| 2014-11-07 15:41:50 | BUILDING PLAN REVIEW |
| | REVISION: 14101067 |
| | PERMIT: 14070014 |
| | ADD: 230 CLEMATIS ST. |
| | CONT: TWENTY TWO GROUP |
| | TEL: (772)528-7241 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. NOV. 07/2014 |
| | ACTION: DENIED |
| | |
| | 1) SKETCH ASK-1 INDICATES A TYPICAL SOFFIT DETAIL |
| | PLEASE PROVIDE WHERE THIS SOFFIT IS LOCATED ON SHEET |
| | A111.00. DEPENDING WHERE THIS SOFFIT IS TO BE LOCATED, |
| | THERE WOULD BE DIFFERENT FASTENERS REQUIRED. THE ASK-1 |
| | DETAIL DOES NOT PROVIDE HOW FAR THE SOFFIT IS TO DROP |
| | WIDTH OR LENGTH OF THE SOFFIT., WHAT THE CLEAR HEIGHT |
| | IS UNDER THIS SOFFIT,NOR IF EXIT LIGHTS OR DIRECTIONS |
| | ARE BLOCKED BY THE SOFFIT. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | THE CEILING/ FLOOR ASSEMBLY IS A FIRE RATED ASSEMBLY |
| | SINCE THERE IS A SECOND STORY, DOES THE EXISTING FLOOR/ |
| | CEILING ASSEMBLY STILL CREATE THE HORIZONTAL FIRE |
| | BARRIER REQUIRED BY 707.3.9. |
| | |
| | 2A) ASK 2 & 3 BOTH OF THESE DETAILS ARE FOR A TYPICAL |
| | CHAIR DISPLAY. AGAIN THE SKETCHES DO NOT INDICATE WHERE |
| | THEY ARE TO BE INSTALLED WITHIN THE TENANT SPACE. SHEET |
| | A113.00 IT APPEARS THIS DISPLAY IS ON THE SOUTH WALL |
| | WHICH IS A 1 HOUR TENANT SEPARATION WALL. IF THIS IS |
| | THE CASE PLEASE PROVIDE THE WALL ASSEMBLY THAT ALLOWS |
| | THE DRYWALL TO BE REMOVED FROM THE ASSEMBLY AND A METAL |
| | STUD OR PLATE INSERTED INTO THE CAVITY. |
| | 2010 FBC-B 709.1(6). / 709.3 FIRE-RESISTANCE RATING. |
| | FIRE PARTITIONS SHALL HAVE A FIRE-RESISTANCE RATING OF |
| | NOT LESS THAN 1 HOUR. |
| | 709.8 JOINTS. JOINTS MADE IN OR BETWEEN FIRE PARTITIONS |
| | SHALL COMPLY WITH SECTION 714. |
| | 714.1 GENERAL. JOINTS INSTALLED IN OR BETWEEN |
| | FIRE-RESISTANCE-RATED WALLS, FLOOR OR FLOOR/CEILING |
| | ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL |
| | BE PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM |
| | DESIGNED TO RESIST THE PASSAGE OF FIRE FOR A TIME |
| | PERIOD NOT LESS THAN THE REQUIRED FIRE-RESISTANCE |
| | RATING OF THE WALL, FLOOR OR ROOF IN OR BETWEEN WHICH |
| | IT IS INSTALLED. FIRE-RESISTANT JOINT SYSTEMS SHALL BE |
| | TESTED IN ACCORDANCE WITH SECTION 714.3. THE VOID |
| | CREATED AT THE INTERSECTION OF A FLOOR/CEILING ASSEMBLY |
| | AND AN EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 714.4. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |