| 2014-11-10 07:34:38 | BUILDING PLAN REVIEW |
| | REVISION: 14110233 |
| | PERMIT: 14021098 |
| | ADD: 915 S. DIXIE HWY. |
| | CONT: DEALERSHIP SOLUTIONS, LLC |
| | TEL: (727)871-0109 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. NOV. 11/2014 |
| | ACTION: DENIED |
| | |
| | 1) EXTERIOR FRAMING DETAILS SK-1 THRU SK-3 W/ |
| | CALCULATIONS: |
| | 1A) SEAL IS ILLEGIBLE . PLANS, SPECIFICATIONS, REPORTS |
| | OR OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL |
| | AND BEING FILED FOR PUBLIC RECORD SHALL HAVE THE |
| | SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | EFFECTIVE DATE 05/06/2009 |
| | (2)(A) EVERY SHEET OF PLANS AND PRINTS WHICH MUST BE |
| | SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL |
| | BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL |
| | ENGINEER IN RESPONSIBLE CHARGE. |
| | |
| | |
| | 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX |
| | SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND |
| | THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE |
| | PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| | ON THE COVER SHEET OR INDEX. |
| | |
| | 2) THERE IS NO SHOP DRAWING REVIEW STAMP FROM THE |
| | ENGINEER OF RECORD JOSEPH P. FULLONS P. E. 61G15-30.006 |
| | (3)DELEGATE ENGINEERS RESPONSIBILITY. |
| | THE DELEGATE ENGINEER SHALL FORWARD THE DELEGATE |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |