT AND INCLUDE IT IN
 THE REVISED PANEL SCHEDULE. INDICATE COMPLIANCE WITH
 THE FBC-E, 505.20
  
 9) A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 REQUIRED FOR FIRE ALARM, SECURITY, CCTV, ACCESS CONTROL
 SYSTEM, ETC..
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-12-16 Cont ID  
Sent By pleduc Date 2014-12-16 Time   Rev Time 0.00
Received By pleduc Date 2014-12-16 Time 14:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2014-11-17 Time   Rev Time 0.00
Received By pleduc Date 2014-11-17 Time 13:48 Sent To PC
Notes
2014-11-17 14:10:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE SEE COMMENTS OF OTHER DEPARTMENTS AND RESUBMIT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-01-15 Cont ID  
Sent By tklarge Date 2015-01-15 Time 11:17 Rev Time 0.00
Received By tklarge Date 2015-01-05 Time 14:13 Sent To  
Notes
2015-01-05 14:13:57B28
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2014-12-20 Time   Rev Time 0.00
Received By shill Date 2014-12-12 Time 11:28 Sent To  
Notes
2014-12-15 11:29:32**** E X P E D I T E D ****
 B28
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-17 Cont ID  
Sent By pleduc Date 2014-11-17 Time   Rev Time 0.00
Received By pleduc Date 2014-11-07 Time 06:12 Sent To  
Notes
2014-11-08 06:12:38B01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2015-01-23 Cont ID  
Sent By rmcdouga Date 2015-01-23 Time 15:49 Rev Time 0.00
Received By rmcdouga Date 2015-01-23 Time 15:49 Sent To  
Notes
2015-01-23 15:50:53MU2015-1472

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-01-14 Cont ID  
Sent By jwitmer Date 2015-01-14 Time 06:56 Rev Time 0.00
Received By jwitmer Date 2015-01-14 Time 06:55 Sent To  
Notes
2015-01-14 06:56:01BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-12-17 Cont ID  
Sent By jwitmer Date 2014-12-17 Time 14:09 Rev Time 0.00
Received By jwitmer Date 2014-12-17 Time 14:09 Sent To  
Notes
2014-12-17 14:09:52BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-11-15 Cont ID  
Sent By jwitmer Date 2014-11-15 Time 12:06 Rev Time 0.00
Received By jwitmer Date 2014-11-15 Time 12:06 Sent To  
Notes
2014-11-15 12:06:31BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-01-15 Cont ID  
Sent By tklarge Date 2015-01-15 Time 11:16 Rev Time 0.00
Received By tklarge Date 2015-01-15 Time 11:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-12-20 Cont ID  
Sent By tklarge Date 2014-12-20 Time 10:19 Rev Time 0.00
Received By tklarge Date 2014-12-19 Time 04:21 Sent To  
Notes
2014-12-19 04:56:131) SINCE THIS WILL BE A CHANGE IN OCCUPANCY, FULL
 COMPLIANCE WITH THE FL. ACCESSIBILITY WILL BE REQUIRED
 PER THE 2010 FL. EXISTING BUILDING CODE SEC.906.1. THE
 BREAK ROOM SINK SHALL COMPLY WITH SEC.212 & 804 OF THE
 2010 FL. ACCESSIBILITY CODE.SHOW COMPLIANCE ON THE
 PLANS.
 2) THE SANITARY RISER IS NOT TO CODE. THE SHAMPOO SINKS
 AND THE WATER CLOSET ARE NOT VENTED IN ACCORDANCE WITH
 THE 2010 FL. PLUMBING CODE SEC. 901.2, 901.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2014-11-13 Time   Rev Time 0.00
Received By tklarge Date 2014-11-13 Time 04:45 Sent To  
Notes
2014-11-13 10:27:35WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 1) INDICATE ON THE PLAN IF THE HANDICAPPED ACCESSIBILE
 TOILET ROOM IS NEW OR EXISTING.
 2) INDDICATE ON THE PLAN WHAT IS EXISTING TO REMAIN AND
 WHAT WILL BE NEW.
 3) THE POSITIONING OF THE SIDE WALL GRAB BAR IN THE
 ACCESSIBLE TOILET ROOM SHALL COMPLY W/ THE 2010 FL.
 ACCESSIBILITY CODE SEC. 604.5.1. SEE FIGURE 604.5.1.
 4) LIST THE OCCUPANCY TYPE ON THE PLAN IN ACCORDANCE W/
 CHAPTER 3 OF THE 2010 FBC.
 5) WATER PIPING EXPOSED TO CONCRETE OR PASSING THRU
 CONCRETE SHALL BE PROTECTED AGAINST EXTERNAL CORROSION
 IN ACCORDANCE WITH 2010 FL. PLUMBING CODE SEC. 305.1,
 305.2, 305.5, & 303.2.
 6) THE SANITARY RISER IS NOT DRAWN TO CODE. THE
 FIXTURES THE SINKS SHALL BE VENTED PER SEC.901.2,
 901.2.1.
 7) SUBMIT MANUF. SPEC SHEETS FOR THE AVERY BACKWASH
 SHAMPOO SYSTEM.
 8) THE SANITARY RISER SHOWS 2 SINKS AND THE FLOOR PLAN
 SHOWS 3. CLARIFY.
 9) IDENTIFY ON THE PLANS WHAT THE LOFT AREA WILL BE
 USED FOR.VERTICAL ACCESSIBILITY MAY BE REQUIRED PER THE
 2010 FL. ACCESSIBILITY CODE SEC.201.1.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
2014-11-13 06:53:281)