Plan Review Details - Permit 14110213
Plan Review Stops For Permit 14110213
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-02-19 Cont ID  
Sent By jwitmer Date 2015-02-19 Time 08:38 Rev Time 0.00
Received By jwitmer Date 2015-02-19 Time 07:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-01-14 Cont ID  
Sent By jwitmer Date 2015-01-14 Time 11:07 Rev Time 0.00
Received By jwitmer Date 2015-01-14 Time 10:55 Sent To  
Notes
2015-01-14 11:07:42BUILDING PLAN REVIEW
 PERMIT: 14110213
 ADD: 222 LAKEVIEW SUITE # 400
 CONT: GREEN CONSTRUCTION
 TEL: (305) 670-1000
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JAN 14/2015
 ACTION: DENIED
  
 NOTICE: THE PERMIT APPLICATION INDICATES UNDER THE
 HEADING DESCRIPTION OF WORK, TYPED SUITE 400/
 HANDWRITTEN 1ST FLOOR BUILD OUT. THE PLANS INDICATE THE
 WORK IS TO BE COMPLETED ON THE 4TH FLOOR, SO THIS
 REVIEW WILL TAKE PLACE AS 4TH FLOOR. CORRECT THE PERMIT
 APPLICATION.
  
 1) SHEET A-04:
 !A) THE (2) NEW ELEVATORS THAT ARE NOT PART OF THIS
 CONTRACT WILL EFFECT THE OUTCOME OF THIS PROJECT,
 PLEASE INDICATE HOW COMPLIANCE WITH FBC-B 708.14.1
 ELEVATOR LOBBIES OR A EXCEPTION WILL BE COMPLIED WITH.
 THE RESPONSE INDICATES TO SEE ENGINEERING PLANS AND
 PLEASE NOTE THE PROPOSED ELEVATOR WILL NOT BE SERVING
 MORE THAN 3 FLOORS.
  
 IN THE MECHANICAL PLANS SHEET M1.2 THERE IS NO MENTION
 OF SHAFT PRESSURIZATION OR ANY EXCEPTION.PLEASE REVIEW
 THE FOLLOWING INFORMAL INTERPRETATION REPORT 7397.
  
 DATE: WED SEP 10 2014
 REPORT: 7397
 CODE: BUILDING CODE YEAR: 2010
 SECTION: 708.14.1
 QUESTION:
 IS IT THE INTENT OF THIS SECTION TO REQUIRE ELEVATOR
 LOBBIES OR THEIR EXCEPTION IN NEW ELEVATORS AND
 SHAFTWAYS IN A PORTION OF A
 HIGHRISE BUILDING THAT IS (5) STORIES IN HEIGHT IF YES
 THEN WOULD THE EXCEPTIONS APPLY?
 COMMENT:
 NONE
 ANSWER:
 YES AND YES
 COMMENTARY:
 A HIGH RISE BUILDING IS DEFINED BY ITS HEIGHT (OCCUPIED
 FLOOR GREATER THAN 75? ABOVE LOWEST LEVEL OF FIRE DEPT.
 VEHICULAR ACCESS);
 NOT THE NUMBER OF FLOORS. AS A NOTE, THE NEXT EDITION
 OF THE CODE WILL ALLOW THE DELETION OF LOBBIES FOR AN
 ELEVATOR IN A HIGH RISE
 BUILDING THAT DOES NOT SERVE FLOORS OVER 75 FEET ABOVE
 THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS.
 I.E. THE LOWER FLOORS OF
 A HIGH RISE BUILDING SERVED BY AN ELEVATOR SERVING ONLY
 THE LOWER FLOORS. (THE FIRST 5 STORIES, IF THEY DO NOT
 HAVE AN OCCUPIED
 FLOOR LEVEL MORE THAN 75 FEET ABOVE FD VEHICLE ACCESS
 AND THE ELEVATOR DOES NOT SERVICE ANY SUCH FLOOR. THE
 PROVISION WILL MOVE
 TO SECTION 713.14.1 IN THE NEXT EDITION. HERE IS THE
 WORDING THAT WILL BE COMING IN THE NEXT EDITION: 4.
 ENCLOSED ELEVATOR LOBBIES
 ARE NOT REQUIRED WHERE THE BUILDING IS PROTECTED BY AN
 AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH
 SECTION
 903.3.1.1 OR 903.3.1.2. THIS EXCEPTION SHALL NOT APPLY
 TO THE FOLLOWING: 4.1. GROUP I-2 OCCUPANCIES; 4.2.
 GROUP I-3 OCCUPANCIES;
 AND 4.3. ELEVATORS SERVING FLOOR LEVELS OVER 75 FEET
 (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT
 VEHICLE ACCESS IN
 HIGH-RISE BUILDINGS
 NOTICE:
 THE BUILDING OFFICIALS ASSOCIATION OF FLORIDA, IN
 COOPERATION WITH THE FLORIDA BUILDING COMMISSION, THE
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ICC,
 AND INDUSTRY AND PROFESSIONAL EXPERTS OFFER THIS
 INTERPRETATION OF THE FLORIDA BUILDING CODE IN THE
 INTEREST OF CONSISTENCY IN THEIR APPLICATION STATEWIDE.
 THIS INTERPRETATION IS INFORMAL, NON-BINDING AND
 SUBJECT TO ACCEPTANCE AND APPROVAL BY THE LOCAL
 BUILDING OFFICIAL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-17 Cont ID  
Sent By jwitmer Date 2014-11-17 Time 14:47 Rev Time 0.00
Received By jwitmer Date 2014-11-17 Time 14:03 Sent To  
Notes
2014-11-17 14:21:00BUILDING PLAN REVIEW
 PERMIT: 14110213
 ADD: 222 LAKEVIEW SUITE # 400
 CONT: GREEN CONSTRUCTION
 TEL: (305) 670-1000
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 17/2014
 ACTION: DENIED
  
 NOTICE: THE PERMIT APPLICATION INDICATES UNDER THE
 HEADING DESCRIPTION OF WORK, TYPED SUITE 400/
 HANDWRITTEN 1ST FLOOR BUILD OUT. THE PLANS INDICATTE
 THE WORK IS TO BE COMPLETED ON THE 4TH FLOOR, SO THIS
 REVIEW WILL TAKE PLACE AS 4TH FLOOR. CORRECT THE PERMIT
 APPLICATION.
  
 1) 1) SHEET A-04:
 !A) THE (2) NEW ELEVATORS THAT ARE NOT PART OF THIS
 CONTRACT WILL EFFECT THE OUTCOME OF THIS PROJECT,
 PLEASE INDICATE HOW COMPLIANCE WITH FBC-B 708.14.1
 ELEVATOR LOBBIES OR A EXCEPTION WILL BE COMPLIED WITH.
  
  
 1B) THE (2) STORAGE ROOMS 403 & 436 ARE LARGE FILE
 ROOMS PLEASE PROVIDE WHAT THE FLOOR LOADS FOR THESE
 ROOMS ARE DESIGNED, SEE 2010 FBC-B TABLE
 1607.1 (25) OFFICE BUILDINGS- FILE ROOMS SHALL BE
 DESIGNED FOR HEAVIER LOADS BASED ON ANTICIPATED
 OCCUPANCY.
  
 1C) THE COFFEE/ BREAK ROOM # 456 INDICATES A SECTION/
 DETAIL 3/ A-09 THIS IS NOT THE CORRECT DETAILS. SHEET
 A-07.6 SHOWS VARIOUS SINK DETAILS.
 PLEASE PROVIDE CORRECT SECTION. 107.2.1.3 DISCREPANCY
 IN PLANS.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-01-31 Cont ID  
Sent By dhayes Date 2015-01-31 Time 14:14 Rev Time 0.00
Received By dhayes Date 2015-01-31 Time 14:14 Sent To  
Notes
2015-01-31 14:15:20SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR ACCESS CONTROL SYSTEM, SECURITY, CCTV,
 AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-02 Cont ID  
Sent By dhayes Date 2014-12-02 Time 11:51 Rev Time 0.00
Received By dhayes Date 2014-12-02 Time 10:52 Sent To  
Notes
2014-12-02 11:53:5612/2/2014
 PROJECT: DADELAND CENTER.STE 400
 PERMIT#: 14110213
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION:DENIED
  
 1) PROVIDE MANUFACTURER PRODUCT SPEC SHEETS FOR AUTO
 FLUSH AND LAV VALVES INDICATING THE OPERATING VOLTAGE
 AND COMPLIANCE WITH THE LISTING REQUIREMENTS OF THE NEC
 110.3(B)
  
 2) INDICATE LOCATION, SIZE, TYPE, PHASE AND VOLTAGE FOR
 SERVICE DISCONNECT SD-1 AND SD-2. FBC- 107.3.5.3
  
 3) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SECURITY, CCTV, NETWORK, DATA,
 COMMUNICATION, FIRE ALARM, ACCESS CONTROL SYSTEM,
 AUDIO, VIDEO.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-11-06 Cont ID  
Sent By pleduc Date 2014-11-06 Time   Rev Time 0.00
Received By pleduc Date 2014-11-06 Time 15:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-02-24 Cont ID  
Sent By jwitmer Date 2015-02-24 Time 12:34 Rev Time 0.00
Received By tklarge Date 2015-02-13 Time   Sent To  
Notes
2015-02-13 16:40:04B06

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-31 Cont ID  
Sent By dhayes Date 2015-01-31 Time 14:18 Rev Time 0.00
Received By dhayes Date 2015-01-09 Time 09:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-02 Cont ID  
Sent By dhayes Date 2014-12-02 Time 12:38 Rev Time 0.00
Received By dhayes Date 2014-11-05 Time 14:28 Sent To  
Notes
2014-11-05 14:25:54B23

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-01-28 Cont ID  
Sent By hmoser Date 2015-01-28 Time 16:19 Rev Time 0.00
Received By hmoser Date 2015-01-28 Time 16:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-02 Cont ID  
Sent By rbergsma Date 2014-12-02 Time   Rev Time 0.75
Received By rbergsma Date 2014-12-02 Time   Sent To  
Notes
2014-12-02 08:38:00PLEASE COMPLETE SEQUENCE OF OPERATION (SMOKE CONTROL)
 HEAT PUMP 2 , " D1 IS CLOSED UNTIL FIRE CONTROL
 ---------------------------------------- " ? ON PAGE
 M2.1

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-02-24 Cont ID  
Sent By tklarge Date 2015-02-24 Time 12:34 Rev Time 0.00
Received By tklarge Date 2015-02-20 Time 12:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-01-23 Cont ID  
Sent By tklarge Date 2015-01-17 Time 08:51 Rev Time 0.00
Received By tklarge Date 2015-01-17 Time 06:44 Sent To  
Notes
2015-01-17 06:29:461) A MINIMUM OF THREE DRINKING FOUNTAINS ARE REQUIRED
 PER TABLE 403. THE RESPONSE REFERS TO REFRIGERATORS IN
 THE COFFEE BREAK ROOM #453 & EMPLOYEE BREAK ROOM #412
 HAVING WATER DISPENSERS. SHOW HOW THESE WATER
 DISPENSERS COMPLY WITH ARI 1010 AND NSF 61.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-22 Cont ID  
Sent By tklarge Date 2014-11-22 Time 08:00 Rev Time 0.00
Received By tklarge Date 2014-11-22 Time 06:39 Sent To  
Notes
2014-11-22 08:00:221) A MINIMUM OF THREE DRINKING FOUNTAINS ARE REQUIRED
 PER TABLE 403.1 OF THE 2010 FPC. TWO OF THE DRINKING
 FOUNTAINS SHALL BE A HI-LO UNIT PER THE 2010 FAC
 SEC.211.2.
 2) SUBMIT THE MANUFACTURER'S SPEC SHEETS/INSTALLATION
 INSTRUCTIONS FOR THE CHRONOMITE INSTANTANEOUS WATER
 HEATERS. WPB AMEND. SEC.107.2.1.
 3) SUBMIT THE OCCUPANT LOAD FOR THE SPACE PER FBC TABLE
 1004.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  