Plan Review Details - Permit 14101015
| Plan Review Stops For Permit 14101015 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2014-12-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-12-02 |
Time |
07:25 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-12-02 |
Time |
06:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2014-11-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-11-17 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-11-17 |
Time |
07:31 |
Sent To |
|
|
| Notes |
| 2014-11-17 08:35:03 | BUILDING PLAN REVIEW | | | PERMIT: 14101015 | | | ADD: 1808 S. AUSTRALIAN AVE. | | | CONT: ACCENT CONSTRUCTION SERVICES | | | TEL: (941)270-1373 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: MON. NOV. 17/2014 | | | ACTION: DENIED | | | | | | 2ND REQUEST 1) THE TITLEBLOCK OF THE PLANS THE ARCHITEC | | | OF RECORD HAS COPIED SIGNATURES NOT ORIGINALS. | | | PLANS ARE TO BE SIGNED PERSONALLY WITH A FULL SIGNATURE | | | FROM THE ARCHETECT OF RECORD PER 481.221 WITH A MINIMUM | | | OF FIRST AND LAST NAME AS SHOWN ON THE ARCHITECTS' | | | LICENSE, FAC 61G1-16.003 | | | NOTICE: | | | CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A | | | LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE | | | FEE TO THE DESIGNERS OF RECORD FOR PLAN REVIEW, IF | | | PLANS ARE REJECTED (3) OR MORE TIMES FOR REPEATED | | | FAILURE TO CORRECT A CODE VIOLATION. | | | | | | | | | | | | | | | 2) COMPLIED. | | | THE D1.1 SHEET DEMOLITION NOTE # 5 INDICATES AN | | | ALTERNATE BID,( NO EITHER / OR) FOR NEW AUTOMATIC | | | SLIDDING ENTRY DOORS. PLEASE REVIEW 2010 WEST PALM | | | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER | | | 1, ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE | | | TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN | | | PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE | | | USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION. | | | | | | 3)SEMI- COMPLIED. THE TITLE PAGE DOES NOT LIST A LIFE | | | SAFETY SHEET, SHEET A1.1 THE 1ST FLOOR RENOVATION PLANS | | | INDICATE ROOM NUMBERS, USAGE OF ROOMS, THE PLANS DO NOT | | | SHOW EGRESS ROUTES FROM THE ROOMS, NO OCCUPANT LOADS, | | | FIRE SPRINKLERS, NO EMERGENCY LIGHTS NOR DIRECTIONAL OR | | | EXIT LIGHTS. | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | | | | BUILDING TYPE; NOTE LISTED AS A IB (SHEET A0.1) | | | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: | | | FIRE RATING OF WALLS - SHEET A1.1 LIST GUEST ROOM | | | COORIDOR KEY NOTE # 1 AS A 1/2 HR FIRE RATED CORRIDOR. | | | PLEASE REVIEW THE 2010 FBC-B 709.3 EXC. 2. 1/2 HOUR | | | RATED COORIDORS ARE FOR BUILDING TYPE IIB, IIIB & VB. | | | THIS BUILDING IS IDENTIFIED AS A TYPE IB. | | | MEANS OF EGRESS | | | EXIT ACCESS | | | EXIT | | | EXIT DISCHARGE | | | FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:EARLY WARNING | | | SMOKE EVACUATION SYSTEMS/ SCHEMATIC FIRE SPRINKLERS | | | INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: | | | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) | | | LIGHT AND VENTILATION | | | | | | 4) 2ND REQUEST. THE A2.1 THE GUEST ROOM CORRIDOR DOES | | | NOT SHOW AS A RATED CORRIDOR FBC-B TABLE 1018.1.- SHEET | | | A1.1 LIST GUEST ROOM COORIDOR KEY NOTE # 1 AS A 1/2 HR | | | FIRE RATED CORRIDOR. PLEASE REVIEW THE 2010 FBC-B 709.3 | | | EXC. 2. 1/2 HOUR RATED COORIDORS ARE FOR BUILDING TYPE | | | IIB, IIIB & VB. THIS BUILDING IS IDENTIFIED AS A TYPE | | | IB. | | | | | | 5-8 ) COMPLIED. SHEET A2.1. THE GUEST ROOM CORRIDOOR | | | DOOR # 1031 DOES NOT SHOW ON THE DOOR SCHEDULE AND | | | SHOULD ALSO BE RATED FBC-B TABLE 715.4. | | | | | | 9) NEW COMMENT. SHEET A1.1 SHOWS (2) MEANS OF EGRESS | | | FROM 1008, THE SQ. FT. OF THE ROOM IS 734 FT./ 15 = 49 | | | OCCUPANTS. THIS ROOM WILL ONLY REQUIRE ONE EXIT. NOTE | | | THE 2ND EXIT SHOWN WITH EXIT DIRECTIONAL LIGHT IS | | | TAKING THE OCCUPANTS THROUGH THE STORAGE ROOM # 1008A. | | | PLEASE REVIEW THE 2010 FBC-B 1014.2 EGRESS THROUGH | | | INTERVENING SPACES. | | | EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH | | | THIS SECTION. | | | 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE | | | ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES. | | | | | | 10) NEW COMMENT. FOYER TO BOARD ROOM DOES NOT SHOW FIRE | | | SPRINKLERS, THERE ARE DOORS BETWEEN THE FOYER AND | | | COORIDOR AND A DROPPED HEADER BETWEEN THE FOYER ITSELF | | | AND THE BOARD ROOM. [F] 903.2.8 GROUP R. | | | AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE | | | WITH SECTION 903.3 SHALL BE PROVIDED THROUGHOUT ALL | | | BUILDINGS WITH A GROUP R FIRE AREA. | | | | | | | | | | | | TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA | | | TUS.ASPX FOR PERMIT STATUS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-11-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-11-06 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-11-06 |
Time |
07:01 |
Sent To |
|
|
| Notes |
| 2014-11-06 08:39:20 | BUILDING PLAN REVIEW | | | PERMIT: 14101015 | | | ADD: 1808 S. AUSTRALIAN AVE. | | | CONT: ACCENT CONSTRUCTION SERVICES | | | TEL: (941)270-1373 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: THURS. NOV. 05/2014 | | | ACTION: DENIED | | | | | | 1) THE TITLEBLOCK OF THE PLANS THE ARCHITEC OF RECORD | | | HAS COPIED SIGNATURES NOT ORIGINALS. | | | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR | | | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE | | | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. | | | FL ADMIN CODE 61G16.003 ARCHITECTS | | | | | | 2) THE D1.1 SHEET DEMOLITION NOTE # 5 INDICATES AN | | | ALTERNATE BID,( NO EITHER / OR) FOR NEW AUTOMATIC | | | SLIDDING ENTRY DOORS. PLEASE REVIEW 2010 WEST PALM | | | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER | | | 1, ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE | | | TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN | | | PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE | | | USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION. | | | | | | 3) THE TITLE PAGE DOES NOT LIST A LIFE SAFETY SHEET, | | | SHEET A2.1 THE 1ST FLOOR RENOVATION PLANS INDICATE ROOM | | | NUMBERS, USAGE OF ROOMS, THE PLANS DO NOT SHOW EGRESS | | | ROUTES FROM THE ROOMS, NO OCCUPANT LOADS, FIRE | | | SPRINKLERS, NO EMERGENCY LIGHTS NOR DIRECTIONAL OR EXIT | | | LIGHTS. | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: | | | FIRE RATING OF WALLS | | | OCCUPANCY LOAD | | | GROSS | | | NET | | | MEANS OF EGRESS | | | EXIT ACCESS | | | EXIT | | | EXIT DISCHARGE | | | FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:EARLY WARNING | | | SMOKE EVACUATION SYSTEMS/ SCHEMATIC FIRE SPRINKLERS | | | INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: | | | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) | | | LIGHT AND VENTILATION | | | | | | 4) THE A2.1 THE GUEST ROOM CORRIDOR DOES NOT SHOW AS A | | | RATED CORRIDOR FBC-B TABLE 1018.1. | | | | | | 5) SHEET A2.1. THE GUEST ROOM CORRIDOOR DOOR # 1031 | | | DOES NOT SHOW ON THE DOOR SCHEDULE AND SHOULD ALSO BE | | | RATED FBC-B TABLE 715.4. | | | | | | 6) SHEET A2.1 THE ELEVATOR EQUIPMENT ROOM AND DOOR ARE | | | MISSING THE FIRE RATINS AS REQUIRED BY FBC-B 3006.4. | | | | | | 7) SHEET A.2.1 BOTH STAIRWELL 2 & 3 APPEAR TO BE IN THE | | | WORK AREA ZONE OF WORK, THEY ARE 2 HR FIRE RATED WALLS | | | WITH 1 1/2 OPENING PROTECTIVES FBC-B 1022.1. | | | | | | 8A) SHEET A2.1 THE PLANS SHOW A HOUSE LAUNDRY, FBC-B | | | TABLE 508.2.5 DOES ALLOW FOR THE WALL TO BE SMOKE TIGHT | | | CONSTRUCTION WHICH WILL REQUIRE COMPLIANCE WITH 711.4 | | | CONTINUITY. | | | | | | 8B) NOTE THE LAUNDRY ROOM DOES NOT INDICATE IF THERE IS | | | A LAUNDRY CHUTE THAT ENDS IN THIS ROOM, IF SO THIS ROOM | | | IS THEN A TERMINATION ROOM AND WOULD NEED TO COMPLY | | | WITH FBC-B 708.13.4. | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA | | | TUS.ASPX FOR PERMIT STATUS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2014-12-04 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-12-03 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-12-03 |
Time |
13:53 |
Sent To |
|
|
| Notes |
| 2014-12-03 15:37:03 | 12/3/2014 | | | PROJECT: DOUBLETREE RENOVATION | | | PERMIT#: 14101015 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: APPROVED WITH EXCEPTION | | | | | | 1) PROVIDE A LOAD CALCULATION FOR PANEL MDP. TOTAL | | | CONNECTED LOAD IS NOT INDICATED AND HAS BEEN ALTERED | | | DUE TO THE ADDING OF PANEL LC-1 AND LC-2. FBC 107.3.5 | | | | | | 2) PROVIDE A LOAD CALCULATION FOR PANEL LDP. TOTAL | | | CONNECTED LOAD IS NOT INDICATED AND HAS BEEN ALTERED | | | DUE TO THE ADDING OF PANEL LC-1 FROM PANEL LC. FBC | | | 107.3.5 | | | | | | 3) VERIFY 2000AMP MAIN IN PANEL MDP HAS GROUND FAULT | | | PROTECTION. NEC 230.95 | | | | | | 4) VERIFY SIZE OF MAIN OCPD IN NEW PANEL LC-1. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2014-11-21 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-11-21 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-11-21 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2014-11-21 16:15:44 | 11/21/2014 | | | PROJECT: DOUBLETREE INTERIOR RENNOVATION | | | PERMIT#: 14101015 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | DUPLICATE COMMENTS | | | | | | 1) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN | | | SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY | | | CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 | | | | | | 2) PROVIDE AUTOMATIC LIGHTING CONTROL PER THE FBC 505.2 | | | | | | 3) PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH | | | PROTECTION FOR THE SERVICE, PANEL BOARDS AND MAIN | | | DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22 | | | | | | 4) PROVIDE AN ACTUAL LOAD CALCULATION IN ACCORDANCE | | | WITH THE NEC ARTICLE 220. IF THE LOCAL UTILITY IS GOING | | | TO BE REFFERENCED AS AN ALTERNATIVE TO A LOAD | | | CALCULATION A LETTER FROM AN AUTHORIZED RERESENTITIVE | | | OF THE LOCAL UTILITY WILL BE REQUIRED INDICATING A FULL | | | 12 MONTHS OF USE. | | | | | | 5) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED | | | MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND | | | ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE | | | REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL | | | BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY | | | INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF | | | A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT | | | REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 | | | REVISE OLANS TO INCLUDE A LIFE SAFETY PLAN TO DETERMINE | | | THE REQUIRED EMERGENCY ILLUMINATION FOR THE MEANS OF | | | EGRESS. | | | A) THE BRANCH CIRCUIT FEEDING THE EMEGENCY /EXIT | | | LIGHTING SHALL BE THE SAME BRANCH CIRCUIT AS THAT | | | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED | | | AHEAD OF ANY LOCAL SWITCHES. THE BRANCH CIRCUIT THAT | | | FEEDS EMERGENCY/EXIT LIGHTS SHALL BE CLEARLY IDENTIFIED | | | AT THE DISTRIBUTION PANEL. | | | | | | 6A) WHERE WALLS OR PARTITIONS ARE REQUIRED TO HAVE A | | | FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE | | | INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE WILL | | | NOT BE REDUCED. FBC 713.3.2 | | | VERIFY FIRE RATED FLOORS AND WALLS PENETRATED BY | | | ELECTRICAL OUTLETS CONDUITS OR CABLES SHALL BE "SHALL | | | BE INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE | | | WILL NOT BE REDUCED". FBC 713.3.2 | | | B) PENETRATIONS OF THE FIRE-RESISTANCE-RATED FLOOR, | | | FLOOR/CEILING ASSEMBLY OR THE CEILING MEMBRANE OF A | | | ROOF/CEILING ASSEMBLY SHALL COMPLY WITH SECTIONS | | | 713.4.1.1 THROUGH 713.4.1.4. PENETRATIONS IN HORIZONTAL | | | SMOKE BARRIERS SHALL ALSO COMPLY WITH 713.5. FBC | | | 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES. | | | | | | 7) PROVIDE MANUFACTURER DATA SHEETS FOR PROPOSED FLOOR | | | BOXES TO INDICATE THE REQUIRED LISTING FOR THE | | | EVIRONMENT IN WHICH THEY ARE INSTALLED. NEC110.3 FBC | | | 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES. | | | | | | 8) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS | | | TO FBC 107.2.1 | | | | | | A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY | | | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS | | | REQUIRED FOR FIRE ALARM, SECURITY, CCTV, ACCESS CONTROL | | | SYSTEMS, AUDIO/VIDEO, ETC.. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-11-07 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-11-07 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-11-07 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2014-11-07 11:52:46 | 11/7/2014 | | | PROJECT: DOUBLETREE INTERIOR RENNOVATION | | | PERMIT#: 14101015 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN | | | SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY | | | CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 | | | | | | 2) PROVIDE AUTOMATIC LIGHTING CONTROL PER THE FBC 505.2 | | | | | | 3) PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH | | | PROTECTION FOR THE SERVICE, PANEL BOARDS AND MAIN | | | DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22 | | | | | | 4) PROVIDE AN ACTUAL LOAD CALCULATION IN ACCORDANCE | | | WITH THE NEC ARTICLE 220. IF THE LOCAL UTILITY IS GOING | | | TO BE REFFERENCED AS AN ALTERNATIVE TO A LOAD | | | CALCULATION A LETTER FROM AN AUTHORIZED RERESENTITIVE | | | OF THE LOCAL UTILITY WILL BE REQUIRED INDICATING A FULL | | | 12 MONTHS OF USE. | | | | | | 5) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED | | | MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND | | | ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE | | | REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL | | | BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY | | | INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF | | | A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT | | | REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 | | | REVISE OLANS TO INCLUDE A LIFE SAFETY PLAN TO DETERMINE | | | THE REQUIRED EMERGENCY ILLUMINATION FOR THE MEANS OF | | | EGRESS. | | | A) THE BRANCH CIRCUIT FEEDING THE EMEGENCY /EXIT | | | LIGHTING SHALL BE THE SAME BRANCH CIRCUIT AS THAT | | | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED | | | AHEAD OF ANY LOCAL SWITCHES. THE BRANCH CIRCUIT THAT | | | FEEDS EMERGENCY/EXIT LIGHTS SHALL BE CLEARLY IDENTIFIED | | | AT THE DISTRIBUTION PANEL. | | | | | | 6A) WHERE WALLS OR PARTITIONS ARE REQUIRED TO HAVE A | | | FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE | | | INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE WILL | | | NOT BE REDUCED. FBC 713.3.2 | | | VERIFY FIRE RATED FLOORS AND WALLS PENETRATED BY | | | ELECTRICAL OUTLETS CONDUITS OR CABLES SHALL BE "SHALL | | | BE INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE | | | WILL NOT BE REDUCED". FBC 713.3.2 | | | B) PENETRATIONS OF THE FIRE-RESISTANCE-RATED FLOOR, | | | FLOOR/CEILING ASSEMBLY OR THE CEILING MEMBRANE OF A | | | ROOF/CEILING ASSEMBLY SHALL COMPLY WITH SECTIONS | | | 713.4.1.1 THROUGH 713.4.1.4. PENETRATIONS IN HORIZONTAL | | | SMOKE BARRIERS SHALL ALSO COMPLY WITH 713.5. FBC | | | 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES. | | | | | | 7) PROVIDE MANUFACTURER DATA SHEETS FOR PROPOSED FLOOR | | | BOXES TO INDICATE THE REQUIRED LISTING FOR THE | | | EVIRONMENT IN WHICH THEY ARE INSTALLED. NEC110.3 FBC | | | 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES. | | | | | | 8) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS | | | TO FBC 107.2.1 | | | | | | A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY | | | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS | | | REQUIRED FOR FIRE ALARM, SECURITY, CCTV, ACCESS CONTROL | | | SYSTEMS, AUDIO/VIDEO, ETC.. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2014-12-04 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2014-12-04 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2014-12-04 |
Time |
11:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2014-11-18 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2014-11-18 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2014-11-18 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2014-11-18 16:27:21 | PERMIT # 14101015 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FAILED: | | | DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE | | | FIRE DEPARTMENT AFTER ALL BUILDING PLAN REVIEWER | | | COMMENTS HAVE BEEN SATISFIED. | | | | | | | | | SUE ELLEN CALDERON | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 644-7326 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2014-11-03 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2014-11-03 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2014-11-03 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2014-11-03 11:54:51 | PERMIT #14101015 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FAILED COMMENTS: | | | 1) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION | | | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND | | | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION | | | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A | | | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A | | | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED | | | BY EMAIL ([email protected]) OR IN WRITING (FAX: | | | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE | | | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? | | | | | | 2) ENGINEERED FIRE ALARM AND FIRE SPRINKLER | | | CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL | | | BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN | | | ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP | | | DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION | | | DOCUMENTS) FOR A SUB-PERMIT. * SHEETS FP-1 & FP-2 SHOW | | | DETAILS FOR SPRINKLER SYSTEM ONLY. | | | | | | 3) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY | | | TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, | | | EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF | | | TRAVEL ETC. | | | | | | 4) EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS | | | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A | | | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. | | | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF | | | OCCUPANTS PERMITTED FOR EACH ROOM. | | | | | | | | | | | | SUE ELLEN CALDERON | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 644-7326 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-12-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-12-05 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-11-26 |
Time |
17:03 |
Sent To |
|
|
| Notes |
| 2014-11-26 17:04:17 | SENT TO C4 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-11-22 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-11-22 |
Time |
05:08 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-11-14 |
Time |
09:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-11-13 |
Time |
16:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2014-12-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-12-05 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-12-05 |
Time |
10:53 |
Sent To |
|
|
| Notes |
| 2014-11-26 17:00:18 | NEW SHEETS SUBMITTED. JG. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2014-11-13 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-11-13 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-11-13 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2014-11-13 14:16:40 | PASS PROVISO | | | PROVIDE NOA FOR ALL OUTSIDE LUVERS AT BUILDING | | | NEXT REVIEW. | | | | | | REFER TO SECTION 1107.2.1 FBC (M) 2010 | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2014-12-04 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-12-04 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-12-04 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2014-11-26 16:59:56 | NEW SHEETS SUBMITTED. JG. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2014-11-22 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-11-22 |
Time |
05:07 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-11-22 |
Time |
04:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2014-11-02 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-11-02 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-11-02 |
Time |
08:58 |
Sent To |
|
|
| Notes |
| 2014-11-02 09:51:40 | 1) SHT. A0.2 - MOUNTING HEIGHTS - SHOWS VERTICAL GRAB | | | BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL | | | POSITION PER THE FL. ACCESS. CODE SEC.609.4. | | | 2) SUBMIT THE OCCUPANT LOAD FOR THE COMMON AREAS OF THE | | | FIRST FLOOR TO ENSURE THE REDUCTION OF THE PLUMBING | | | FIXTURES WILL NOT CREATE A VIOLATION OF THE MINIMUM | | | REQUIRED PLUMBING FIXTURES PER TABLE 403.1 OF THE FPC. | | | 3) THE DRINKING FOUNTAINS SHALL BE ACCESSIBLE TO THE | | | PUBLIC AT ALL TIMES THAT THE BUILDING IS OCCUPIED. THE | | | DRINKING FOUNTAINS SHALL BE LOCATED TO AN AREA THAT | | | WILL PROVIDE ACCESS.FPC SEC. 403.3.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
|