Plan Review Details - Permit 14110345
Plan Review Stops For Permit 14110345
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-04-21 Cont ID  
Sent By jwitmer Date 2015-04-21 Time 12:41 Rev Time 0.00
Received By jwitmer Date 2015-04-21 Time 12:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-02-26 Cont ID  
Sent By jwitmer Date 2015-02-26 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2015-02-26 Time   Sent To  
Notes
2015-02-26 12:11:22BUILDING PLAN REVIEW
 PERMIT: 14110345
 ADD: 550 S ROSEMARY AVE SUITE # 158
 CONT: CONSTRUCTION TECHNOLOGIES
 TEL: (954)598-0810
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MAY 11, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 2ND REVIEW
 DATE: THURS. FEB. 26/ 2010
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1.4 QUALITY OF
 BUILDING PLANS.THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE
 SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY,
 OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 2) THE NEW SHEETS BEING ADDED TO THE SET HAVE NOT BEEN
 REVIEWED AND STAMPED BY CITY PLACE MANAGEMENT TEAM FOR
 APPROVAL.
  
 3) SHEET A2.2 RESTROOM DETAILS SHOW THE GRAB RAILS
 DIMENSIONED 36 INCHES TO THE CENTERLINE FOR HEIGHT
 REQUIREMENTS. THIS WAS A CHANGE IN THE 2010 FL
 ACCESSIBILITY CODE, NORMALLY RED LINED BUT PLEASE
 UPDATE TO THE 2010 FL ACCESS. CODE SECTION 609.4 33- 36
 INCHES MEASURED TO THE TOP OF THE GRIPPING SURFACE.
  
 4) SHEET A4.0 REVISION # 1 INDICATES A RC5, NOT FOUND
 ON THE INTERIOR SECTION ELEVATION NOTES. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
2015-02-19 14:53:00NEW SHEETS SUBMITTED. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-01-26 Cont ID  
Sent By jwitmer Date 2015-01-26 Time 12:00 Rev Time 0.00
Received By jwitmer Date 2015-01-26 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-11-18 Cont ID  
Sent By jwitmer Date 2014-11-18 Time 11:22 Rev Time 0.00
Received By jwitmer Date 2014-11-18 Time 07:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2015-05-01 Cont ID  
Sent By dhayes Date 2015-05-01 Time 15:24 Rev Time 0.00
Received By dhayes Date 2015-05-01 Time 15:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2015-03-19 Cont ID  
Sent By sciard Date 2015-03-19 Time 13:08 Rev Time 0.00
Received By sciard Date 2015-03-19 Time 13:08 Sent To  
Notes
2015-03-19 13:12:111. ADDITION OF CIRCUITS A38,40 FOR SUMP PUMP NOT
 INCLUDED ON PANEL "A" SCHEDULE ON SHEET 3.1.
2015-02-19 14:53:25NEW SHEETS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-02-05 Cont ID  
Sent By tlarge Date 2015-02-05 Time 15:07 Rev Time 0.00
Received By dhayes Date 2015-02-05 Time 15:07 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-02-02 Cont ID  
Sent By dhayes Date 2015-02-02 Time 16:38 Rev Time 0.00
Received By dhayes Date 2015-02-02 Time 16:25 Sent To  
Notes
2015-02-02 16:41:56RESUBMITTAL SET IS INCOMPLETE. CALLED CONTRACTOR TO
 COME BACK IN TO CHANGE OUT SHEETS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-19 Cont ID  
Sent By dhayes Date 2014-12-19 Time 08:24 Rev Time 0.00
Received By dhayes Date 2014-12-19 Time 07:34 Sent To  
Notes
2014-12-19 07:58:0912/19/2014
 PROJECT: B&B
 PERMIT#: 14110345
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 1) VERIFY MAIN SERVICE ENTRANCE CONDUCTORS ARE APPROVED
 TO SUPPORT TOTAL CONNECTED LOAD. THERE IS NO SIZE
 INDICATED ON THE RISER DIAGRAM.
  
 2) CORRECT NOTE 5 ON PANEL SCHEDULE "B" THAT CALLS FOR
 A 150AMP CIRCUIT BREAKER TO FEED PANEL "A". THERE IS A
 CONFLICTING NOTE ON THE RISER DIAGRAM THAT CALLS FOR
 THAT TO BE A 200AMP BREAKER. PLEASE CLARIFY.
  
 3) VERIFY EXISTING WIREWAY IS ADAQUATE SIZE FOR THE NEW
 SERVICE.
  
 4) PROVIDE GFCI PROTECTION WHERE RECEPTACLES OUTLETS
 ARE INSTALLED WITHIN 1.8 M (6 FT) OF THE OUTSIDE EDGE
 OF A SINK.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-04-10 Cont ID  
Sent By pleduc Date 2015-04-10 Time   Rev Time 0.00
Received By pleduc Date 2015-04-10 Time 16:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-02-25 Cont ID  
Sent By pleduc Date 2015-02-25 Time   Rev Time 0.00
Received By pleduc Date 2015-02-25 Time 13:54 Sent To  
Notes
2015-02-19 14:54:05NEW SHEETS SUBMITTED. JG.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-11-12 Cont ID  
Sent By pleduc Date 2014-11-12 Time   Rev Time 0.00
Received By pleduc Date 2014-11-12 Time 10:59 Sent To  
Notes
2014-11-12 17:02:26THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 SHEET A2.0 SHOWS OCCUPANCY SIGN LOADS THAT DO NOT MATCH
 THE OCCUPANCY LOAD CALCULATIONS. THE OCCUPANCY LOAD
 INDICATED IS NOT APPROVED AND WILL BE DETERMINED AT THE
 TIME OF FINAL INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-05-01 Cont ID  
Sent By dhayes Date 2015-05-01 Time 15:24 Rev Time 0.00
Received By dhayes Date 2015-04-08 Time 08:35 Sent To  
Notes
2015-04-10 08:35:35B23

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-04-04 Cont ID  
Sent By hmoser Date 2015-04-04 Time 11:39 Rev Time 0.00
Received By hmoser Date 2015-02-19 Time 14:51 Sent To  
Notes
2015-02-19 14:52:22RE-SUBMITTAL SENT TO B14 BIN FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-02-09 Cont ID  
Sent By hmoser Date 2015-02-09 Time 09:32 Rev Time 0.00
Received By hmoser Date 2015-02-05 Time 15:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-02 Cont ID  
Sent By dhayes Date 2015-02-02 Time 16:45 Rev Time 0.00
Received By dhayes Date 2015-01-08 Time   Sent To  
Notes
2015-01-09 08:24:54INCOMING SENT TO C-11.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-19 Cont ID  
Sent By dhayes Date 2014-12-19 Time 08:24 Rev Time 0.00
Received By dhayes Date 2014-11-07 Time 06:54 Sent To  
Notes
2014-11-08 06:56:51B13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-11-18 Cont ID  
Sent By jwitmer Date 2014-11-18 Time 11:22 Rev Time 0.00
Received By jwitmer Date 2014-11-18 Time 08:00 Sent To  
Notes
2014-11-18 11:54:34NO CHANGE IN OCCUPANCY.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-04-04 Cont ID  
Sent By hmoser Date 2015-04-04 Time 11:25 Rev Time 0.00
Received By hmoser Date 2015-04-04 Time 10:31 Sent To  
Notes
2015-04-04 11:25:01REFER TO SECTION 603.5 NONMETALLIC DUCTS. DO NOT
 PAINT FIBERGLASS OR FLEX DUCT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-02-09 Cont ID  
Sent By tklarge Date 2015-02-07 Time 04:19 Rev Time 0.00
Received By hmoser Date 2015-02-09 Time 08:27 Sent To  
Notes
2015-02-09 09:32:37PLAN DENIED
 1) SEPARATE APPLICATION,PLAN AND PERMIT REQUIRED FOR
 HOODS AND COOLERS.
 2) REFER TO SECTION 603.5 NON METALLIC DUCT.
 FYI DO NOT PAINT FIBERGLASS OR FLEX DUCT. 1210
 FBC (M)
 3) PROVIDE DUCT SIZE AND LOUVER SIZE ON THE PLAN
 FOR OUTSIDE AIR DUCT. SECTION 107 FBC 2010
 4) REFER TO SECTION 503.2.5.4 SHUTOFF DAMPER
 CONTROLS FLORIDA ENERGY CODE 2010
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-02-02 Cont ID  
Sent By   Date 2015-02-02 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2015-02-02 16:45:39SEE ELECTRICAL PLAN REVIEW NOTE AND FRONT SCREEN
 2/2/2015. DAH

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-03 Cont ID  
Sent By rbergsma Date 2014-12-03 Time   Rev Time 1.00
Received By rbergsma Date 2014-12-03 Time   Sent To  
Notes
2014-12-03 11:20:50THE OCCUPANCY #'S STATED DO NOT AGREE WITH THE
 VENTILATION SCHEDULE ON M1.1
 PLEASE CLARIFY THE NEED FOR ADDITIONAL A/C TONNAGE ON
 THE ENERGY CALC'S
 ANY ADDED SERVICABLE EQUIPTMENT ON THE ROOF WILL BE
 SUBJECT TO FBC 304.11 BELOW:
  
 304.11 GUARDS.
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT,
 FANS OR OTHER COMPONENTS THAT REQUIRE SERVICE AND ROOF
 HATCH OPENINGS ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND
 EACH END OF SUCH APPLIANCES, EQUIPMENT, FANS,
 COMPONENTS AND ROOF HATCH OPENINGS AND THE TOP OF THE
 GUARD SHALL BE LOCATED NOT LESS THAN 42 INCHES (1067
 MM) ABOVE THE ELEVATED SURFACE ADJACENT TO THE GUARD.
 THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE
 PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE AND SHALL
 COMPLY WITH THE LOADING REQUIREMENTS FOR GUARDS
 SPECIFIED IN THE FLORIDA BUILDING CODE, BUILDING.
  
 REVIEW THE SHAFT WALL CLEARANCES ON A2.3 DETAIL 4 WITH
 REGARD TO FBC-M 506.3.10 THRU 506.3.10.2 BELOW:
  
 506.3.10 GREASE DUCT ENCLOSURES.
 A GREASE DUCT SERVING A TYPE I HOOD THAT PENETRATES A
 FIRE-RATED CEILING, FIRE-RATED WALL OR FLOOR SHALL BE
 ENCLOSED FROM THE POINT OF PENETRATION TO THE OUTLET
 TERMINAL. A DUCT SHALL PENETRATE EXTERIOR WALLS ONLY AT
 LOCATIONS WHERE UNPROTECTED OPENINGS ARE PERMITTED BY
 THE FLORIDA BUILDING CODE, BUILDING. THE DUCT ENCLOSURE
 SHALL SERVE A SINGLE GREASE DUCT AND SHALL NOT CONTAIN
 OTHER DUCTS, PIPING OR WIRING SYSTEMS. DUCT ENCLOSURES
 SHALL BE EITHER FIELD-APPLIED OR FACTORY-BUILT. DUCT
 ENCLOSURES SHALL HAVE A FIRE-RESISTANCE RATING NOT LESS
 THAN THAT OF THE FLOOR ASSEMBLY PENETRATED, BUT NEED
 NOT EXCEED 2 HOURS. DUCT ENCLOSURES SHALL BE AS
 PRESCRIBED BY SECTION 506.3.10.1, 506.3.10.2 OR
 506.3.10.3. THE ENCLOSURE SHALL BE SEPARATED FROM THE
 DUCT BY A MINIMUM OF 6 INCHES (152 MM) AND A MAXIMUM OF
 12 INCHES (305MM) AND SHALL SERVE A SINGLE GREASE
 EXHAUST DUCT SYSTEM.
  
 506.3.10.1 SHAFT ENCLOSURE.
 COMMERCIAL KITCHEN GREASE DUCTS CONSTRUCTED IN
 ACCORDANCE WITH SECTION 506.3.1 SHALL BE PERMITTED TO
 BE ENCLOSED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING REQUIREMENTS FOR SHAFT CONSTRUCTION.
 SUCH GREASE DUCT SYSTEMS AND EXHAUST EQUIPMENT SHALL
 HAVE A CLEARANCE TO COMBUSTIBLE CONSTRUCTION OF NOT
 LESS THAN 18 INCHES (457 MM), AND SHALL HAVE A
 CLEARANCE TO NONCOMBUSTIBLE CONSTRUCTION AND GYPSUM
 WALLBOARD ATTACHED TO NONCOMBUSTIBLE STRUCTURES OF NOT
 LESS THAN 6 INCHES (76 MM). DUCT ENCLOSURES SHALL BE
 SEALED AROUND THE DUCT AT THE POINT OF PENETRATION AND
 VENTED TO THE OUTSIDE OF THE BUILDING THROUGH THE USE
 OF WEATHER-PROTECTED OPENINGS.
  
 506.3.10.2 FIELD-APPLIED GREASE DUCT ENCLOSURE.
 COMMERCIAL KITCHEN GREASE DUCTS CONSTRUCTED IN
 ACCORDANCE WITH SECTION 506.3.1 SHALL BE ENCLOSED BY A
 FIELD-APPLIED GREASE DUCT ENCLOSURE THAT IS A LISTED
 AND LABELED MATERIAL, SYSTEM, PRODUCT OR METHOD OF
 CONSTRUCTION SPECIFICALLY EVALUATED FOR SUCH PURPOSE IN
 ACCORDANCE WITH ASTM E 2336. THE SURFACE OF THE DUCT
 SHALL BE CONTINUOUSLY COVERED ON ALL SIDES FROM THE
 POINT AT WHICH THE DUCT ORIGINATES TO THE OUTLET
 TERMINAL. DUCT PENETRATIONS SHALL BE PROTECTED WITH A
 THROUGH-PENETRATION FIRESTOP SYSTEM CLASSIFIED AND
 INSTALLED AS TESTED IN ACCORDANCE WITH ASTM E 814 OR UL
 1479 AND HAVING AN ?F? AND ?T? RATING OF NOT LESS THAN
 1 HOUR, BUT NOT LESS THAN THE FIRE-RESISTANCE RATING OF
 THE ASSEMBLY BEING PENETRATED. SUCH SYSTEMS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE LISTING AND THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS. EXPOSED DUCT
 WRAP SYSTEMS SHALL BE PROTECTED WHERE SUBJECT TO
 PHYSICAL DAMAGE.

Review Stop P PLUMBING
Rev No 5 Status P Date 2015-04-11 Cont ID  
Sent By tlarge Date 2015-04-11 Time 08:39 Rev Time 0.00
Received By tklarge Date 2015-04-11 Time 06:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2015-03-07 Cont ID  
Sent By tklarge Date 2015-03-07 Time 03:15 Rev Time 0.00
Received By tklarge Date 2015-03-06 Time 06:07 Sent To  
Notes
2015-03-06 13:14:191) SHT. A2.2 - ELEVATION DETAILS #4 & 6 - THE GRAB BARS
 ARE TO BE MEASUERD TO THE TOP OF THE GRIPPING SURFACE
 FROM THE FLOOR, NOT TO THE CENTERLINE AS SHOWN. 2010
 FAC SEC.609.4.
 2) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE ZOELLER
 PUMP. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 3) SHT. P3.1 - THE MOP SINK (P-11) IS NOT SHOWN ON THE
 WATER RISER.CLARIFY.
 4) SHT.P3.1 - RISER #1 - SHOWS THE ICE MACHINE AND
 COOLER DISCHARGING TO THE GREASY WASTE SYSTEM. WASTES
 THAT DO NOT REQUIRE TREATMENT OR SEPARATION SHALL NOT
 DISCHARGE INTO ANY INTERCEPTOR OR SEPARATOR PER THE
 2010 FPC SEC.1003.2.
 5) SHT.P4.1 - DETAIL #10 - THE DETAIL FOR THE GREASE
 INTERCEPTOR IS NOT FOR A SCHIER TANK. DELETE THIS
 SPECIFICATION FROM THE PLANS AND INCLUDE THE SUBMITTED
 SPECIFICATION FOR THE SCHIER INTERCEPTOR ON THE PLANS
 OR SUBMIT 2 COPIES OF THE SPEC FOR THE SCHIER TANK.ONLY
 ONE COPY WAS SUBMITTED.
 6) THE CALCULATIONS FOR THE SIZING OF THE SCHIER
 INTERCEPTOR DO NOT APPEAR TO BE IN COMPLIANCE WITH THE
 METHOD RECOMMENDED BY SCHIER SCHIER RECOMMENDS THAT THE
 DRAINAGE SYSTEM FLOW RATE BE DETERMINED BY THE SIZE OF
 THE INTERCEPTOR'S INLET PIPE (STEP #1).
 THEN CALCULATE GREASE CAPACITY AFTER SIZING FOR FLOW
 RATE. I DO NOT SEE THE FLOW RATE CALCULATIONS ON SHT.
 P1.1. THE DAYS FOR PUMP OUT CYCLE IN SCHIER'S CATALOG
 IS 30, 60 & 90. THERE IS NO 45 DAY PUMP OUT CYCLE.
 CLARIFY.
 7) THE CALCULATIONS FOR THE SIZING OF THE SCIER
 INTERCEPTOR SHOULD BE VERIFIED BY A SCHIER
 REPRESENTATIVE TO CONFIRM THE SIZING IS CORRECT. YOU
 CAN CONTACT THE REPRESENTATIVE AT 1-800-538-4792.
 8) PUMPS CONNECTED TO THE DRAINAGE SYSTEM SHALL BE
 CONNECTED IN ACCORDANCE WITH THE 2010 FPC
 SEC.712.3.5.PROVIDE A DETAIL AS TO HOW THE PUMP
 DISCHARGE LINE IS CONNECTED TO THE SANITARY SYSTEM OR
 REFER TO THIS CODE SECTION ON THE PLAN.
 9) THE HYDRO-MECHANICAL INTERCEPTORS FROM SCHIER HAVE
 FLOW CONTROLS THAT MUST BE VENTED IN ACCORDANCE WITH
 2010 FPC SEC.1003.3.4.2. EACH INTERCEPTOR SHALL BE
 EQUIPPED WITH A VENT FOR THE FLOW CONTROLS. SHOW THE
 LOCATION AND SIZE OF THE VENTS ON SHT.P1.1 AND ON THE
 SSANITARY RISER ON SHT.P3.1. THE FLOW CONTROL DEVICE
 SHALL BE VENTED AND TERMINATE NOT LESS THAN SIX (6)
 INCHES ABOVE THE FLOOD RIM LEVEL OR BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS PER THE
 2010 FPC SEC;1003.3.4.2.
 10) SUMP VENT SHALL RISE VERTICALLY A MINIMUM OF 6
 INCHES ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST TRAP OR
 TRAPPED FIXTURE BEING VENTED PRIOR TO OFFSETTING PER
 2010 FPC SEC.905.4, 905.5.
 11) THE LOCATION OF THE CHECK VALVE AND FULL OPEN VALVE
 FOR THE SUMP PUMP SHALL BE LOCATED ABOVE THE SUMP COVER
 OR UNDERGROUND OUTSIDE OF THE SUMP PIT AS REQUIRED PER
 THE 2010 FPC SEC.712.2,
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-02-07 Cont ID  
Sent By hmoser Date 2015-02-07 Time 04:18 Rev Time 0.00
Received By tklarge Date 2015-02-07 Time 03:04 Sent To M
Notes
2015-02-07 03:41:341) SHT.P1.1 -GREASE INTERCEPTOR SIZING CALCULATIONS -
 THE GREASE INTERCEPTOR SIZING CALCULATIONS SHOW A
 CAPACITY REQUIREMENT OF 2100 GALLONS. SHOW THE SIZE OF
 THE EXISTING GREASE INTERCEPTOR(S) ON THE PLANS TO
 CONFIRM THAT THE EXISTING INTERCEPTOR(S) HAVE THE
 CAPACITY TO SEPARATE THE THE GREASY WASTE AND FUNCTION
 IN THE MANNER DESIGNED TO ELIMINATE GREASE INTO THE
 SANITARY SYSTEM. SIZE OF GREASE INTERCEPTORS SHALL
 COMPLY WITH THE 2010 FBC-PLUMBING SECS.1003.1,
 1003.5.1.NOTE: THE MAXIMUM VOLUME OF AN INDIVIDUAL
 GREASE INTERCEPTOR CHAMBER SHALL BE 1,250 GALLONS. WHEN
 THE REQUIRED EFFECTIVE CAPACITY OF THE GREASE
 INTERCEPTOR IS GREATER THAN 1250 GALLONS, INSTALLATION
 OF MULTI - CHAMBERED GREASE INTERCEPTORS OR GREASE
 INTERCEPTORS IN SERIES IS REQUIRED. 3RD REQUEST,
 2) IDENTIFY ON THE PLANS THE LOCATION OF THE EXISTING
 GREASE INTERCEPTORS. THIS INFORMATION MAY BE OBTAINED
 FROM CITY PLACE ADMINISTRATION OR YOU CAN CONTACT
 SANDRA FELICIANO IN THE CITY OF WPB UTILITIES DEPT. WHO
 MAY HAVE SOME INFORMATION. MS. FELICIANO'S PHONE NUMBER
 IS 561-822-2171.
 3) INDICATE THE TYPE OF THE EXISTING INTERCEPTOR(S) ARE
 THEY THE CONCRETE VAULT TYPE OR HYDROMECHANICAL? IF
 HYDROMECHANICAL THEN THE SIZING EQUATION IN TABLE
 1003.5.1 CANNOT BE USED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-01-17 Cont ID  
Sent By tklarge Date 2015-01-17 Time 11:22 Rev Time 0.00
Received By tklarge Date 2015-01-17 Time 09:09 Sent To  
Notes
2015-01-17 11:22:261) THE GREASE INTERCEPTOR SIZING CALCULATIONS ON
 SHT.P1.1 SHOW A CAPACITY REQUIREMENT OF 2100 GALLONS.
 SHOW THE SIZE OF THE EXISTING GREASE INTERCEPTOR(S) ON
 THE PLANS TO CONFIRM THE EXISTING GREASY WASTE SYSTEM
 IS ADEQUATE FOR THIS RESTAURANT. NOTE: THE MAXIMUM
 CAPACITY OF A SINGLE GREASE INTERCEPTOR IS 1250 GALS.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1. & 2010 FPC
 SEC.1003.5.1.
 2) THE REVISED SHEETS SHALL BE INSERTED INTO THE
 EXISTING SET TO MAKE 2 COMPLETE SETS OF PLANS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-22 Cont ID  
Sent By tklarge Date 2014-11-22 Time 11:33 Rev Time 0.00
Received By tklarge Date 2014-11-22 Time 09:48 Sent To  
Notes
2014-11-22 11:32:551)SUBMIT THE CORRECT OCCUPANT LOAD FOR THE SPACE. SHT.
 A2.0 SHOWS THREE DIFFERENT NUMBERS (248, 236, 172 ).
 THE MINIMUM SANITARY FACILITIES WILL BE BASED ON THE
 CORRECT OCCUPANT LOAD.
 2) SHT. A2.2 - ELEVS. #4 & # 8 - SUBMIT ELEVATIONS
 WHERE THE DIMENSIONS CAN BE CLEARLY READ. WPB AMEND. TO
 2010 FBC SEC.107.2.1.
 3) KNEE AND TOE CLEARANCES FOR THE LAVATORIES SHALL
 COMPLY WITH 2010 FAC SEC.306.SHOW THIS ON THE PLANS.
 4) SHT. P1.1 - REFERENCE IS MADE TO THE 2007 FLORIDA
 BUILDING CODE. THE CODE IN EFFECT IS THE 2010 FBC.
 5) SHTS.P1.1 & P3.1 - IDENTIFY THE EXISTING GREASE
 WASTE LINE AND THE FIXTURES THAT ARE DISCHARGING INTO
 IT. 2010 FPC SEC.1003.3.1.
 6) SUBMIT A SITE PLAN SHOWING THE LOCATION OF THE
 EXISTING GREASE INTERCEPTOR AND THE SIZE OF THE GREASE
 INTERCEPTOR. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 7) SUBMIT SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR TO ENSURE THE CAPACITY IS ENOUGH FOR THIS
 APPLICATION.FPC SEC.1003.2
 8) SHT. P3.1 - SIZE THE WASTE STACK FOR THE URINAL.WPB
 AMEND. TO 2010 FBC SEC.107.2.1.
 9)THE WATER CLOSET IN THE WOMEN'S RESTROOM IS BEING WET
 VENT WHICH PLACES THE URINAL ON A WET VENT WHICH IS NOT
 PERMITTED PER THE FPC SEC.909.1.
 10) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED
 PER THE 2010 FGC SEC. 301.3.
 11) SHT.P3.1 - THE TYPICAL GAS EQUIPMENT CONNECTION
 SHOWS A SYMBOL FOR A MEDIUM PRESSURE REGULATOR AND
 THERE APPEARS TO BE A MPR AT EACH APPLIANCE BUT THE
 NOTE STATES IT IS LESS THAN A 2 PSI SYSTEM. CLARIFY.
 12)SHT. P3.1 - THE GAS LINE GOES FROM 1" TO 2".
 CLARIFY.
 13) PROVIDE FOR THERMAL EXPANSION OF THE HOT WATER
 SYSTEM PER FPC SEC.607.3.
 14) EQUIPMENT K-14 IS SHOWN ON THE FLOOR PLAN BUT NOT
 ON THE EQUIPMENT SCHEDULE OR RISER. CLARIFY.
 15) THE BEVERAGE DISPENSERS SHALL BE EQUIPPED WITH
 BACKFLOW PREVENTERS TO PREVENT CARBON DIOXIDE FROM
 ENTERING THE WATER LINES. FPC SEC. 608.16.1.
 16) COFFE MACINES AND NON-CARBONATED BEVERAGE
 DISPENSERS SHALL BE PROTECTED AGAINST BACKFLOW PER FPC
 SEC.608.16.10.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-11-20 Cont ID  
Sent By eschneid Date 2014-11-20 Time 13:08 Rev Time 0.25
Received By eschneid Date 2014-11-20 Time 13:08 Sent To  
Notes
2014-11-14 12:28:4611/14/14