Plan Review Details - Permit 14110235
Plan Review Stops For Permit 14110235
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-12-04 Cont ID  
Sent By scaldero Date 2014-12-04 Time 11:20 Rev Time 0.00
Received By scaldero Date 2014-12-04 Time 11:20 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-11-10 Cont ID  
Sent By scaldero Date 2014-11-10 Time 11:33 Rev Time 0.00
Received By scaldero Date 2014-11-10 Time 11:24 Sent To M
Notes
2014-11-10 11:33:30PERMIT #14110235
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REVIEW FAILED:
 1) 2 COPIES OF ALL SUBMITTED PLANS SHEETS AND DATA
 SHEETS MUST BE SUBMITTED. ONLY 1 COPY PROVIDED.
 2) PER FBC 904.11.1, A MANUAL ACTIVATION DEVICE SHALL
 BE LOCATED ALONG THE EGRESS PATH AND BE A MINIMUM OF 10
 FEET AND A MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST
 SYSTEM. THIS IS NOT OUTLINED IN NARRATIVE, NOR IS IT
 INDICATED ON THE LAYOUT SHEET SUBMITTED.
 3) LAYOUT SHEET PROVIDED IS NOT CLEAR ON ACTUAL
 APPLIANCES USED AND THEIR LOCATIONS/LAYOUT IN REFERENCE
 TO KITCHEN SETUP. A BETTER LAYOUT SHEET NEEDS TO BE
 PROVIDED, THAT SHOWS THE APPLIANCES, THEIR LAYOUT, AND
 THE KITCHEN LAYOUT. PLAN SHOULD INDICATE LOCATION OF
 MANUAL ACTIVATION DEVICE, CLASS K EXTINGUISHER, ETC.
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-04 Cont ID  
Sent By scaldero Date 2014-12-04 Time 11:20 Rev Time 0.00
Received By scaldero Date 2014-11-24 Time 11:28 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-21 Cont ID  
Sent By hmoser Date 2014-11-21 Time 14:46 Rev Time 0.00
Received By hmoser Date 2014-11-05 Time 18:25 Sent To  
Notes
2014-11-05 18:25:51ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-11-26 Cont ID  
Sent By hmoser Date 2014-11-26 Time 14:32 Rev Time 0.00
Received By hmoser Date 2014-11-26 Time 14:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-11-21 Cont ID  
Sent By hmoser Date 2014-11-21 Time 14:46 Rev Time 0.00
Received By hmoser Date 2014-11-19 Time 14:43 Sent To  
Notes
2014-11-21 14:46:19PLAN DENIED
 . PROVIDE MORE INFORMATION ON THE
 PYRO CHEM SUPPRESSION SYSTEM.
 PER SECTION 107 FBC 2010
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676