| 2014-12-08 12:13:25 | 12/8/2014 |
| | PROJECT: TENANT IMPROVEMENTS, PP STE1000 |
| | PERMIT#: 14101018 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION |
| | |
| | 1) NEC 240.4 CLARIFICATION REQUIRED. SHEET E1.1 |
| | INDICATES A TWO POLE 30AMP CIRCUIT #27/29 WITH TWO #8CU |
| | FEEDING CU-10E-9 LOCATED ON THE ROOF. HOWEVER, |
| | ELECTRICAL KEYNOTE 1 ON THE SAME SHEET STATES CONNECT |
| | CU-10E-9 TO AHU-10E-9 USING TWO #12 1#12G IN 1/2" |
| | CONDUIT. PLEASE INDICATE WHERE, HOW AND WITH WHAT TYPE, |
| | SIZE AND STYLE OF OCPD PROTECT THE #12 CIRCUIT FROM THE |
| | CU-10E-9 TO AHU-10E-9. |
| | |
| | 2) NEC 314.27(C ) BOXES LISTED SPECIFICALLY FOR THIS |
| | APPLICATION SHALL BE USED FOR RECEPTACLES LOCATED IN |
| | THE FLOOR. PROVIDE MANUFACTURER'S SPECIFICATION DATA |
| | SHEETS FOR THE OUTLETS LOCATED IN THE FLOOR. |
| | A. NEC 300.21 PROVIDE A FIRE STOP DETAIL FOR ALL WALL |
| | AND FLOOR PENETRATIONS OF FIRE RATED ASSEMBLIES. |
| | B. FBC 713.4 PENETRATIONS OF A FLOOR, FLOOR/CEILING |
| | ASSEMBLY OR THE CEILING MEMBRANE OF A ROOF/CEILING |
| | ASSEMBLY NOT REQUIRED TO BE ENCLOSED IN A SHAFT BY |
| | SECTION 708.2 SHALL BE PROTECTED IN ACCORDANCE WITH |
| | SECTIONS 713.4.1 THROUGH 713.4.2.2. |
| | |
| | 3) FBC 505.2.2 EX 4.SPACES WHERE AN AUTOMATIC SHUTOFF |
| | WOULD ENDANGER OCCUPANT SAFETY OR SECURITY. ELECTRICAL |
| | ROOM LIGHTS SHOULD NOT BE CONNECTED TO A MOTION SENSOR |
| | SWITCH. |
| | |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR FIRE ALARM, ACCESS CONTROL SYSTEM, |
| | SECURITY, CCTV, NETWORK, DATA, COMMUNICATION, SITE |
| | LIGHTING, AND GENERATORS. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |