| Plan Review Stops For Permit 14110166 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2015-01-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-01-22 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-01-12 |
Time |
08:48 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2014-11-29 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-11-29 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-11-29 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2014-11-29 13:35:34 | 2ND REVIEW: FBC 2010 | | | | | | SEE THE COMMENTS FROM 11/23/14. THE SUBMITTAL IS STILL | | | NOT ADEQUATE. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-11-23 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-11-23 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-11-23 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2014-11-23 09:35:06 | 1ST REVIEW: FBC 2010 | | | | | | THE SUBMITTED PLANS DO NOT CONTAIN ADEQUATE DETAIL TO | | | DETERMINE COMPLIANCE WITH THE FBC. PROVIDE MATERIALS | | | AND CONNECTION METHODS. | | | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE | | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | | ELECTRONIC MEDIA DOCUMENTS SHALL BE | | | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN | | | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS | | | CODE AND RELEVANT LAWS, ORDINANCES, RULES | | | AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | | AS TO THE QUALITY OF MATERIALS, WHERE | | | QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL | | | CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR | | | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5). | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2015-01-24 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-01-24 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-01-24 |
Time |
15:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2014-11-29 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-11-29 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-11-29 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2014-11-29 13:39:44 | 2ND REVIEW: FBC 2010 | | | | | | SEE THE COMMENTS FROM 11/23/14. THE SUBMITTAL IS STILL | | | NOT ADEQUATE. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-11-23 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-11-23 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-11-23 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2014-11-23 09:36:19 | 1ST REVIEW: FBC 2010 | | | | | | THE SUBMITTED PLANS DO NOT CONTAIN ADEQUATE DETAIL TO | | | DETERMINE COMPLIANCE WITH THE NEC . NO ELECTRICAL | | | DETAILS WERE PROVIDED. SEE ZONING REVIEW AS TO | | | PERMITTED ELECTRICAL. | | | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE | | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | | ELECTRONIC MEDIA DOCUMENTS SHALL BE | | | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN | | | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS | | | CODE AND RELEVANT LAWS, ORDINANCES, RULES | | | AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | | AS TO THE QUALITY OF MATERIALS, WHERE | | | QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL | | | CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR | | | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5). | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-01-24 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-01-24 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-01-09 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2015-01-22 17:27:25 | TO DAH DESK | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-11-29 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-11-29 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-11-25 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2014-11-25 07:15:59 | SENT TO ZONING BOX. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-11-23 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-11-23 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-11-04 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2014-11-04 16:32:34 | TO ZONING | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2014-11-25 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2014-11-25 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2014-11-25 |
Time |
08:32 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-11-05 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2014-11-05 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2014-11-05 |
Time |
10:25 |
Sent To |
B |
|
| Notes |
| 2014-11-05 10:29:54 | 11/5/14 ZONING FAILED | | | | | | 1. SIGN MUST BE A MAX OF 20 SQUARE FEET. | | | 2. SIGN MUST BE 15' FROM THE PROPERTY LINE. | | | 3. MAX HEIGHT OF THE SIGN IS 6' | | | PROHIBITED FOR ELECTRONIC MESSAGE | | | 1. LAMPS/BULBS IN THE EXCESS OF 30 WATTS | | | 2. EXPOSED REFLECTORIZED LAMPS/BULBS | | | 3. LAMPS/BULBS NOT COVERED BY A LENS,FILTER,LOUVER OR | | | SUNSCREEN | | | 4. MODES OF OPERATION THAT SCHOOL, FLASH, TWINKLE OR | | | SPARKLE |
|
|