Plan Review Details - Permit 14110234
| Plan Review Stops For Permit 14110234 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2015-06-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-06-26 |
Time |
07:30 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-06-26 |
Time |
06:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-04-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-04-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-04-22 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-04-22 16:55:02 | BUILDING PLAN REVIEW | | | PERMIT: 14110234 | | | ADD: 5200 BAYWINDS DR. | | | CONT: TBD | | | TEL: (561)791-3155 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: WED. APRIL 22/ 2015 | | | ACTION: DENIED | | | | | | 1) THE PLANS (FLOOR PLAN) SUBMITTED INDICATE THE | | | PROPOSED WORK, THERE WERE NO PLANS SUBMITED WITH THE | | | EXISTING CONDITION OR DEMOLITION PLANS. THE PERRMIT | | | APPLICATION INDICATES TO BUILD A STORAGE ADDITION. THE | | | PLANS SUBMITTED ARE CONCEPTUAL IN NATURE. | | | | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN | | | REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE | | | DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE | | | FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN; | | | SITE PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR | | | TRUSS LAYOUT; ALL FENESTRATION PENETRATIONS; FLASHING; | | | AND ROUGH OPENING DIMENSIONS; AND ALL EXTERIOR | | | ELEVATIONS: | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | 107.3.5.1.1 BUILDING | | | | | | FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD | | | ELEVATIONS,FLOOD REQUIREMENTS IN ACCORDANCE WITH | | | SECTION 1612, INCLUDING LOWEST FLOOR | | | ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT | | | MATERIALS | | | FLOOD ZONE CERTIFICATES | | | FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES | | | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD | | | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. | | | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS | | | REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION. | | | | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES | | | REQUIRED: | | | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE | | | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR | | | HEIGHT. | | | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND | | | ELEVATION CERTIFICATE IS REQUIRED | | | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE | | | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR | | | ATTENDANTS | | | A/C PADS OR OTHER SLABS FOR GENERATORS | | | FEMA FORM OMB NO. 1660-0008 EXPIRES: | | | JULY 31/2015 | | | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR | | | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. | | | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE | | | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: | | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | | | | | | 2) STRUCTURAL REQUIREMENTS SHALL INCLUDE: | | | SOIL CONDITIONS/ANALYSIS | | | 1803.5.2 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, | | | STRENGTH OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR | | | WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED | | | IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE | | | PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION | | | BE CONDUCTED. | | | | | | | | | 3) ROOF SYSTEMS SHEET 1 THE TRUSS DETAIL SHOWS A TRUSS | | | MARKED # 1 WITH 500 LBS UPLIFT AND 40 LATERAL OADS, THE | | | CONNECTION SCHEDULE LACKS THE TIE DOWN INFORMATION THAT | | | THE GIRDER THAT THE COMMON TRUSSES TIE INTO. | | | THE TYPICAL WALL SECTION ALSO IS MISSING THE GIRDER AND | | | THE TYPE OF CONNECTION THE TOP AND BOTOM CHORDS OF THE | | | COMMON JACKS CONNECT WITH. 107.2.1.3 ADDITIONAL | | | INFORMATION. THIS ROOF FRAMING IS PART OF THE MAIN WIND | | | FORCE RESISTING SYSTEM. | | | | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA | | | TUS.ASPX FOR PERMIT STATUS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-11-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-11-18 |
Time |
07:07 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-11-18 |
Time |
06:45 |
Sent To |
|
|
| Notes |
| 2014-11-18 07:07:08 | BUILDING PLAN REVIEW | | | PERMIT: 14110234 | | | ADD: 5200 BAYWINDS DR. | | | CONT: TBD | | | TEL: (561)791-3155 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: TUES. NOV. 18/ 2014 | | | ACTION: DENIED | | | | | | 1) THE PLANS (FLOOR PLAN) SUBMITTED INDICATE THE | | | PROPOSED WORK, THERE WERE NO PLANS SUBMITED WITH THE | | | EXISTING CONDITION OR DEMOLITION PLANS. THE PERRMIT | | | APPLICATION INDICATES TO BUILD A STORAGE ADDITION. THE | | | PLANS SUBMITTED ARE A CONCEPT OF THE SCOPE OF WORK, NOT | | | WORKING PLANS THAT CAN BE REVIEWED FOR CODE COMPLIANCE. | | | | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN | | | REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE | | | DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE | | | FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN; | | | SITE PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR | | | TRUSS LAYOUT; ALL FENESTRATION PENETRATIONS; FLASHING; | | | AND ROUGH OPENING DIMENSIONS; AND ALL EXTERIOR | | | ELEVATIONS: | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | 107.3.5.1.1 BUILDING | | | SET BACK/SEPARATION (ASSUMED PROPERTY LINES) | | | FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD | | | ELEVATIONS | | | 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS | | | SHALL BE DETERMINED. | | | 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED | | | (SEE TABLE 503). | | | 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL | | | INCLUDE THE FOLLOWING COMPONENTS: | | | FIRE-RESISTANT SEPARATIONS | | | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION | | | 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: | | | PRE-ENGINEERED SYSTEMS | | | 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL | | | INCLUDE THE FOLLOWING | | | REQUIREMENTS: | | | OCCUPANT LOAD AND EGRESS CAPACITIES | | | 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: | | | OCCUPANCY LOAD | | | GROSS | | | NET | | | MEANS OF EGRESS | | | EXIT ACCESS | | | EXIT | | | EXIT DISCHARGE | | | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION | | | DOORS | | | EMERGENCY LIGHTING AND EXIT SIGNS | | | 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: | | | SOIL CONDITIONS/ANALYSIS | | | TERMITE PROTECTION | | | DESIGN LOADS | | | WIND REQUIREMENTS | | | BUILDING ENVELOPE | | | FOUNDATION | | | FLOOD REQUIREMENTS IN ACCORDANCE WITH SECTION 1612, | | | INCLUDING LOWEST FLOOR | | | ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT | | | MATERIALS | | | WALL SYSTEMS | | | FLOOR SYSTEMS | | | ROOF SYSTEMS | | | 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE | | | FOLLOWING: | | | SITE REQUIREMENTS | | | ACCESSIBLE ROUTE | | | VERTICAL ACCESSIBILITY | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA | | | TUS.ASPX FOR PERMIT STATUS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2015-06-24 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2015-08-18 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-06-24 |
Time |
12:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2015-04-10 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-04-10 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-04-10 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2015-04-10 09:34:35 | 4/10/2015 | | | PROJECT: 5200 BAYWINDS DR | | | PERMIT#: 14110234 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | DUPLICATE COMMENTS: | | | | | | 1) PROVIDE TWO COMPLETE SETS OF ELECTRICAL PLANS AND | | | SPECIFICATIONS TO INCLUDE BUT NOT BE LIMITED TO THE | | | FOLLOWING: | | | A) ELECTRICAL FLOOR PLAN TO INDICATE THE LOCATION OF | | | THE ADDITION, ELECTRICAL SERVICE, PANEL, OUTLETS, AND | | | EQUIPMENT. INDICATE WHICH ARE EXISTING AND WHICH ARE | | | NEW, WIRE SIZES WIRING METHODS ETC... | | | B) ELECTRICAL LIGHTING PLAN TO INDICATE ADDITION, | | | GENERAL, EXIT AND EMERGENCY LIGHTING AND LIGHTING | | | CONTROL. INDCATE WHICH ARE EXISTING AND WHICH ARE NEW, | | | WIRE AND CONDUIT SIZES WIRING METHODS ETC... | | | C) ENERGY CALCULATIONS, LOAD CALCULATIONS, PANEL | | | SCHEDULE(S) AND LINE DIAGRAM TO INDICATE ALL CIRCUITS, | | | INDCATE WHICH ARE EXISTING AND WHICH ARE NEW. | | | D) MANUFACTURER PRODUCT DATA SHEETS FOR ALL APPLIANCES | | | THAT INCLUDE THE MODEL NUMBER, LISTING INFORMATION, AND | | | ELECTRICAL SPECIFICATIONS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-11-06 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-11-06 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-11-06 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2014-11-06 11:36:11 | 11/6/2014 | | | PROJECT: 5200 BAYWINDS DR | | | PERMIT#: 14110234 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE TWO COMPLETE SETS OF ELECTRICAL PLANS AND | | | SPECIFICATIONS TO INCLUDE BUT NOT BE LIMITED TO THE | | | FOLLOWING: | | | A) ELECTRICAL FLOOR PLAN TO INDICATE THE LOCATION OF | | | THE ADDITION, ELECTRICAL SERVICE, PANEL, OUTLETS, AND | | | EQUIPMENT. INDCATE WHICH ARE EXISTING AND WHICH ARE | | | NEW, WIRE SIZES WIRING MEATHODS ETC... . | | | B) ELECTRICAL LIGHTING PLAN TO INDICATE ADDITION, | | | GENERAL, EXIT AND EMERGENCY LIGHTING AND LIGHTING | | | CONTROL. INDCATE WHICH ARE EXISTING AND WHICH ARE NEW, | | | WIRE AND CONDUIT SIZES WIRING MEATHODS ETC... | | | C) ENERGY CALCULATIONS, LOAD CALCULATIONS, PANEL | | | SCHEDULE(S) AND LINE DIAGRAM TO INDICATE ALL CIRCUITS, | | | INDCATE WHICH ARE EXISTING AND WHICH ARE NEW. | | | D) MANUFACTURER PRODUCT DATA SHEETS FOR ALL APPLIANCES | | | THAT INCLUDE THE MODEL NUMBER, LISTING INFORMATION, AND | | | ELECTRICAL SPECIFICATIONS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2015-06-29 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-06-29 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2015-06-29 |
Time |
14:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2015-05-04 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-05-04 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2015-05-04 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2015-05-04 14:49:49 | PERMIT # 14110234 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 1) DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY | | | THE FIRE DEPARTMENT AFTER COMMENTS BY ALL PLAN | | | REVIEWERS HAVE BEEN SATISFIED. | | | | | | | | | SUE ELLEN CALDERON | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 644-7326 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2014-11-10 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2014-11-10 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2014-11-10 |
Time |
11:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2015-08-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-08-20 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-08-18 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2015-08-18 15:49:55 | RESUB ROUTED TO JWITMER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-08-18 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-07-10 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2015-06-23 |
Time |
|
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-05-16 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2015-05-16 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2015-03-16 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-03-17 06:28:10 | SENT TO B23 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-12-02 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-12-02 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-11-05 |
Time |
11:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2015-08-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-08-21 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-08-21 |
Time |
17:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2015-07-10 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2015-07-10 |
Time |
06:44 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-07-09 |
Time |
07:18 |
Sent To |
|
|
| Notes |
| 2015-07-09 07:36:38 | 3RD REVIEW: FBC 2010 MECHANICAL | | | 7/9/2015 | | | | | | 1) PROVIDE A MEANS OF VENTILATION FOR THE NEW STORAGE | | | ROOM- TABLE 403.3 FBC-10 MECHANICAL. | | | 2) THE NEW HVAC PLAN INDICATES 8"X8" CEILING REGISTERS | | | IN THE CATERING KITCHEN, HOWEVER THE PARTIAL MEP PLAN | | | ON SHEET 2 INDICATES 2'X2' DIFFUSERS: PLEASE CORRECT. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2015-05-16 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2015-05-16 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2015-05-16 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2015-05-16 10:57:16 | PLAN DENIED | | | APPLICATION SHOWS NO MECHANICAL. PAGE 2 | | | OF THE PLAN SHOWS TWO NEW AIR CONDITIONING DROPS. | | | PROVIDE A PLAN SHOWING THE EXISTING DUCT | | | AND PROVIDE GRILL SIZE DUCT SIZE AND CFM | | | OF NEW DUCT. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2014-12-02 |
|
|
Cont ID |
|
| Sent By |
rbergsma |
Date |
2014-12-02 |
Time |
|
Rev Time |
0.75 |
| Received By |
rbergsma |
Date |
2014-12-02 |
Time |
|
Sent To |
|
|
| Notes |
| 2014-12-02 09:46:12 | THIS IS A COMMERCIAL BUILDING AND THIS OVEN CAN PRODUCE | | | HEAT, ODORS AND SMOKE, PLEASE REVIEW THESE SECTIONS OF | | | THE FLORIDA MECHANICAL CODE 2010 | | | | | | 502.1 GENERAL. | | | AN EXHAUST SYSTEM SHALL BE PROVIDED, MAINTAINED AND | | | OPERATED AS SPECIFICALLY REQUIRED BY THIS SECTION AND | | | FOR ALL OCCUPIED AREAS WHERE MACHINES, VATS, TANKS, | | | FURNACES, FORGES, SALAMANDERS AND OTHER APPLIANCES, | | | EQUIPMENT AND PROCESSES IN SUCH AREAS PRODUCE OR THROW | | | OFF DUST OR PARTICLES SUFFICIENTLY LIGHT TO FLOAT IN | | | THE AIR, OR WHICH EMIT HEAT, ODORS, FUMES, SPRAY, GAS | | | OR SMOKE, IN SUCH QUANTITIES SO AS TO BE IRRITATING OR | | | INJURIOUS TO HEALTH OR SAFETY. | | | | | | 506.4 DUCTS SERVING TYPE II HOODS. | | | 506.4.1 DUCTS. | | | 506.4.2 TYPE II TERMINATIONS. |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
4 |
Status |
P |
Date |
2015-08-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-08-20 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-08-20 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
F |
Date |
2015-06-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-06-26 |
Time |
07:16 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-06-26 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-06-26 07:20:44 | BUILDING PLAN REVIEW | | | PERMIT: 14110234 | | | ADD: 5200 BAYWINDS DR. | | | CONT: TBD | | | TEL: (561)791-3155 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: FRI. JUNE 26/ 2015 | | | ACTION: DENIED | | | | | | 1) THE PLANS (FLOOR PLAN) SUBMITTED INDICATE THE | | | PROPOSED WORK, THERE WERE NO PLANS SUBMITED WITH THE | | | EXISTING CONDITION OR DEMOLITION PLANS. THE PERRMIT | | | APPLICATION INDICATES TO BUILD A STORAGE ADDITION. THE | | | PLANS SUBMITTED ARE CONCEPTUAL IN NATURE. | | | | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN | | | REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE | | | DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE | | | FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN; | | | SITE PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR | | | TRUSS LAYOUT; ALL FENESTRATION PENETRATIONS; FLASHING; | | | AND ROUGH OPENING DIMENSIONS; AND ALL EXTERIOR | | | ELEVATIONS: | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | 107.3.5.1.1 BUILDING | | | | | | FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD | | | ELEVATIONS,FLOOD REQUIREMENTS IN ACCORDANCE WITH | | | SECTION 1612, INCLUDING LOWEST FLOOR | | | ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT | | | MATERIALS | | | FLOOD ZONE CERTIFICATES | | | FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES | | | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD | | | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. | | | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS | | | REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION. | | | | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES | | | REQUIRED: | | | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE | | | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR | | | HEIGHT. | | | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND | | | ELEVATION CERTIFICATE IS REQUIRED | | | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE | | | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR | | | ATTENDANTS | | | A/C PADS OR OTHER SLABS FOR GENERATORS | | | FEMA FORM OMB NO. 1660-0008 EXPIRES: | | | JULY 31/2015 | | | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR | | | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. | | | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE | | | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: | | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | | | TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA | | | TUS.ASPX FOR PERMIT STATUS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
F |
Date |
2015-04-22 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2015-04-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2015-04-22 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-06-26 07:19:06 | BUILDING PLAN REVIEW | | | PERMIT: 14110234 | | | ADD: 5200 BAYWINDS DR. | | | CONT: TBD | | | TEL: (561)791-3155 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: WED. APRIL 22/ 2015 | | | ACTION: DENIED | | | | | | 1) THE PLANS (FLOOR PLAN) SUBMITTED INDICATE THE | | | PROPOSED WORK, THERE WERE NO PLANS SUBMITED WITH THE | | | EXISTING CONDITION OR DEMOLITION PLANS. THE PERRMIT | | | APPLICATION INDICATES TO BUILD A STORAGE ADDITION. THE | | | PLANS SUBMITTED ARE CONCEPTUAL IN NATURE. | | | | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN | | | REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE | | | DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE | | | FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN; | | | SITE PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR | | | TRUSS LAYOUT; ALL FENESTRATION PENETRATIONS; FLASHING; | | | AND ROUGH OPENING DIMENSIONS; AND ALL EXTERIOR | | | ELEVATIONS: | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | 107.3.5.1.1 BUILDING | | | | | | FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD | | | ELEVATIONS,FLOOD REQUIREMENTS IN ACCORDANCE WITH | | | SECTION 1612, INCLUDING LOWEST FLOOR | | | ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT | | | MATERIALS | | | FLOOD ZONE CERTIFICATES | | | FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES | | | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD | | | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. | | | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS | | | REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION. | | | | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES | | | REQUIRED: | | | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE | | | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR | | | HEIGHT. | | | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND | | | ELEVATION CERTIFICATE IS REQUIRED | | | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE | | | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR | | | ATTENDANTS | | | A/C PADS OR OTHER SLABS FOR GENERATORS | | | FEMA FORM OMB NO. 1660-0008 EXPIRES: | | | JULY 31/2015 | | | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR | | | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. | | | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE | | | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: | | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | | | TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA | | | TUS.ASPX FOR PERMIT STATUS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2014-11-18 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2014-11-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2014-11-18 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-06-26 07:16:55 | BUILDING PLAN REVIEW | | | PERMIT: 14110234 | | | ADD: 5200 BAYWINDS DR. | | | CONT: TBD | | | TEL: (561)791-3155 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: NOV. 18/ 2014 | | | ACTION: DENIED | | | | | | 1) THE PLANS (FLOOR PLAN) SUBMITTED INDICATE THE | | | PROPOSED WORK, THERE WERE NO PLANS SUBMITED WITH THE | | | EXISTING CONDITION OR DEMOLITION PLANS. THE PERRMIT | | | APPLICATION INDICATES TO BUILD A STORAGE ADDITION. THE | | | PLANS SUBMITTED ARE CONCEPTUAL IN NATURE. | | | | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN | | | REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE | | | DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE | | | FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN; | | | SITE PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR | | | TRUSS LAYOUT; ALL FENESTRATION PENETRATIONS; FLASHING; | | | AND ROUGH OPENING DIMENSIONS; AND ALL EXTERIOR | | | ELEVATIONS: | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | 107.3.5.1.1 BUILDING | | | | | | FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD | | | ELEVATIONS,FLOOD REQUIREMENTS IN ACCORDANCE WITH | | | SECTION 1612, INCLUDING LOWEST FLOOR | | | ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT | | | MATERIALS | | | FLOOD ZONE CERTIFICATES | | | FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES | | | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD | | | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. | | | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS | | | REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION. | | | | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES | | | REQUIRED: | | | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE | | | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR | | | HEIGHT. | | | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND | | | ELEVATION CERTIFICATE IS REQUIRED | | | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE | | | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR | | | ATTENDANTS | | | A/C PADS OR OTHER SLABS FOR GENERATORS | | | FEMA FORM OMB NO. 1660-0008 EXPIRES: | | | JULY 31/2015 | | | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR | | | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. | | | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE | | | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: | | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | | | | | | 2) STRUCTURAL REQUIREMENTS SHALL INCLUDE: | | | SOIL CONDITIONS/ANALYSIS | | | 1803.5.2 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, | | | STRENGTH OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR | | | WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED | | | IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE | | | PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION | | | BE CONDUCTED. | | | | | | | | | 3) ROOF SYSTEMS SHEET 1 THE TRUSS DETAIL SHOWS A TRUSS | | | MARKED # 1 WITH 500 LBS UPLIFT AND 40 LATERAL OADS, THE | | | CONNECTION SCHEDULE LACKS THE TIE DOWN INFORMATION THAT | | | THE GIRDER THAT THE COMMON TRUSSES TIE INTO. | | | THE TYPICAL WALL SECTION ALSO IS MISSING THE GIRDER AND | | | THE TYPE OF CONNECTION THE TOP AND BOTOM CHORDS OF THE | | | COMMON JACKS CONNECT WITH. 107.2.1.3 ADDITIONAL | | | INFORMATION. THIS ROOF FRAMING IS PART OF THE MAIN WIND | | | FORCE RESISTING SYSTEM. | | | | | | TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA | | | TUS.ASPX FOR PERMIT STATUS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2015-07-10 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2015-07-10 |
Time |
04:18 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-07-10 |
Time |
04:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2015-05-09 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-05-09 |
Time |
05:35 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-05-09 |
Time |
05:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2014-11-22 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-11-22 |
Time |
06:38 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-11-22 |
Time |
06:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2015-06-30 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-06-30 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-06-30 |
Time |
15:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2014-11-18 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2014-11-18 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2014-11-18 |
Time |
13:07 |
Sent To |
|
|
| Notes |
| 2014-11-14 12:13:10 | 11/14/14 |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |