Plan Review Details - Permit 14110342
Plan Review Stops For Permit 14110342
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-11-17 Cont ID  
Sent By rmcdouga Date 2014-11-17 Time 15:16 Rev Time 0.00
Received By rmcdouga Date 2014-11-17 Time 15:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-11-14 Cont ID  
Sent By shill Date 2014-11-14 Time 16:40 Rev Time 0.00
Received By shill Date 2014-11-14 Time 16:40 Sent To  
Notes
2014-11-14 16:42:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE SHUTTER INSTALLATION SCHEDULE SUBMITTED HAS
 "CONC BLOCK" FOR SUBSTRATE AND ELCO PANEL MATE FOR
 FASTENER. SEE ANCHOR CHART ON SHEET 4. HORIZONTAL
 INSTALLATIONS HAVE A BLOCK SUBSTRATE (FILLED CELLS ARE
 BLOCK, NOT CONCRETE). VERTICAL INSTALLATIONS USUALLY
 HAVE CONCRETE TOP, BLOCK BOTTOM. THE FASTENER SELECTED
 CANNOT BE USED WITH A BLOCK SUBSTRATE.
  
 FBC 2010 RESIDENTIAL 301.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-08 Cont ID  
Sent By shill Date 2014-11-08 Time 11:30 Rev Time 0.00
Received By shill Date 2014-11-08 Time 11:30 Sent To  
Notes
2014-11-08 11:37:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A FLOOR PLAN WHICH SHOWS PROPOSED LOCATIONS
 OF PROPOSED NEW SHUTTERS, FBC 107. A PLAN WAS PROVIDED
 BUT THE OPENINGS ARE NOT NUMBERED TO CORRELATE WITH THE
 INSTALLATION SCHEDULE.
  
 2. THE SHUTTER INSTALLATION SCHEDULE IS INCOMPLETE.
 PROVIDE SPAN AND SHUTTER GLASS SEPARATION AND SELECT
 ONE SHUTTER CONNECTION MOUNTING TYPE. I HAD PROVIDED
 THE INFORMATION WHICH CONTRACTORS FIND MOST DIFFICULT
 TO COMPLETE. CONTRACTOR IS TO PROVIDE THE REMAINING
 INFORMATION WITH THE EXCEPTION OF WALL PRESSURES
 (COLUMN 3) AND THE LAST COLUMN. THE EXAMPLE I GAVE WAS
 AN EXAMPLE. I PROVIDED WORST CASE FOR C1 AND C2. PLEASE
 PROVIDE AN INSTALLATION SCHEDULE WHICH SPECIFIES WHICH
 ONE OF THE TWO METHODS WILL BE INSTALLED; FBC 107, FBC
 2010 RESIDENTIAL 301.
  
 3. IMPACT DOOR PRODUCT APPROVALS WERE PROVIDED. FOR
 THIS SHUTTER PERMIT, ONLY SHUTTER INFORMATION IS
 REQUIRED. THE DOOR PRODUCT APPROVALS SHOULD BE INCLUDED
 EITHER IN THE ORIGINAL PERMIT APPLICATION OR THE
 PENDING REVISION #14110277.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-14 Cont ID  
Sent By shill Date 2014-11-14 Time 16:42 Rev Time 0.00
Received By shill Date 2014-11-12 Time 09:03 Sent To  
Notes
2014-11-13 09:04:04RE-SUBMITTAL SENT TO SAMANTHA HILL FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-08 Cont ID  
Sent By shill Date 2014-11-08 Time 11:37 Rev Time 0.00
Received By shill Date 2014-11-07 Time 16:21 Sent To  
Notes
2014-11-07 16:21:4111/7 TO SH DESK WITH REVISION 14110277
2014-11-07 11:22:10ROUTED TO BUILDING LESS THAN 5000