| 2014-11-26 09:17:05 | BUILDING PLAN REVIEW |
| | PERMIT: 14110155 |
| | ADD: 700 S ROSEMARY AVE. SUITE 140 |
| | CONT: CHANDLER CONSTRUCTION |
| | TEL: (561)791-6934 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. NOV. 26/ 2014 |
| | |
| | NOTICE GREASE DUCTS WILL REQUIRE A SEPARATE PERMIT & |
| | REVIEW. |
| | |
| | ACTION: BUILDING PROVISO |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | |
| | 1) SHEET A2.2 SHOWS A GREASE DUCT WITH A 2 HR. DUCT |
| | WRAP THAT WILL BE INCOMPLIANCE WITH FBC-M ASTM E 2336. |
| | NO LITERATURE HAS BEEN PROVIDED. THE 2010 FBC-B 708.2 |
| | EXCEPTION #4 STATES GREASE DUCTS SHALL BE PROTECTED IN |
| | ACCORDANCE WITH THE FBC-MECHANICAL. PLEASE PROVIDE THE |
| | LITERATURE SHOWING COMPLIANCE. |
| | |
| | 2) THERE IS A DISCREPANCY IN THE PLANS AND HOW THE |
| | ACTUAL FIELD CONDITION OF THE 2 HR. DUCT WRAP, PLEASE |
| | REVIEW 2010 FBC-M 506.3.10.2. THE SURFACE OF THE DUCT |
| | SHALL BE CONTINUOUSLY COVERED ON ALL SIDES FROM THE |
| | POINT AT WHICH THE DUCT ORIGINATES TO THE OUTLET |
| | TERMINAL. THE PLANS, TYPICAL CURB DETAIL ON A2.1 & |
| | SECTION THROUGH THE GREASE DUCT CHASE, A2.2 SHOW THE |
| | DUCT WRAP CONTINUING TO THE ROOF TOP HOOD EXHAUST FAN. |
| | IN REALITY THE DUCT WRAP STOPS AT THE TOP OF THE HOOD |
| | EXHAUST DUCT ROOF TOP CURB, PLEASE SHOW THE OUTLET |
| | TERMINAL HOW IT WILL BE MADE WATER TIGHT, AND HOW IT |
| | WILL BE ATTACHED TO THE ROOF TOP CURB. PLEASE ALLOW IN |
| | SIZING FOR THE CURB 2 LAYERS OF DUCT WRAP TO CONTINUE |
| | TO THE TOP OF THE ROOF CURB. |
| | |
| | 3A) SHEET A-8.2 DETAIL B SHOWS NEW GLAZING IN THE |
| | STOREFRONT, THESE PRODUCT APPROVALS ARE TO BE REVIEWED |
| | AS A DEFERRED SUBMITTAL UNDER 107.3.4.2 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION,. |
| | |
| | 3B) ALSO NOTE THAT THE DESIGNER OF RECORD IS TO HAVE |
| | REVIEWED AND APPROVED THE SUBMITTED PRODUCT APPROVALS |
| | WITH THEIR SHOP DRAWING STAMP OF APPROVAL. |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |