| 2014-11-04 10:41:22 | BUILDING PLAN REVIEW |
| | PERMIT: 14110037 |
| | ADD: 1355 BEAR ISLAND DR |
| | CONT: ALL PHASE ROOFING |
| | TEL: (561)704-2671 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. NOV. 04/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) THE CONTRACTOR SUBMITTED ROOFING NOA 11-0414.09 |
| | BERMUDA CONCRETE FLAT ROOF TILE WITH #M 2 COMPONENT |
| | FOAM TILE ADHESIVE NOA, THE BERMUDA CONCRETE FLAT ROOF |
| | TILE NOA TABLE # 6 FOR SINGLE PATTY ADHESIVE SET SYSTEM |
| | HAS NOT BEEN CIRCLED IF THE INSTALATION IS TO USE A |
| | MEDIUM PATTY OR LARGE PATTY FOR UPLIFT. |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1.2 FOR |
| | ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION |
| | DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE |
| | TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING |
| | REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| | RATING THAT ARE REQUIRED TO BE INSTALLED. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |