Plan Review Details - Permit 14101072
| Plan Review Stops For Permit 14101072 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2014-11-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-11-14 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-11-14 |
Time |
07:51 |
Sent To |
|
|
| Notes |
| 2014-11-14 07:52:34 | CONTRACTOR EMAILED THE CORRECT INFORMATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2014-11-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-11-12 |
Time |
18:39 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-11-12 |
Time |
18:39 |
Sent To |
|
|
| Notes |
| 2014-11-12 18:44:06 | PLAN REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) THE AMERICAST GENERATOR PADS ARE DESIGNED TO BE USED | | | WITH SPECIFIC GENERATOR MODELS. SUBMIT MANUFACTURER'S | | | SPECIFICATIONS WITH THE MODEL NUMBER AND OUTPUT | | | CAPACITY (KW) FOR THE GENERATOR THAT WILL BE INSTALLED. | | | FBC 107.2.1 ( THE LETTER FROM THE CONTRACTOR STATES | | | THAT THE GENERATOR IS A 20 KW GE MODEL, HOWEVER, THE | | | MODEL NUMBER IN THE LETTER IS FOR A 20 KW BRIGGS & | | | STRATTON GENERATOR. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-11-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-11-07 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-11-07 |
Time |
16:49 |
Sent To |
E |
|
| Notes |
| 2014-11-07 16:57:35 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) THE AMERICAST GENERATOR PADS ARE DESIGNED TO BE USED | | | WITH SPECIFIC GENERATOR MODELS. SUBMIT MANUFACTURER'S | | | SPECIFICATIONS WITH THE MODEL NUMBER AND OUTPUT | | | CAPACITY (KW) FOR THE GENERATOR THAT WILL BE INSTALLED. | | | FBC 107.2.1 | | | | | | 2) ONLY ONE SET OF DRAWINGS FOR THE AMERICAST GENERATOR | | | PAD WAS SUBMITTED. A MINIMUM OF TWO SETS ARE REQUIRED. | | | FBC 107.1 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-11-08 |
|
|
Cont ID |
|
| Sent By |
TimLarge |
Date |
2014-11-08 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-11-08 |
Time |
10:57 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2014-11-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-11-19 |
Time |
05:32 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-11-19 |
Time |
05:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2014-11-12 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-11-12 |
Time |
06:09 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-11-12 |
Time |
06:09 |
Sent To |
|
|
| Notes |
| 2014-11-12 06:09:26 | 1) THE GAS SIZING TABLE THAT YOU HAVE REFERENCED ON THE | | | GAS DRAWING IS FROM AN OUTDATED EDITION OF THE CODE. | | | THIS TABLE NUMBER IN THE 2010 FL. GAS CODE IS FOR CSST, | | | NOT PE. SUBMIT 2 COPIES OF THE CORRECT GAS SIZING TABLE | | | FROM THE 2010 FGC WHICH IS THE CODE IN EFFECT, NOT THE | | | 2001 EDITION. | | | 2) SUBMIT 2 COPIES OF A CLEAR AND LEGIBLE PLAN OF THE | | | DRAWING FROM AMERICAN WELDING & TANK CO. WPB AMEND. TO | | | 2010 FBC SEC.107.2.1. | | | 3) SUBMIT 2 CLEAR AND LEGIBLE COPIES OF THE DRAWING | | | FROM NFPA FOR THE TANK LOCATIONS. THE CODE EDITION IN | | | EFFECT IS THE 2008 EDITION, NOT THE 1996 EDITION THAT | | | YOU SUBMITTED. WPB AMEND. TO 2010 FBC SEC.107.2.1. | | | 4) INDICATE THE DISTANCE OF THE LP TANK FROM THE | | | DRIVEWAY. COMPLY WITH NFPA 58 SEC.6.6.6 .1 (D). | | | 5) SUBMIT TWO COPIES OF THE SIGNED AND SEALED DRAWINGS | | | FOR THE AMERICAST SLAB. WPB AMEND. TO 2010 FBC | | | SEC.107.2.1. | | | 6) SUBMIT DOCUMENTATION THAT THE GENERATOR IS LISTED | | | AND LABELED IN ACCORDANCE W/ 2010 FGC SEC. 301.3. | | | 7) STATIONARY GENERATORS SHALL MEET THE REQUIREMENTS OF | | | UL 22OO PER THE 2010 FGC SEC.616.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-11-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-11-19 |
Time |
05:32 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-11-17 |
Time |
08:25 |
Sent To |
|
|
| Notes |
| 2014-11-18 08:25:49 | GAVE TO T LARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-11-12 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-11-12 |
Time |
06:29 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-11-12 |
Time |
06:29 |
Sent To |
|
|
| Notes |
| 2014-10-31 15:41:48 | ROUTED TO ZONING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2014-11-04 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2014-11-04 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2014-11-04 |
Time |
12:23 |
Sent To |
B |
|
| Notes |
|
|
|