Plan Review Details - Permit 14101015
Plan Review Stops For Permit 14101015
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-12-02 Cont ID  
Sent By jwitmer Date 2014-12-02 Time 07:25 Rev Time 0.00
Received By jwitmer Date 2014-12-02 Time 06:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-11-17 Cont ID  
Sent By jwitmer Date 2014-11-17 Time 08:35 Rev Time 0.00
Received By jwitmer Date 2014-11-17 Time 07:31 Sent To  
Notes
2014-11-17 08:35:03BUILDING PLAN REVIEW
 PERMIT: 14101015
 ADD: 1808 S. AUSTRALIAN AVE.
 CONT: ACCENT CONSTRUCTION SERVICES
 TEL: (941)270-1373
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. NOV. 17/2014
 ACTION: DENIED
  
 2ND REQUEST 1) THE TITLEBLOCK OF THE PLANS THE ARCHITEC
 OF RECORD HAS COPIED SIGNATURES NOT ORIGINALS.
 PLANS ARE TO BE SIGNED PERSONALLY WITH A FULL SIGNATURE
 FROM THE ARCHETECT OF RECORD PER 481.221 WITH A MINIMUM
 OF FIRST AND LAST NAME AS SHOWN ON THE ARCHITECTS'
 LICENSE, FAC 61G1-16.003
 NOTICE:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A
 LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE
 FEE TO THE DESIGNERS OF RECORD FOR PLAN REVIEW, IF
 PLANS ARE REJECTED (3) OR MORE TIMES FOR REPEATED
 FAILURE TO CORRECT A CODE VIOLATION.
  
  
  
  
 2) COMPLIED.
 THE D1.1 SHEET DEMOLITION NOTE # 5 INDICATES AN
 ALTERNATE BID,( NO EITHER / OR) FOR NEW AUTOMATIC
 SLIDDING ENTRY DOORS. PLEASE REVIEW 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION.
  
 3)SEMI- COMPLIED. THE TITLE PAGE DOES NOT LIST A LIFE
 SAFETY SHEET, SHEET A1.1 THE 1ST FLOOR RENOVATION PLANS
 INDICATE ROOM NUMBERS, USAGE OF ROOMS, THE PLANS DO NOT
 SHOW EGRESS ROUTES FROM THE ROOMS, NO OCCUPANT LOADS,
 FIRE SPRINKLERS, NO EMERGENCY LIGHTS NOR DIRECTIONAL OR
 EXIT LIGHTS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
  
 BUILDING TYPE; NOTE LISTED AS A IB (SHEET A0.1)
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 FIRE RATING OF WALLS - SHEET A1.1 LIST GUEST ROOM
 COORIDOR KEY NOTE # 1 AS A 1/2 HR FIRE RATED CORRIDOR.
 PLEASE REVIEW THE 2010 FBC-B 709.3 EXC. 2. 1/2 HOUR
 RATED COORIDORS ARE FOR BUILDING TYPE IIB, IIIB & VB.
 THIS BUILDING IS IDENTIFIED AS A TYPE IB.
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:EARLY WARNING
 SMOKE EVACUATION SYSTEMS/ SCHEMATIC FIRE SPRINKLERS
 INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
  
 4) 2ND REQUEST. THE A2.1 THE GUEST ROOM CORRIDOR DOES
 NOT SHOW AS A RATED CORRIDOR FBC-B TABLE 1018.1.- SHEET
 A1.1 LIST GUEST ROOM COORIDOR KEY NOTE # 1 AS A 1/2 HR
 FIRE RATED CORRIDOR. PLEASE REVIEW THE 2010 FBC-B 709.3
 EXC. 2. 1/2 HOUR RATED COORIDORS ARE FOR BUILDING TYPE
 IIB, IIIB & VB. THIS BUILDING IS IDENTIFIED AS A TYPE
 IB.
  
 5-8 ) COMPLIED. SHEET A2.1. THE GUEST ROOM CORRIDOOR
 DOOR # 1031 DOES NOT SHOW ON THE DOOR SCHEDULE AND
 SHOULD ALSO BE RATED FBC-B TABLE 715.4.
  
 9) NEW COMMENT. SHEET A1.1 SHOWS (2) MEANS OF EGRESS
 FROM 1008, THE SQ. FT. OF THE ROOM IS 734 FT./ 15 = 49
 OCCUPANTS. THIS ROOM WILL ONLY REQUIRE ONE EXIT. NOTE
 THE 2ND EXIT SHOWN WITH EXIT DIRECTIONAL LIGHT IS
 TAKING THE OCCUPANTS THROUGH THE STORAGE ROOM # 1008A.
 PLEASE REVIEW THE 2010 FBC-B 1014.2 EGRESS THROUGH
 INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
  
 10) NEW COMMENT. FOYER TO BOARD ROOM DOES NOT SHOW FIRE
 SPRINKLERS, THERE ARE DOORS BETWEEN THE FOYER AND
 COORIDOR AND A DROPPED HEADER BETWEEN THE FOYER ITSELF
 AND THE BOARD ROOM. [F] 903.2.8 GROUP R.
 AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE
 WITH SECTION 903.3 SHALL BE PROVIDED THROUGHOUT ALL
 BUILDINGS WITH A GROUP R FIRE AREA.
  
  
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-06 Cont ID  
Sent By jwitmer Date 2014-11-06 Time 08:39 Rev Time 0.00
Received By jwitmer Date 2014-11-06 Time 07:01 Sent To  
Notes
2014-11-06 08:39:20BUILDING PLAN REVIEW
 PERMIT: 14101015
 ADD: 1808 S. AUSTRALIAN AVE.
 CONT: ACCENT CONSTRUCTION SERVICES
 TEL: (941)270-1373
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. NOV. 05/2014
 ACTION: DENIED
  
 1) THE TITLEBLOCK OF THE PLANS THE ARCHITEC OF RECORD
 HAS COPIED SIGNATURES NOT ORIGINALS.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 2) THE D1.1 SHEET DEMOLITION NOTE # 5 INDICATES AN
 ALTERNATE BID,( NO EITHER / OR) FOR NEW AUTOMATIC
 SLIDDING ENTRY DOORS. PLEASE REVIEW 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION.
  
 3) THE TITLE PAGE DOES NOT LIST A LIFE SAFETY SHEET,
 SHEET A2.1 THE 1ST FLOOR RENOVATION PLANS INDICATE ROOM
 NUMBERS, USAGE OF ROOMS, THE PLANS DO NOT SHOW EGRESS
 ROUTES FROM THE ROOMS, NO OCCUPANT LOADS, FIRE
 SPRINKLERS, NO EMERGENCY LIGHTS NOR DIRECTIONAL OR EXIT
 LIGHTS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 FIRE RATING OF WALLS
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:EARLY WARNING
 SMOKE EVACUATION SYSTEMS/ SCHEMATIC FIRE SPRINKLERS
 INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
  
 4) THE A2.1 THE GUEST ROOM CORRIDOR DOES NOT SHOW AS A
 RATED CORRIDOR FBC-B TABLE 1018.1.
  
 5) SHEET A2.1. THE GUEST ROOM CORRIDOOR DOOR # 1031
 DOES NOT SHOW ON THE DOOR SCHEDULE AND SHOULD ALSO BE
 RATED FBC-B TABLE 715.4.
  
 6) SHEET A2.1 THE ELEVATOR EQUIPMENT ROOM AND DOOR ARE
 MISSING THE FIRE RATINS AS REQUIRED BY FBC-B 3006.4.
  
 7) SHEET A.2.1 BOTH STAIRWELL 2 & 3 APPEAR TO BE IN THE
 WORK AREA ZONE OF WORK, THEY ARE 2 HR FIRE RATED WALLS
 WITH 1 1/2 OPENING PROTECTIVES FBC-B 1022.1.
  
 8A) SHEET A2.1 THE PLANS SHOW A HOUSE LAUNDRY, FBC-B
 TABLE 508.2.5 DOES ALLOW FOR THE WALL TO BE SMOKE TIGHT
 CONSTRUCTION WHICH WILL REQUIRE COMPLIANCE WITH 711.4
 CONTINUITY.
  
 8B) NOTE THE LAUNDRY ROOM DOES NOT INDICATE IF THERE IS
 A LAUNDRY CHUTE THAT ENDS IN THIS ROOM, IF SO THIS ROOM
 IS THEN A TERMINATION ROOM AND WOULD NEED TO COMPLY
 WITH FBC-B 708.13.4.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-12-04 Cont ID  
Sent By dhayes Date 2014-12-03 Time 15:37 Rev Time 0.00
Received By dhayes Date 2014-12-03 Time 13:53 Sent To  
Notes
2014-12-03 15:37:0312/3/2014
 PROJECT: DOUBLETREE RENOVATION
 PERMIT#: 14101015
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 1) PROVIDE A LOAD CALCULATION FOR PANEL MDP. TOTAL
 CONNECTED LOAD IS NOT INDICATED AND HAS BEEN ALTERED
 DUE TO THE ADDING OF PANEL LC-1 AND LC-2. FBC 107.3.5
  
 2) PROVIDE A LOAD CALCULATION FOR PANEL LDP. TOTAL
 CONNECTED LOAD IS NOT INDICATED AND HAS BEEN ALTERED
 DUE TO THE ADDING OF PANEL LC-1 FROM PANEL LC. FBC
 107.3.5
  
 3) VERIFY 2000AMP MAIN IN PANEL MDP HAS GROUND FAULT
 PROTECTION. NEC 230.95
  
 4) VERIFY SIZE OF MAIN OCPD IN NEW PANEL LC-1.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-11-21 Cont ID  
Sent By dhayes Date 2014-11-21 Time 16:14 Rev Time 0.00
Received By dhayes Date 2014-11-21 Time 16:14 Sent To  
Notes
2014-11-21 16:15:4411/21/2014
 PROJECT: DOUBLETREE INTERIOR RENNOVATION
 PERMIT#: 14101015
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 DUPLICATE COMMENTS
  
 1) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN
 SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 2) PROVIDE AUTOMATIC LIGHTING CONTROL PER THE FBC 505.2
  
 3) PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH
 PROTECTION FOR THE SERVICE, PANEL BOARDS AND MAIN
 DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22
  
 4) PROVIDE AN ACTUAL LOAD CALCULATION IN ACCORDANCE
 WITH THE NEC ARTICLE 220. IF THE LOCAL UTILITY IS GOING
 TO BE REFFERENCED AS AN ALTERNATIVE TO A LOAD
 CALCULATION A LETTER FROM AN AUTHORIZED RERESENTITIVE
 OF THE LOCAL UTILITY WILL BE REQUIRED INDICATING A FULL
 12 MONTHS OF USE.
  
 5) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED
 MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND
 ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE
 REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL
 BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY
 INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF
 A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT
 REQUIRES EMERGENCY ILLUMINATION. NEC 700.16
 REVISE OLANS TO INCLUDE A LIFE SAFETY PLAN TO DETERMINE
 THE REQUIRED EMERGENCY ILLUMINATION FOR THE MEANS OF
 EGRESS.
 A) THE BRANCH CIRCUIT FEEDING THE EMEGENCY /EXIT
 LIGHTING SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES. THE BRANCH CIRCUIT THAT
 FEEDS EMERGENCY/EXIT LIGHTS SHALL BE CLEARLY IDENTIFIED
 AT THE DISTRIBUTION PANEL.
  
 6A) WHERE WALLS OR PARTITIONS ARE REQUIRED TO HAVE A
 FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE
 INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE WILL
 NOT BE REDUCED. FBC 713.3.2
 VERIFY FIRE RATED FLOORS AND WALLS PENETRATED BY
 ELECTRICAL OUTLETS CONDUITS OR CABLES SHALL BE "SHALL
 BE INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE
 WILL NOT BE REDUCED". FBC 713.3.2
 B) PENETRATIONS OF THE FIRE-RESISTANCE-RATED FLOOR,
 FLOOR/CEILING ASSEMBLY OR THE CEILING MEMBRANE OF A
 ROOF/CEILING ASSEMBLY SHALL COMPLY WITH SECTIONS
 713.4.1.1 THROUGH 713.4.1.4. PENETRATIONS IN HORIZONTAL
 SMOKE BARRIERS SHALL ALSO COMPLY WITH 713.5. FBC
 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
  
 7) PROVIDE MANUFACTURER DATA SHEETS FOR PROPOSED FLOOR
 BOXES TO INDICATE THE REQUIRED LISTING FOR THE
 EVIRONMENT IN WHICH THEY ARE INSTALLED. NEC110.3 FBC
 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
  
 8) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1
  
 A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 REQUIRED FOR FIRE ALARM, SECURITY, CCTV, ACCESS CONTROL
 SYSTEMS, AUDIO/VIDEO, ETC..
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-11-07 Cont ID  
Sent By dhayes Date 2014-11-07 Time 11:52 Rev Time 0.00
Received By dhayes Date 2014-11-07 Time 09:30 Sent To  
Notes
2014-11-07 11:52:4611/7/2014
 PROJECT: DOUBLETREE INTERIOR RENNOVATION
 PERMIT#: 14101015
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN
 SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 2) PROVIDE AUTOMATIC LIGHTING CONTROL PER THE FBC 505.2
  
 3) PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH
 PROTECTION FOR THE SERVICE, PANEL BOARDS AND MAIN
 DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22
  
 4) PROVIDE AN ACTUAL LOAD CALCULATION IN ACCORDANCE
 WITH THE NEC ARTICLE 220. IF THE LOCAL UTILITY IS GOING
 TO BE REFFERENCED AS AN ALTERNATIVE TO A LOAD
 CALCULATION A LETTER FROM AN AUTHORIZED RERESENTITIVE
 OF THE LOCAL UTILITY WILL BE REQUIRED INDICATING A FULL
 12 MONTHS OF USE.
  
 5) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED
 MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND
 ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE
 REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL
 BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY
 INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF
 A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT
 REQUIRES EMERGENCY ILLUMINATION. NEC 700.16
 REVISE OLANS TO INCLUDE A LIFE SAFETY PLAN TO DETERMINE
 THE REQUIRED EMERGENCY ILLUMINATION FOR THE MEANS OF
 EGRESS.
 A) THE BRANCH CIRCUIT FEEDING THE EMEGENCY /EXIT
 LIGHTING SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES. THE BRANCH CIRCUIT THAT
 FEEDS EMERGENCY/EXIT LIGHTS SHALL BE CLEARLY IDENTIFIED
 AT THE DISTRIBUTION PANEL.
  
 6A) WHERE WALLS OR PARTITIONS ARE REQUIRED TO HAVE A
 FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE
 INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE WILL
 NOT BE REDUCED. FBC 713.3.2
 VERIFY FIRE RATED FLOORS AND WALLS PENETRATED BY
 ELECTRICAL OUTLETS CONDUITS OR CABLES SHALL BE "SHALL
 BE INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE
 WILL NOT BE REDUCED". FBC 713.3.2
 B) PENETRATIONS OF THE FIRE-RESISTANCE-RATED FLOOR,
 FLOOR/CEILING ASSEMBLY OR THE CEILING MEMBRANE OF A
 ROOF/CEILING ASSEMBLY SHALL COMPLY WITH SECTIONS
 713.4.1.1 THROUGH 713.4.1.4. PENETRATIONS IN HORIZONTAL
 SMOKE BARRIERS SHALL ALSO COMPLY WITH 713.5. FBC
 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
  
 7) PROVIDE MANUFACTURER DATA SHEETS FOR PROPOSED FLOOR
 BOXES TO INDICATE THE REQUIRED LISTING FOR THE
 EVIRONMENT IN WHICH THEY ARE INSTALLED. NEC110.3 FBC
 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
  
 8) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1
  
 A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 REQUIRED FOR FIRE ALARM, SECURITY, CCTV, ACCESS CONTROL
 SYSTEMS, AUDIO/VIDEO, ETC..
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2014-12-04 Cont ID  
Sent By scaldero Date 2014-12-04 Time 11:46 Rev Time 0.00
Received By scaldero Date 2014-12-04 Time 11:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-11-18 Cont ID  
Sent By scaldero Date 2014-11-18 Time 16:24 Rev Time 0.00
Received By scaldero Date 2014-11-18 Time 16:24 Sent To  
Notes
2014-11-18 16:27:21PERMIT # 14101015
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED:
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL BUILDING PLAN REVIEWER
 COMMENTS HAVE BEEN SATISFIED.
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-11-03 Cont ID  
Sent By scaldero Date 2014-11-03 Time 11:48 Rev Time 0.00
Received By scaldero Date 2014-11-03 Time 11:48 Sent To  
Notes
2014-11-03 11:54:51PERMIT #14101015
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
 1) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 2) ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. * SHEETS FP-1 & FP-2 SHOW
 DETAILS FOR SPRINKLER SYSTEM ONLY.
  
 3) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 4) EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-12-05 Cont ID  
Sent By jwitmer Date 2014-12-05 Time 10:53 Rev Time 0.00
Received By jwitmer Date 2014-11-26 Time 17:03 Sent To  
Notes
2014-11-26 17:04:17SENT TO C4 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-22 Cont ID  
Sent By tklarge Date 2014-11-22 Time 05:08 Rev Time 0.00
Received By tklarge Date 2014-11-14 Time 09:42 Sent To  
Notes
2014-11-15 09:42:22C12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2014-11-13 Time 16:26 Sent To  
Notes
2014-10-31 16:27:57C12
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-12-05 Cont ID  
Sent By jwitmer Date 2014-12-05 Time 10:53 Rev Time 0.00
Received By jwitmer Date 2014-12-05 Time 10:53 Sent To  
Notes
2014-11-26 17:00:18NEW SHEETS SUBMITTED. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-11-13 Cont ID  
Sent By hmoser Date 2014-11-13 Time 14:16 Rev Time 0.00
Received By hmoser Date 2014-11-13 Time 10:56 Sent To  
Notes
2014-11-13 14:16:40PASS PROVISO
 PROVIDE NOA FOR ALL OUTSIDE LUVERS AT BUILDING
 NEXT REVIEW.
  
 REFER TO SECTION 1107.2.1 FBC (M) 2010
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-12-04 Cont ID  
Sent By tklarge Date 2014-12-04 Time 09:06 Rev Time 0.00
Received By tklarge Date 2014-12-04 Time 09:06 Sent To  
Notes
2014-11-26 16:59:56NEW SHEETS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-11-22 Cont ID  
Sent By tklarge Date 2014-11-22 Time 05:07 Rev Time 0.00
Received By tklarge Date 2014-11-22 Time 04:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-02 Cont ID  
Sent By tklarge Date 2014-11-02 Time 09:51 Rev Time 0.00
Received By tklarge Date 2014-11-02 Time 08:58 Sent To  
Notes
2014-11-02 09:51:401) SHT. A0.2 - MOUNTING HEIGHTS - SHOWS VERTICAL GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION PER THE FL. ACCESS. CODE SEC.609.4.
 2) SUBMIT THE OCCUPANT LOAD FOR THE COMMON AREAS OF THE
 FIRST FLOOR TO ENSURE THE REDUCTION OF THE PLUMBING
 FIXTURES WILL NOT CREATE A VIOLATION OF THE MINIMUM
 REQUIRED PLUMBING FIXTURES PER TABLE 403.1 OF THE FPC.
 3) THE DRINKING FOUNTAINS SHALL BE ACCESSIBLE TO THE
 PUBLIC AT ALL TIMES THAT THE BUILDING IS OCCUPIED. THE
 DRINKING FOUNTAINS SHALL BE LOCATED TO AN AREA THAT
 WILL PROVIDE ACCESS.FPC SEC. 403.3.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  