Plan Review Details - Permit 14101067
Plan Review Stops For Permit 14101067
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-01-26 Cont ID  
Sent By jwitmer Date 2015-01-26 Time 15:55 Rev Time 0.00
Received By jwitmer Date 2015-01-26 Time 15:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-12-07 Cont ID  
Sent By jwitmer Date 2014-12-07 Time 08:48 Rev Time 0.00
Received By jwitmer Date 2014-12-07 Time 08:31 Sent To  
Notes
2014-12-07 08:48:45BUILDING PLAN REVIEW
 REVISION: 14101067
 PERMIT: 14070014
 ADD: 230 CLEMATIS ST.
 CONT: TWENTY TWO GROUP
 TEL: (772)528-7241
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SUN. DEC. 07/2014
 ACTION: DENIED.
  
 2A) ASK 2 & 3 BOTH OF THESE DETAILS ARE FOR A TYPICAL
 CHAIR DISPLAY. THESE SUBMITTED PLANS E2.1 NOW INDICATE
 WHERE THEY ARE TO BE INSTALLED WITHIN THE TENANT
 SEPARATION DEMISSING WAL WHICH IS A 1 HOUR TENANT
 SEPARATION WALL. PLEASE PROVIDE THE WALL ASSEMBLY THAT
 ALLOWS THE DRYWALL TO BE REMOVED FROM THE ASSEMBLY AND
 A METAL STUD OR PLATE INSERTED INTO THE CAVITY.
 2010 FBC-B 709.1(6). / 709.3 FIRE-RESISTANCE RATING.
 FIRE PARTITIONS SHALL HAVE A FIRE-RESISTANCE RATING OF
 NOT LESS THAN 1 HOUR.
 709.8 JOINTS. JOINTS MADE IN OR BETWEEN FIRE PARTITIONS
 SHALL COMPLY WITH SECTION 714.
 714.1 GENERAL. JOINTS INSTALLED IN OR BETWEEN
 FIRE-RESISTANCE-RATED WALLS, FLOOR OR FLOOR/CEILING
 ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL
 BE PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE FOR A TIME
 PERIOD NOT LESS THAN THE REQUIRED FIRE-RESISTANCE
 RATING OF THE WALL, FLOOR OR ROOF IN OR BETWEEN WHICH
 IT IS INSTALLED. FIRE-RESISTANT JOINT SYSTEMS SHALL BE
 TESTED IN ACCORDANCE WITH SECTION 714.3. THE VOID
 CREATED AT THE INTERSECTION OF A FLOOR/CEILING ASSEMBLY
 AND AN EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 714.4.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-07 Cont ID  
Sent By jwitmer Date 2014-11-07 Time 16:05 Rev Time 0.00
Received By jwitmer Date 2014-11-07 Time 14:36 Sent To  
Notes
2014-11-07 15:41:50BUILDING PLAN REVIEW
 REVISION: 14101067
 PERMIT: 14070014
 ADD: 230 CLEMATIS ST.
 CONT: TWENTY TWO GROUP
 TEL: (772)528-7241
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. NOV. 07/2014
 ACTION: DENIED
  
 1) SKETCH ASK-1 INDICATES A TYPICAL SOFFIT DETAIL
 PLEASE PROVIDE WHERE THIS SOFFIT IS LOCATED ON SHEET
 A111.00. DEPENDING WHERE THIS SOFFIT IS TO BE LOCATED,
 THERE WOULD BE DIFFERENT FASTENERS REQUIRED. THE ASK-1
 DETAIL DOES NOT PROVIDE HOW FAR THE SOFFIT IS TO DROP
 WIDTH OR LENGTH OF THE SOFFIT., WHAT THE CLEAR HEIGHT
 IS UNDER THIS SOFFIT,NOR IF EXIT LIGHTS OR DIRECTIONS
 ARE BLOCKED BY THE SOFFIT. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 THE CEILING/ FLOOR ASSEMBLY IS A FIRE RATED ASSEMBLY
 SINCE THERE IS A SECOND STORY, DOES THE EXISTING FLOOR/
 CEILING ASSEMBLY STILL CREATE THE HORIZONTAL FIRE
 BARRIER REQUIRED BY 707.3.9.
  
 2A) ASK 2 & 3 BOTH OF THESE DETAILS ARE FOR A TYPICAL
 CHAIR DISPLAY. AGAIN THE SKETCHES DO NOT INDICATE WHERE
 THEY ARE TO BE INSTALLED WITHIN THE TENANT SPACE. SHEET
 A113.00 IT APPEARS THIS DISPLAY IS ON THE SOUTH WALL
 WHICH IS A 1 HOUR TENANT SEPARATION WALL. IF THIS IS
 THE CASE PLEASE PROVIDE THE WALL ASSEMBLY THAT ALLOWS
 THE DRYWALL TO BE REMOVED FROM THE ASSEMBLY AND A METAL
 STUD OR PLATE INSERTED INTO THE CAVITY.
 2010 FBC-B 709.1(6). / 709.3 FIRE-RESISTANCE RATING.
 FIRE PARTITIONS SHALL HAVE A FIRE-RESISTANCE RATING OF
 NOT LESS THAN 1 HOUR.
 709.8 JOINTS. JOINTS MADE IN OR BETWEEN FIRE PARTITIONS
 SHALL COMPLY WITH SECTION 714.
 714.1 GENERAL. JOINTS INSTALLED IN OR BETWEEN
 FIRE-RESISTANCE-RATED WALLS, FLOOR OR FLOOR/CEILING
 ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL
 BE PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE FOR A TIME
 PERIOD NOT LESS THAN THE REQUIRED FIRE-RESISTANCE
 RATING OF THE WALL, FLOOR OR ROOF IN OR BETWEEN WHICH
 IT IS INSTALLED. FIRE-RESISTANT JOINT SYSTEMS SHALL BE
 TESTED IN ACCORDANCE WITH SECTION 714.3. THE VOID
 CREATED AT THE INTERSECTION OF A FLOOR/CEILING ASSEMBLY
 AND AN EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 714.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-12-05 Cont ID  
Sent By jwitmer Date 2014-12-05 Time 13:08 Rev Time 0.00
Received By dhayes Date 2014-12-05 Time 08:17 Sent To B
Notes
2014-12-05 13:09:27FWD TO J.WITMER'S DESK

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-11-08 Cont ID  
Sent By dhayes Date 2014-11-08 Time 11:02 Rev Time 0.00
Received By dhayes Date 2014-11-08 Time 11:02 Sent To  
Notes
2014-11-08 11:13:5011/8/2014
 PROJECT: DWR WPB
 PERMIT#: 14070014, REVISION#14101067
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW FOR REVISION#14101067
 ACTION: DENIED
  
 1) THERE IS A LIGHT FIXTURE INDICATED ON THE SOFFIT
 DETAIL BUT THERE ARE NO ELECTRICAL PLANS WITH THIS
 SUBMITTAL. PLEASE PROVIDE AN ELECTRICAL PLAN INDICATING
 THE PROPOSED WIRING MEATHOD, CIRCUIT AND CONTROL. WPB
 AMENDMENTS TO THE FBC 107.3.2, FBC SECTIONS 505.2.1,
 505.2.2, 505.2.3 AND 505.2.4.
  
 2) INDICATE MEATHOD OF BONDING METAL FRAMING MEMBERS.
 FBC 2704.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-01-26 Cont ID  
Sent By   Date 2015-01-26 Time   Rev Time 0.00
Received By   Date 2015-01-23 Time   Sent To  
Notes
2015-01-24 08:46:14SENT TO J. W. DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-07 Cont ID  
Sent By jwitmer Date 2014-12-07 Time 08:49 Rev Time 0.00
Received By jwitmer Date 2014-12-04 Time 08:23 Sent To  
Notes
2014-12-05 08:17:28DHAYES DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-08 Cont ID  
Sent By dhayes Date 2014-11-08 Time 11:14 Rev Time 0.00
Received By dhayes Date 2014-10-31 Time 14:32 Sent To  
Notes
2014-10-31 14:32:54GAVE TO J WITMER