Plan Review Details - Permit 14110234
Plan Review Stops For Permit 14110234
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-06-26 Cont ID  
Sent By jwitmer Date 2015-06-26 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2015-06-26 Time 06:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-22 Cont ID  
Sent By jwitmer Date 2015-04-22 Time   Rev Time 0.00
Received By jwitmer Date 2015-04-22 Time   Sent To  
Notes
2015-04-22 16:55:02BUILDING PLAN REVIEW
 PERMIT: 14110234
 ADD: 5200 BAYWINDS DR.
 CONT: TBD
 TEL: (561)791-3155
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. APRIL 22/ 2015
 ACTION: DENIED
  
 1) THE PLANS (FLOOR PLAN) SUBMITTED INDICATE THE
 PROPOSED WORK, THERE WERE NO PLANS SUBMITED WITH THE
 EXISTING CONDITION OR DEMOLITION PLANS. THE PERRMIT
 APPLICATION INDICATES TO BUILD A STORAGE ADDITION. THE
 PLANS SUBMITTED ARE CONCEPTUAL IN NATURE.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN;
 SITE PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR
 TRUSS LAYOUT; ALL FENESTRATION PENETRATIONS; FLASHING;
 AND ROUGH OPENING DIMENSIONS; AND ALL EXTERIOR
 ELEVATIONS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
  
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS,FLOOD REQUIREMENTS IN ACCORDANCE WITH
 SECTION 1612, INCLUDING LOWEST FLOOR
 ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT
 MATERIALS
 FLOOD ZONE CERTIFICATES
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
  
 2) STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS
 1803.5.2 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION,
 STRENGTH OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR
 WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED
 IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
  
 3) ROOF SYSTEMS SHEET 1 THE TRUSS DETAIL SHOWS A TRUSS
 MARKED # 1 WITH 500 LBS UPLIFT AND 40 LATERAL OADS, THE
 CONNECTION SCHEDULE LACKS THE TIE DOWN INFORMATION THAT
 THE GIRDER THAT THE COMMON TRUSSES TIE INTO.
 THE TYPICAL WALL SECTION ALSO IS MISSING THE GIRDER AND
 THE TYPE OF CONNECTION THE TOP AND BOTOM CHORDS OF THE
 COMMON JACKS CONNECT WITH. 107.2.1.3 ADDITIONAL
 INFORMATION. THIS ROOF FRAMING IS PART OF THE MAIN WIND
 FORCE RESISTING SYSTEM.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-18 Cont ID  
Sent By jwitmer Date 2014-11-18 Time 07:07 Rev Time 0.00
Received By jwitmer Date 2014-11-18 Time 06:45 Sent To  
Notes
2014-11-18 07:07:08BUILDING PLAN REVIEW
 PERMIT: 14110234
 ADD: 5200 BAYWINDS DR.
 CONT: TBD
 TEL: (561)791-3155
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 18/ 2014
 ACTION: DENIED
  
 1) THE PLANS (FLOOR PLAN) SUBMITTED INDICATE THE
 PROPOSED WORK, THERE WERE NO PLANS SUBMITED WITH THE
 EXISTING CONDITION OR DEMOLITION PLANS. THE PERRMIT
 APPLICATION INDICATES TO BUILD A STORAGE ADDITION. THE
 PLANS SUBMITTED ARE A CONCEPT OF THE SCOPE OF WORK, NOT
 WORKING PLANS THAT CAN BE REVIEWED FOR CODE COMPLIANCE.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN;
 SITE PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR
 TRUSS LAYOUT; ALL FENESTRATION PENETRATIONS; FLASHING;
 AND ROUGH OPENING DIMENSIONS; AND ALL EXTERIOR
 ELEVATIONS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 PRE-ENGINEERED SYSTEMS
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS
 TERMITE PROTECTION
 DESIGN LOADS
 WIND REQUIREMENTS
 BUILDING ENVELOPE
 FOUNDATION
 FLOOD REQUIREMENTS IN ACCORDANCE WITH SECTION 1612,
 INCLUDING LOWEST FLOOR
 ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT
 MATERIALS
 WALL SYSTEMS
 FLOOR SYSTEMS
 ROOF SYSTEMS
 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-06-24 Cont ID  
Sent By lmarchan Date 2015-08-18 Time 15:49 Rev Time 0.00
Received By dhayes Date 2015-06-24 Time 12:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-04-10 Cont ID  
Sent By dhayes Date 2015-04-10 Time 09:34 Rev Time 0.00
Received By dhayes Date 2015-04-10 Time 09:34 Sent To  
Notes
2015-04-10 09:34:354/10/2015
 PROJECT: 5200 BAYWINDS DR
 PERMIT#: 14110234
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 DUPLICATE COMMENTS:
  
 1) PROVIDE TWO COMPLETE SETS OF ELECTRICAL PLANS AND
 SPECIFICATIONS TO INCLUDE BUT NOT BE LIMITED TO THE
 FOLLOWING:
 A) ELECTRICAL FLOOR PLAN TO INDICATE THE LOCATION OF
 THE ADDITION, ELECTRICAL SERVICE, PANEL, OUTLETS, AND
 EQUIPMENT. INDICATE WHICH ARE EXISTING AND WHICH ARE
 NEW, WIRE SIZES WIRING METHODS ETC...
 B) ELECTRICAL LIGHTING PLAN TO INDICATE ADDITION,
 GENERAL, EXIT AND EMERGENCY LIGHTING AND LIGHTING
 CONTROL. INDCATE WHICH ARE EXISTING AND WHICH ARE NEW,
 WIRE AND CONDUIT SIZES WIRING METHODS ETC...
 C) ENERGY CALCULATIONS, LOAD CALCULATIONS, PANEL
 SCHEDULE(S) AND LINE DIAGRAM TO INDICATE ALL CIRCUITS,
 INDCATE WHICH ARE EXISTING AND WHICH ARE NEW.
 D) MANUFACTURER PRODUCT DATA SHEETS FOR ALL APPLIANCES
 THAT INCLUDE THE MODEL NUMBER, LISTING INFORMATION, AND
 ELECTRICAL SPECIFICATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-11-06 Cont ID  
Sent By dhayes Date 2014-11-06 Time 10:58 Rev Time 0.00
Received By dhayes Date 2014-11-06 Time 10:58 Sent To  
Notes
2014-11-06 11:36:1111/6/2014
 PROJECT: 5200 BAYWINDS DR
 PERMIT#: 14110234
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE TWO COMPLETE SETS OF ELECTRICAL PLANS AND
 SPECIFICATIONS TO INCLUDE BUT NOT BE LIMITED TO THE
 FOLLOWING:
 A) ELECTRICAL FLOOR PLAN TO INDICATE THE LOCATION OF
 THE ADDITION, ELECTRICAL SERVICE, PANEL, OUTLETS, AND
 EQUIPMENT. INDCATE WHICH ARE EXISTING AND WHICH ARE
 NEW, WIRE SIZES WIRING MEATHODS ETC... .
 B) ELECTRICAL LIGHTING PLAN TO INDICATE ADDITION,
 GENERAL, EXIT AND EMERGENCY LIGHTING AND LIGHTING
 CONTROL. INDCATE WHICH ARE EXISTING AND WHICH ARE NEW,
 WIRE AND CONDUIT SIZES WIRING MEATHODS ETC...
 C) ENERGY CALCULATIONS, LOAD CALCULATIONS, PANEL
 SCHEDULE(S) AND LINE DIAGRAM TO INDICATE ALL CIRCUITS,
 INDCATE WHICH ARE EXISTING AND WHICH ARE NEW.
 D) MANUFACTURER PRODUCT DATA SHEETS FOR ALL APPLIANCES
 THAT INCLUDE THE MODEL NUMBER, LISTING INFORMATION, AND
 ELECTRICAL SPECIFICATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-06-29 Cont ID  
Sent By scaldero Date 2015-06-29 Time 14:58 Rev Time 0.00
Received By scaldero Date 2015-06-29 Time 14:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-05-04 Cont ID  
Sent By scaldero Date 2015-05-04 Time 14:48 Rev Time 0.00
Received By scaldero Date 2015-05-04 Time 14:48 Sent To  
Notes
2015-05-04 14:49:49PERMIT # 14110234
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY
 THE FIRE DEPARTMENT AFTER COMMENTS BY ALL PLAN
 REVIEWERS HAVE BEEN SATISFIED.
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-11-10 Cont ID  
Sent By scaldero Date 2014-11-10 Time 11:59 Rev Time 0.00
Received By scaldero Date 2014-11-10 Time 11:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-08-20 Cont ID  
Sent By jwitmer Date 2015-08-20 Time 16:25 Rev Time 0.00
Received By jwitmer Date 2015-08-18 Time 15:49 Sent To  
Notes
2015-08-18 15:49:55RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-08-18 Cont ID  
Sent By dhayes Date 2015-07-10 Time 15:49 Rev Time 0.00
Received By lmarchan Date 2015-06-23 Time   Sent To E
Notes
2015-06-24 12:21:48B22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-16 Cont ID  
Sent By hmoser Date 2015-05-16 Time 10:58 Rev Time 0.00
Received By hmoser Date 2015-03-16 Time   Sent To  
Notes
2015-03-17 06:28:10SENT TO B23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-02 Cont ID  
Sent By skennedy Date 2014-12-02 Time 13:03 Rev Time 0.00
Received By skennedy Date 2014-11-05 Time 11:41 Sent To  
Notes
2014-11-06 11:40:42B02

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-08-21 Cont ID  
Sent By ccole Date 2015-08-21 Time 17:17 Rev Time 0.00
Received By ccole Date 2015-08-21 Time 17:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-07-10 Cont ID  
Sent By hmoser Date 2015-07-10 Time 06:44 Rev Time 0.00
Received By ccole Date 2015-07-09 Time 07:18 Sent To  
Notes
2015-07-09 07:36:383RD REVIEW: FBC 2010 MECHANICAL
 7/9/2015
  
 1) PROVIDE A MEANS OF VENTILATION FOR THE NEW STORAGE
 ROOM- TABLE 403.3 FBC-10 MECHANICAL.
 2) THE NEW HVAC PLAN INDICATES 8"X8" CEILING REGISTERS
 IN THE CATERING KITCHEN, HOWEVER THE PARTIAL MEP PLAN
 ON SHEET 2 INDICATES 2'X2' DIFFUSERS: PLEASE CORRECT.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-05-16 Cont ID  
Sent By hmoser Date 2015-05-16 Time 10:57 Rev Time 0.00
Received By hmoser Date 2015-05-16 Time 10:43 Sent To  
Notes
2015-05-16 10:57:16PLAN DENIED
 APPLICATION SHOWS NO MECHANICAL. PAGE 2
 OF THE PLAN SHOWS TWO NEW AIR CONDITIONING DROPS.
 PROVIDE A PLAN SHOWING THE EXISTING DUCT
 AND PROVIDE GRILL SIZE DUCT SIZE AND CFM
 OF NEW DUCT.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-02 Cont ID  
Sent By rbergsma Date 2014-12-02 Time   Rev Time 0.75
Received By rbergsma Date 2014-12-02 Time   Sent To  
Notes
2014-12-02 09:46:12THIS IS A COMMERCIAL BUILDING AND THIS OVEN CAN PRODUCE
 HEAT, ODORS AND SMOKE, PLEASE REVIEW THESE SECTIONS OF
 THE FLORIDA MECHANICAL CODE 2010
  
 502.1 GENERAL.
 AN EXHAUST SYSTEM SHALL BE PROVIDED, MAINTAINED AND
 OPERATED AS SPECIFICALLY REQUIRED BY THIS SECTION AND
 FOR ALL OCCUPIED AREAS WHERE MACHINES, VATS, TANKS,
 FURNACES, FORGES, SALAMANDERS AND OTHER APPLIANCES,
 EQUIPMENT AND PROCESSES IN SUCH AREAS PRODUCE OR THROW
 OFF DUST OR PARTICLES SUFFICIENTLY LIGHT TO FLOAT IN
 THE AIR, OR WHICH EMIT HEAT, ODORS, FUMES, SPRAY, GAS
 OR SMOKE, IN SUCH QUANTITIES SO AS TO BE IRRITATING OR
 INJURIOUS TO HEALTH OR SAFETY.
  
 506.4 DUCTS SERVING TYPE II HOODS.
 506.4.1 DUCTS.
 506.4.2 TYPE II TERMINATIONS.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status P Date 2015-08-20 Cont ID  
Sent By jwitmer Date 2015-08-20 Time 16:25 Rev Time 0.00
Received By jwitmer Date 2015-08-20 Time   Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2015-06-26 Cont ID  
Sent By jwitmer Date 2015-06-26 Time 07:16 Rev Time 0.00
Received By jwitmer Date 2015-06-26 Time   Sent To  
Notes
2015-06-26 07:20:44BUILDING PLAN REVIEW
 PERMIT: 14110234
 ADD: 5200 BAYWINDS DR.
 CONT: TBD
 TEL: (561)791-3155
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRI. JUNE 26/ 2015
 ACTION: DENIED
  
 1) THE PLANS (FLOOR PLAN) SUBMITTED INDICATE THE
 PROPOSED WORK, THERE WERE NO PLANS SUBMITED WITH THE
 EXISTING CONDITION OR DEMOLITION PLANS. THE PERRMIT
 APPLICATION INDICATES TO BUILD A STORAGE ADDITION. THE
 PLANS SUBMITTED ARE CONCEPTUAL IN NATURE.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN;
 SITE PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR
 TRUSS LAYOUT; ALL FENESTRATION PENETRATIONS; FLASHING;
 AND ROUGH OPENING DIMENSIONS; AND ALL EXTERIOR
 ELEVATIONS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
  
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS,FLOOD REQUIREMENTS IN ACCORDANCE WITH
 SECTION 1612, INCLUDING LOWEST FLOOR
 ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT
 MATERIALS
 FLOOD ZONE CERTIFICATES
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2015-04-22 Cont ID  
Sent By   Date 2015-04-22 Time   Rev Time 0.00
Received By   Date 2015-04-22 Time   Sent To  
Notes
2015-06-26 07:19:06BUILDING PLAN REVIEW
 PERMIT: 14110234
 ADD: 5200 BAYWINDS DR.
 CONT: TBD
 TEL: (561)791-3155
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. APRIL 22/ 2015
 ACTION: DENIED
  
 1) THE PLANS (FLOOR PLAN) SUBMITTED INDICATE THE
 PROPOSED WORK, THERE WERE NO PLANS SUBMITED WITH THE
 EXISTING CONDITION OR DEMOLITION PLANS. THE PERRMIT
 APPLICATION INDICATES TO BUILD A STORAGE ADDITION. THE
 PLANS SUBMITTED ARE CONCEPTUAL IN NATURE.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN;
 SITE PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR
 TRUSS LAYOUT; ALL FENESTRATION PENETRATIONS; FLASHING;
 AND ROUGH OPENING DIMENSIONS; AND ALL EXTERIOR
 ELEVATIONS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
  
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS,FLOOD REQUIREMENTS IN ACCORDANCE WITH
 SECTION 1612, INCLUDING LOWEST FLOOR
 ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT
 MATERIALS
 FLOOD ZONE CERTIFICATES
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2014-11-18 Cont ID  
Sent By   Date 2014-11-18 Time   Rev Time 0.00
Received By   Date 2014-11-18 Time   Sent To  
Notes
2015-06-26 07:16:55BUILDING PLAN REVIEW
 PERMIT: 14110234
 ADD: 5200 BAYWINDS DR.
 CONT: TBD
 TEL: (561)791-3155
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: NOV. 18/ 2014
 ACTION: DENIED
  
 1) THE PLANS (FLOOR PLAN) SUBMITTED INDICATE THE
 PROPOSED WORK, THERE WERE NO PLANS SUBMITED WITH THE
 EXISTING CONDITION OR DEMOLITION PLANS. THE PERRMIT
 APPLICATION INDICATES TO BUILD A STORAGE ADDITION. THE
 PLANS SUBMITTED ARE CONCEPTUAL IN NATURE.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN;
 SITE PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR
 TRUSS LAYOUT; ALL FENESTRATION PENETRATIONS; FLASHING;
 AND ROUGH OPENING DIMENSIONS; AND ALL EXTERIOR
 ELEVATIONS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
  
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS,FLOOD REQUIREMENTS IN ACCORDANCE WITH
 SECTION 1612, INCLUDING LOWEST FLOOR
 ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT
 MATERIALS
 FLOOD ZONE CERTIFICATES
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
  
 2) STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS
 1803.5.2 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION,
 STRENGTH OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR
 WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED
 IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
  
 3) ROOF SYSTEMS SHEET 1 THE TRUSS DETAIL SHOWS A TRUSS
 MARKED # 1 WITH 500 LBS UPLIFT AND 40 LATERAL OADS, THE
 CONNECTION SCHEDULE LACKS THE TIE DOWN INFORMATION THAT
 THE GIRDER THAT THE COMMON TRUSSES TIE INTO.
 THE TYPICAL WALL SECTION ALSO IS MISSING THE GIRDER AND
 THE TYPE OF CONNECTION THE TOP AND BOTOM CHORDS OF THE
 COMMON JACKS CONNECT WITH. 107.2.1.3 ADDITIONAL
 INFORMATION. THIS ROOF FRAMING IS PART OF THE MAIN WIND
 FORCE RESISTING SYSTEM.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-07-10 Cont ID  
Sent By tlarge Date 2015-07-10 Time 04:18 Rev Time 0.00
Received By tklarge Date 2015-07-10 Time 04:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-05-09 Cont ID  
Sent By tklarge Date 2015-05-09 Time 05:35 Rev Time 0.00
Received By tklarge Date 2015-05-09 Time 05:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-11-22 Cont ID  
Sent By tklarge Date 2014-11-22 Time 06:38 Rev Time 0.00
Received By tklarge Date 2014-11-22 Time 06:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-06-30 Cont ID  
Sent By sgraham Date 2015-06-30 Time 15:16 Rev Time 0.00
Received By sgraham Date 2015-06-30 Time 15:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-11-18 Cont ID  
Sent By sgraham Date 2014-11-18 Time 13:07 Rev Time 0.00
Received By sgraham Date 2014-11-18 Time 13:07 Sent To  
Notes
2014-11-14 12:13:1011/14/14